Number or control scheme lines
- 0...240 with ladder programming
- 0...500 with FBD programming
Clock drift
- 12 min/year at 0-55 °C
- 6 s/month at 25-25 °C
Checks
program memory on each power up
[Us] rated supply voltage
100...240 V AC
Supply voltage limits
85...264 V
Supply frequency
50/60 Hz
Maximum supply current
- 30 mA at 240 V (without extension)
- 80 mA at 100 V (without extension)
Power consumption in VA
7 VA without extension
Discrete input voltage
100...240 V AC
Discrete input current
0.6 mA
Voltage state 1 guaranteed
>= 79 V for discrete input
Voltage state 0 guaranteed
<= 40="" v="" for="" discrete="">=>
Current state 1 guaranteed
>= 0.17 mA (discrete input)
Current state 0 guaranteed
<= 0.5="" ma="" (discrete="">=>
Input impedance
350 kOhm for discrete input
Number of outputs
4 relay
Output voltage limits
- 5...30 V DC (relay output)
- 24...250 V AC
Contacts type and composition
NO for relay output
Output thermal current
8 A for all 4 outputs for relay output
Switching capacity in mA
>= 10 mA at 12 V (relay output)
Operating rate in Hz
- 0.1 Hz (at Ie) for relay output
- 10 Hz (no load) for relay output
[Uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
Response time
- 50 ms with ladder programming (from state 0 to state 1) for discrete input
- 50 ms with ladder programming (from state 1 to state 0) for discrete input
- 50...255 ms with FBD programming (from state 0 to state 1) for discrete input
- 50...255 ms with FBD programming (from state 1 to state 0) for discrete input
- 10 ms (from state 0 to state 1) for relay output
- 5 ms (from state 1 to state 0) for relay output
Tightening torque
0.5 N.m
Overvoltage category
III conforming to EN/IEC 60664-1
Immunity to microbreaks
10 ms
Disturbance radiated/conducted
class B conforming to EN 55022-11 group 1
Pollution degree
2 conforming to EN/IEC 61131-2
Operating altitude
2000 m
Maximum altitude transport
3048 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
30
Package 2 Weight
7.892 kg
WEEE