Quantcast

OV/UV 65..260V Acdc 110-240V Ac/Dc 1C/O

OV/UV 65..260V Acdc 110-240V Ac/Dc 1C/O

OV/UV 65..260V Acdc 110-240V Ac/Dc 1C/O

Item Number: RM17UBE15

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

voltage control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Connections - terminals

screw connectors

[In] rated current

5 A

Insulation resistance

  • > 500 MOhm at 500 V DC conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC conforming to IEC 60664-1

Connections - terminals

  • screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Local signalling

  • LED (green) for power ON
  • LED (yellow) for relay ON

Mounting support

35 mm symmetrical DIN rail conforming to EN/IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Width

17.5 mm

Net weight

0.08 kg

Standards

EN/IEC 60255-6

Product certifications

  • UL
  • GL
  • GOST
  • C-Tick
  • CSA

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

IP degree of protection

  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP1504008EN

Circularity Profile

ENVEOLI1504008EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Relay type

voltage control relay

Product specific application

for single-phase and DC supply

Relay name

RM17UBE

Relay monitored parameters

  • self-powered
  • overvoltage and undervoltage detection

Time delay type

adjustable 0.1...10 s, 0 + 10 % on crossing the threshold

Switching capacity in VA

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC/DC

Power consumption in VA

0...3 VA AC

Measurement range

65...260 V voltage AC/DC

Utilisation category

  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
  • DC-14 conforming to IEC 60947-5-1

Contacts type and composition

1 C/O

[Uc] control circuit voltage

110...240 V

Reset time

1500 ms time delay

Maximum switching voltage

250 V AC/DC

[Us] rated supply voltage

110...240 V AC/DC 50/60 Hz +/- 10 %

Supply voltage limits

50...270 V AC/DC

Maximum power consumption in W

1 W DC

Immunity to microbreaks

20 ms

Control circuit frequency

50...60 Hz +/- 10 %

Output contacts

1 C/O

Nominal output current

5 A

Maximum measuring cycle

150 ms measurement cycle as true rms value

Hysteresis

3 % fixed of threshold setting

Run-up delay at power-up

  • 1000 ms DC
  • 500 ms AC

Measurement accuracy

+/- 10 % of the full scale value

Repeat accuracy

  • +/- 0.5 % for input and measurement circuit
  • +/- 1 % for time delay

Measurement error

  • < 1="" %="" over="" the="" whole="" range="" with="" voltage="">
  • 0.2 %/°C with temperature variation

Polarity

non reversible polarity on DC supply

Quality labels

CE

Overvoltage category

III conforming to IEC 60664-1

[Ui] rated insulation voltage

  • 250 V conforming to IEC 60664-1
  • 400 V conforming to IEC 60664-1

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Operating rate

<= 360="" operations/hour="" full="">

Safety reliability data

  • B10d = 470000
  • MTTFd = 502.2 years

Functionality

overvoltage and undervoltage detection

Compatibility code

RM17

Electromagnetic compatibility

  • emission standard for industrial environments conforming to EN/IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Directives

  • 73/23/EEC - low voltage directive
  • 89/336/EEC - electromagnetic compatibility

Vibration resistance

  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1

Shock resistance

5 gn conforming to IEC 60068-2-27

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

  • 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

  • 4 kV conforming to IEC 60255-5
  • 4 kV conforming to IEC 60664-1
  • 4 kV conforming to IEC 61000-4-5

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

88.0 g

Package 1 Height

2.8 cm

Package 1 width

7.8 cm

Package 1 Length

9.7 cm

Unit Type of Package 2

S02

Number of Units in Package 2

48

Package 2 Weight

4.568 kg

Package 2 Height

15 cm

Package 2 width

30 cm

Package 2 Length

40 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • End of Life Manual

  • Application Solutions

  • eTechPub

  • Certificates (MSDS)