Quantcast

Selector Switch Contactor Box

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range of product

Harmony XALD

Product or component type

complete control station

Product destination

for XB5 Ø 22 mm control and signalling units

Physical

Cable entry

  • 2 knock-outs for cable entry, clamping capacity: 14-14 mm
  • 2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: 12-12 mm

Net weight

0.187 kg

Mechanical durability

1000000 cycles

Connections - terminals

  • screw clamp terminals, <= 2="" x="" 1.5="" mm²="" with="" cable="" end="" conforming="" to="" en/iec="">
  • screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1

[Ie] rated operational current

  • 6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
  • 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
  • 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
  • 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
  • 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
  • 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1

Electrical durability

  • 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-40...70 °C

IP degree of protection

  • IP66 conforming to IEC 60529
  • IP67
  • IP69
  • IP69K

IK degree of protection

IK03 conforming to EN 50102

Standards

  • EN/IEC 60947-5-1
  • CSA C22.2 No 14
  • UL 508
  • JIS C8201-5-1
  • EN/IEC 60947-5-5
  • EN/IEC 60947-5-4
  • EN/IEC 60947-1
  • JIS C8201-1

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP1806010EN

Circularity Profile

ENVEOLI1806010EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Material

Contacts material

silver alloy (Ag/Ni)

Material

polycarbonate

Others

Resistance to high pressure washer

7000000 Pa at 55 °C, distance : 0.1 m

Operator position information

2 positions

Key number

455

Key withdrawal position

left-hand

Positive opening

without

Operating travel

4.3 mm (total travel)

Torque value

0.14 N.m NO changing electrical state

Tightening torque

0.8...1.2 N.m conforming to EN/IEC 60947...1

Shape of screw head

  • cross compatible with Philips no 1 screwdriver
  • cross compatible with pozidriv No 1 screwdriver
  • slotted compatible with flat Ø 4 mm screwdriver
  • slotted compatible with flat Ø 5.5 mm screwdriver

Short-circuit protection

10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1

[Ith] conventional free air thermal current

10 A conforming to EN/IEC 60947-5-1

[Ui] rated insulation voltage

600 V (pollution degree 3) conforming to EN/IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-1

Electrical reliability

  • λ < 10exp(-6)="" at="" 5="" v,="" 1="" ma="" conforming="" to="" en/iec="">
  • λ < 10exp(-8)="" at="" 17="" v,="" 5="" ma="" conforming="" to="" en/iec="">

Compatibility code

XALD

Protective treatment

TH

Overvoltage category

class II conforming to IEC 60536

NEMA degree of protection

  • NEMA 13
  • NEMA 4X

Vibration resistance

5 gn (f= 12-500 Hz) conforming to IEC 60068-2-6

Shock resistance

  • 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
  • 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

187.0 g

Package 1 Height

7 cm

Package 1 width

7 cm

Package 1 Length

10 cm

Unit Type of Package 2

S03

Number of Units in Package 2

40

Package 2 Weight

7.94 kg

Package 2 Height

30 cm

Package 2 width

30 cm

Package 2 Length

40 cm

Package 3 Height

77 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Device short name

XALD

Control station application

Start-Stop function

Colour of base of enclosure

light grey (RAL 7035)

Colour of cover

dark grey (RAL 7016)

Operator profile

1 key selector switch

Operators description

key switch ''O-I'' 1 NO

Control station composition

1 key selector switch 1 NO O-I marking

Marking location

marking on legend holder

Contact operation

slow-break
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Product Environmental

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

Frequently Asked Questions

hide show

What are the codes to make up XALD144E ?

XALD01 + ZBY2178 + ZB5AG2 + ZENL1111 + ZENL1121