Harmony Control Relays Modular 3 phase Voltage Control Relay 5A, 2CO, 220…480V AC

Home ProductsIndustrialHarmonyModular 3 phase Voltage Control Relay

Harmony Control Relays Modular 3 phase Voltage Control Relay 5A, 2CO, 220…480V AC

Item Number: RM35UB330

Datasheet

Product Dimensions

Width icon

Width<ul><li>35 mm</li><li>1.4 in</li></ul>

Height icon

Height<ul><li>90 mm</li><li>3.5 in</li></ul>

Depth icon

Depth<ul><li>72 mm</li><li>2.8 in</li></ul>

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product Harmony Control Relays
Product or component type 3-phase control relay

Physical

Control type without test button
[in] rated current 5 A
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Standards IEC 60255-1
Product certifications
  • C-Tick
  • GOST
  • CSA
  • GL
  • UL
Ambient air temperature for storage
  • -40...70 °C
  • -40...158 °F
Ambient air temperature for operation -20...50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068...2-30
Ip degree of protection
  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529
Insulation resistance
  • > 500 MOhm at 500 V DC conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC conforming to IEC 60664-1
Connections - terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end
  • screw terminals, 1 x 0.2...2 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end
Connections - terminals screw connectors
Local signalling
  • LED (green) for power ON
  • LED (yellow) for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Width
  • 35 mm
  • 1.4 in
Height
  • 90 mm
  • 3.5 in
Depth
  • 72 mm
  • 2.8 in
Net weight
  • 0.13 kg
  • 0.29 lb(US)
Mercury free Yes
Environmental disclosure ENVPEP1601004EN
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope Out
Average percentage of recycled plastic content 0 %
Package 2 bare product quantity 48
Package 1 bare product quantity 1
At least in Europe
Weee label No
Relay type voltage control relay
Product specific application for 3-phase supply
Relay name RM35UB3
Relay monitored parameters overvoltage and undervoltage between phases
Contacts type and composition 2 C/O
[uc] control circuit voltage 220...480 V
[us] rated supply voltage , self-powered
Supply voltage limits 194...528 V AC
Measurement range 208...480 V AC
Voltage detection threshold 194 V
Threshold adjustment voltage
  • 2...20 % of Un selected
  • -12...-2 % in the range 220 V AC
  • +2...+10 % in the range 480 V AC
Hysteresis 2 %
Repeat accuracy
  • +/- 0.5 % for input and measurement circuit
  • +/- 1 % for time delay
Measurement error
  • < 1 % over the whole range with voltage variation
  • 0.05 %/°C with temperature variation
Time delay type adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
Setting accuracy of time delay 10 %
Reset time 1500 ms time delay
Response time < 200 ms (in the event of a fault)
Run-up delay at power-up 650 ms
Output contacts 1 C/O + 1 C/O, 1 per threshold
Nominal output current 5 A
Maximum switching voltage 250 V AC/DC
Switching capacity in va 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Power consumption in va 0...22 VA at 400 V AC 50 Hz
Control circuit frequency 50...60 Hz +/- 15 %
Measurement accuracy +/- 10 % of the full scale value
Maximum measuring cycle 150 ms measurement cycle as true rms value
Quality labels CE
Operating rate <= 360 operations/hour full load
Functionality overvoltage and undervoltage detection
Compatibility code RM3
Electromagnetic compatibility
  • emission standard for industrial environments conforming to IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Directives
  • 73/23/EEC - low voltage directive
  • 89/336/EEC - electromagnetic compatibility
Pollution degree 3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Dielectric test voltage 2 kV, 1 min AC 50 Hz
[ui] rated insulation voltage 400 V conforming to IEC 60664-1
Operating position any position without derating
Tightening torque 0.6...1 N.m conforming to IEC 60947...1
Housing material polycarbonate
Safety reliability data
  • B10d = 300000
  • MTTFd = 319.6 years
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 4.500 cm
Package 1 width 7.800 cm
Package 1 length 9.700 cm
Package 1 weight 133.000 g
Unit type of package 2 S03
Number of units in package 2 48
Package 2 height 30.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 6.649 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 99 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 8.484476439790575
Carbon footprint of the manufacturing phase [a1 to a3] 8 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.01647657068062827
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.04088311518324607
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 90.47160000000001
Carbon footprint of the use phase [b2, b3, b4, b6] 90 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.23654319371727747
Carbon footprint of the end-of-life phase [c1 to c4] 0.2 kg CO2 eq.
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 99.24997931937175
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
End of life manual availability ENVEOLI1601004EN
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Application Notes

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.