Browse all
Browse all

Harmony Control Relays Modular 3 phase Voltage Control Relay 5A, 1CO, 208...480V AC

Home ProductsIndustrialHarmonyModular 3 phase Voltage Control Relay

Harmony Control Relays Modular 3 phase Voltage Control Relay 5A, 1CO, 208...480V AC

Item Number: RM17UB310

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product Harmony Control Relays
Product or component type 3-phase control relay
Warranty 18 months

Physical

Connections - terminals screw connectors
[in] rated current 5 A
Insulation resistance
  • > 500 MOhm at 500 V DC conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC conforming to IEC 60664-1
Local signalling
  • LED (green) for power ON
  • LED (yellow) for relay ON
Connections - terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Control type without test button
Width 17.5 mm
Net weight 0.08 kg
Ambient air temperature for operation -20...50 °C
Standards IEC 60255-1
Product certifications
  • GOST
  • UL
  • GL
  • C-Tick
  • CSA
Ambient air temperature for storage -40...70 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068...2-30
Ip degree of protection
  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1601001EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation X
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope Out
At least in Europe
Average percentage of recycled plastic content 0 %
Package 2 bare product quantity 48
Package 1 bare product quantity 1
Warranty duration(in months) bmecat 18
Weee label No
Relay type voltage control relay
Product specific application for 3-phase supply
Relay name RM17UB3
Relay monitored parameters overvoltage and undervoltage between phases
Time delay type adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
Switching capacity in va 1250 VA
Measurement range 220...480 V AC
Contacts type and composition 1 C/O
[uc] control circuit voltage 208...480 V
Reset time 1500 ms time delay
Maximum switching voltage 250 V AC/DC
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Supply voltage limits 183...528 V AC
Power consumption in va 0...22 VA at 400 V AC 50 Hz
Control circuit frequency 50...60 Hz +/- 10 %
Voltage detection threshold 183 V
Output contacts 1 C/O
Nominal output current 5 A
Hysteresis 2 %
Measurement accuracy +/- 10 % of the full scale value
Run-up delay at power-up 650 ms
Maximum measuring cycle 150 ms measurement cycle as true rms value
Threshold adjustment voltage
  • 2...20 % of Un selected
  • -2...-17 % in the range 220 V AC
  • +2...+10 % in the range 480 V AC
  • -2...-12 % in the range 208 V AC
Repeat accuracy
  • +/- 0.5 % for input and measurement circuit
  • +/- 1 % for time delay
Measurement error
  • < 1 % over the whole range with voltage variation
  • 0.05 %/°C with temperature variation
Response time < 200 ms (in the event of a fault)
Quality labels CE
Operating position any position without derating
Overvoltage category III conforming to IEC 60664-1
[ui] rated insulation voltage 400 V conforming to IEC 60664-1
Tightening torque 0.6...1 N.m conforming to IEC 60947...1
Housing material polycarbonate
Utilisation category
  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
  • DC-14 conforming to IEC 60947-5-1
Operating rate <= 360 operations/hour full load
[us] rated supply voltage , self-powered
Safety reliability data
  • B10d = 470000
  • MTTFd = 502.2 years
Functionality overvoltage and undervoltage detection
Compatibility code RM17
Electromagnetic compatibility
  • emission standard for industrial environments conforming to IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance 5 gn conforming to IEC 60068-2-27
Pollution degree 3 conforming to IEC 60664-1
Directives
  • 89/336/EEC - electromagnetic compatibility
  • 73/23/EEC - low voltage directive
Dielectric test voltage 2 kV, 1 min AC 50 Hz
Non-dissipating shock wave 4 kV
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 2.400 cm
Package 1 width 7.800 cm
Package 1 length 9.900 cm
Package 1 weight 87.000 g
Unit type of package 2 S02
Number of units in package 2 48
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 4.675 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 98 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 1.8854370782510697
Carbon footprint of the manufacturing phase [a1 to a3] 2 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.2457174757419692
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.000372352797064255
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 95.41983755211216
Carbon footprint of the use phase [b2, b3, b4, b6] 95 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.22465860666956494
Carbon footprint of the end-of-life phase [c1 to c4] 0.2 kg CO2 eq.
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 97.77602306557182
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number ba9cbb5b-722a-41d2-b7d0-f60d5f3f104d
China rohs label 5
End of life manual availability ENVEOLI1601001EN
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Application Notes

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.