TeSys D Contactor 3P(3 NO) , AC-3 , <= 440V, 95A, 32V AC 50 Hz coil
Item Number: LC1D95C5
Specifications
Design
Range
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
[ie] rated operational current
- 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
- 125 A (at <60 °C) at <= 690 V AC-1 for power circuit
Mechanical durability
Electrical durability
- 1.2 Mcycles 95 A AC-3
- 1.3 Mcycles 125 A AC-1
Connections - terminals
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
- power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end
- power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end
- power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end
- power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end
- power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end
- power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
Insulation resistance
Mounting support
- plate
- rail
Standards
- EN/IEC 60947-1
- EN/IEC 60947-4-1
- EN/IEC 60947-5-1
- UL 60947-4-1
- UL 60947-5-1
- CSA C22.2 No 60947-4-1
- CSA C22.2 No 60947-5-1
- GB/T 14048.4
Product certifications
- IECEE CB Scheme
- UL
- CSA
- CCC
- EAC
- LROS (Lloyds register of shipping)
- RINA
- BV
- DNV-GL
Ip degree of protection
Climatic withstand
Height
Width
Depth
Net weight
Others
Package 1 bare product quantity
Device short name
Contactor application
- motor control
- resistive load
Utilisation category
- AC-4
- AC-1
- AC-3
Poles description
[uc] control circuit voltage
Motor power kw
- 25 kW at 220...230 V AC 50 Hz (AC-3)
- 45 kW at 380...400 V AC 50 Hz (AC-3)
- 45 kW at 415...440 V AC 50 Hz (AC-3)
- 55 kW at 500 V AC 50 Hz (AC-3)
- 45 kW at 660...690 V AC 50 Hz (AC-3)
- 45 kW at 1000 V AC 50 Hz (AC-3)
Motor power hp
- 7.5 hp at 120 V AC 60 Hz for 1 phase motors
- 15 hp at 230/240 V AC 60 Hz for 1 phase motors
- 30 hp at 200/208 V AC 60 Hz for 3 phases motors
- 30 hp at 230/240 V AC 60 Hz for 3 phases motors
- 60 hp at 460/480 V AC 60 Hz for 3 phases motors
- 60 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility code
Pole contact composition
Contact compatibility
Protective cover
[ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 125 A (at 60 °C) for power circuit
Irms rated making capacity
- 1100 A at 440 V AC for power circuit conforming to IEC 60947
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
[icw] rated short-time withstand current
- 1100 A 40 °C - 1 s for power circuit
- 800 A 40 °C - 10 s for power circuit
- 400 A 40 °C - 1 min for power circuit
- 135 A 40 °C - 10 min for power circuit
- 140 A - 100 ms for signalling circuit
- 120 A - 500 ms for signalling circuit
- 100 A - 1 s for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 200 A gG at <= 690 V coordination type 1 for power circuit
- 160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
Power dissipation per pole
- 12.5 W AC-1
- 7.2 W AC-3
[ui] rated insulation voltage
- power circuit: 1000 V conforming to IEC 60947-4-1
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- signalling circuit: 690 V conforming to IEC 60947-1
- signalling circuit: 600 V CSA certified
- signalling circuit: 600 V UL certified
Overvoltage category
Pollution degree
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.3...0.6 Uc (-40-70 °C):drop-out AC 50 Hz
- 0.85...1.1 Uc (-40-55 °C):operational AC 50 Hz
- 1...1.1 Uc (55-70 °C):operational AC 50 Hz
Inrush power in va
Hold-in power consumption in va
Heat dissipation
Operating time
- 20...35 ms closing
- 6...20 ms opening
Maximum operating rate
Tightening torque
- control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
- power circuit: 12 N.m - on connector hexagonal screw head 4 mm
Auxiliary contact composition
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
Minimum switching voltage
Minimum switching current
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Protective treatment
Permissible ambient air temperature around the device
- -60...80 °C storage
- -40...60 °C operation
- 60...70 °C with derating
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- shocks contactor open (8 Gn for 11 ms)
- vibrations contactor closed (3 Gn, 5...300 Hz)
- shocks contactor closed (10 Gn for 11 ms)
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight