Quantcast

Clipsal MAX9 Surge Protection Device SPD, 3P, 40kA

Clipsal MAX9 Surge Protection Device SPD, 3P, 40kA

Clipsal MAX9 Surge Protection Device SPD, 3P, 40kA

Item Number: MX9SP340
Retail
$457
RRP (Inc. GST)

Product Dimensions

Width icon

Width54 mm

Height icon

Height85 mm

Depth icon

Depth64 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-
max9 spd

Specifications

Design

Sustainable offer status

Green Premium product

Range of product

MAX9

Range

MAX9

Product or component type

surge arrester

Device application

distribution

Physical

Local signalling

flag

[Ue] rated operational voltage

240/415 V +/- 6 % AC 50/60 Hz

Local signalling

white/red flag

Local signalling

flag (white/red)

Mounting mode

clip-on

Mounting support

DIN rail

Height

85 mm

Width

54 mm

Depth

64 mm

Net weight

340 g

Connections - terminals

  • tunnel type terminal (top or bottom) 2.5-25 mm² rigid
  • tunnel type terminal (top or bottom) 4-16 mm² flexible
    • Wire stripping length

      14 mm

      Standards

    • IEC 61643-11:2011
    • EN 61643-11:2012
      • IP degree of protection

        IP20

        IK degree of protection

        IK03 conforming to IEC 62262

        Relative humidity

        5-95 % at 55-55 °C

        Ambient air temperature for operation

        -25-70 °C

        Ambient air temperature for storage

        -40-85 °C

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

         Pro-active China RoHS declaration (out of China RoHS legal scope)

        Environmental Disclosure

        ENVPEP130303EN

        Circularity Profile

        ENVEOLI130301EN

        Others

        Surge arrester class type

        type 2

        Surge arrester technology

        MOV

        Nominal discharge current

        15 kA conforming to IEC 61643-11

        Maximum discharge current

        40 kA conforming to IEC 61643-11

        [Uc] maximum continuous operating voltage

        350 V AC

        Maximum [Up] voltage protection level

        <1.6 kV type 2

        [Ures] residual voltage

        1545 V

        [Ut] temporary overvoltage

        336 V L/PE 5 s withstand

        Signalling circuit voltage

        AC: 250 V 50/60 Hz

        Signalling output current

        0.25 A

        Comb busbar and distribution block compatibility

        tooth

        9 mm pitches

        6

        Cable cross section

      • 2.5-25 mm² rigid
      • 4-16 mm² flexible
        • Response time

          <= 25 ns

          Maximum residual current

        • 240/415 V
        • 0.6 mA 240/415 V
          • Tightening torque

            3.5-3.5 N.m

            Targeted country

            Australia

            Quality labels

            RCM

            Pollution degree

            2

            Operating altitude

            0...2000 m

            Unit Type of Package 1

            PCE

            Number of Units in Package 1

            1

            Package 1 Weight

            356 g

            Package 1 Height

            7.4 cm

            Package 1 width

            9.4 cm

            Package 1 Length

            6.4 cm

            Unit Type of Package 2

            BB1

            Number of Units in Package 2

            4

            Package 2 Weight

            1.424 kg

            Package 2 Height

            8.2 cm

            Package 2 width

            27.5 cm

            Package 2 Length

            9.6 cm

            Unit Type of Package 3

            CAR

            Number of Units in Package 3

            28

            Package 3 Weight

            10.468 kg

            Package 3 Height

            20 cm

            Package 3 width

            30 cm

            Package 3 Length

            40 cm

            Poles description

            3P

            Remote signalling

            with

            Signal contacts composition

            1 NO + 1 NC

            Surge arrester type

            electrical distribution network

            Earthing system

          • TN-C
          • TN-S
          • TT
            • Show all specifications

              Frequently Asked Questions

              hide show

              What is the backup protection device for MAX9 SPD?

              We recommend using MAX9 MCB backup protection device for MAX9 SPD. You can use 1P 40A MCB (MX9MC140) for 1P SPD (MX9SP140), and 3P 40A MCB (MX9MC340) for 3P SPD (MX9SP340).
              max9 busbar
              max9 AFDD