How the user can control the ‘Start-up” voltage drop of the motor feeder in My Ecodial L.
FA135914
30 September 2021
My Ecodial L 3.4 enables the user to change or set the limit for “Start-up” voltage drop of the motor feeder circuit.
But the maximum value allowed by the Ecodial – to set the feeder startup voltage drop is 15 %. (The same is also supported by the UTE C 15-105 (French) standard.)
(Below figure is showing the circuit characteristics; and the place to set the limit for the start-up voltage drop).
![](https://pprodbfo22-secommunities.cs209.force.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008z10JQAQ&oid=00DA0000000abSm)