Quantcast

Spare Coils

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys D
  • TeSys D control relay
    • Range

      TeSys

      Product or component type

      contactor coil

      Product compatibility

    • LC1DT20...DT40
    • LC1D09...D38
    • CAD
      • Warranty

        18 months

        Physical

        Mechanical durability

        15 Mcycles

        Ambient air temperature for operation

        -5-60 °C

        Net weight

        0.07 kg

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Pro-active compliance (Product out of EU RoHS legal scope)

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

         Pro-active China RoHS declaration (out of China RoHS legal scope)

        California proposition 65

        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

        Others

        Device short name

        LXD1

        Control circuit type

        AC at 50/60 Hz

        [Uc] control circuit voltage

        48 V AC 50/60 Hz

        Average resistance

        21.7 Ohm at 20 °C

        Inductance of closed circuit

        0.87 H

        Maximum operating rate

        3600 cyc/h 60 °C

        Coil technology

        without built-in suppressor module

        Control circuit voltage limits

      • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
      • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
      • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
        • Inrush power in VA

        • 70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
        • 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
          • Hold-in power consumption in VA

          • 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
          • 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
            • Heat dissipation

              2-3 W at 50/60 Hz

              Unit Type of Package 1

              PCE

              Number of Units in Package 1

              1

              Package 1 Weight

              76 g

              Package 1 Height

              5 cm

              Package 1 width

              6.6 cm

              Package 1 Length

              4 cm

              PVC free

              Yes
              Show all specifications

              Documents & downloads

              hide show
              Filter items
              • All

              • Product Brochures

              • Technical Data Catalogues

              • Installation Instruction

              Frequently Asked Questions

              hide show

              What is the replacement AC coil for CAD32 and CAD50 relay?

              Issue:
              AC coil replacement for CAD32 and CAD50

              Product Line:
              Relays

              Environment:
              Tesys CAD Control Relays

              Cause:
              Product selection

              Resolution:
              Volt = coil part number
              12 = LXD1J7
              21 = LXD1Z7
              24 = LXD1B7
              32 = LXD1C7
              36 = LXD1CC7
              42 = LXD1D7
              48 = LXD1E7
              60 = LXD1EE7
              100 = LXD1K7
              110 = LXD1F7
              115 = LXD1FE7
              120 = LXD1G7
              127 = LXD1FC7
              200 = LXD1L7
              208 = LXD1LL7
              220/230 = LXD1M7
              230 595 21 LXD1P7
              230/240 = LXD1U7
              277 781 30 LXD1W7
              380/400 = LXD1Q7
              400 = LXD1V7
              415 = LXD1N7
              440 = LXD1R7
              480 = LXD1T7
              600 = LXD1X7
              690 = LXD1Y7

               

              What is the code for a 415VAC coil for a LC1D40A Contactor?

              The 415V coil is LXD3N7

              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

              Issue:
              Identifying replacement coils for tesys D non-reversing and reversing conactors

              Product Line:
              IEC Contactors and Starters

              Environment:
              Products sold and used in the United States

              Cause:
              Replacement coil is needed

              Resolution:
              DC replacement coils are not available.
              AC Coils are 50/60 hertz for voltages as listed below:

              Volts - Part Number
              12 ____ LXD1J7
              21 ____ LXD1Z7
              24 ____ LXD1B7
              32 ____ LXD1C7
              36 ____ LXD1CC7
              42 ____ LXD1D7
              48 ____ LXD1E7
              60 ____ LXD1EE7
              100 ___ LXD1K7 ( never brought to North America )
              110 ___ LXD1F7
              115 ___ LXD1FE7
              120 ___ LXD1G7
              127 ___ LXD1FC7
              200 ___ LXD1L7
              208 ___ LXD1LE7
              220 ___ LXD1M7
              230 ___ LXD1P7
              240 ___ LXD1U7
              277 ___ LXD1W7
              380 ___ LXD1Q7
              400 ___ LXD1V7
              415 ___ LXD1N7
              440 ___ LXD1R7
              480 ___ LXD1T7
              575 ___ LXD1SC7
              600 ___ LXD1X7
              690 ___ LXD1Y7


              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil.