TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector

TeSys D Contactor, 3P(3 NO), AC-3, <= 440V, 9A, 12VDC Coil

Catalogue Number: LC1D09JL
TeSys LC1D09 D12 D18 - 3P - DC coil - screw & screw clamp connector
Retail
$370.87
RRP (Inc. GST)

Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product name
TeSys D
Product or component type
contactor
Device short name
LC1D
Contactor application
  • resistive load
  • motor control
    • Utilisation category
    • AC-4
    • AC-1
    • AC-3
      • Poles description
        3P
        Pole contact composition
        3 NO
        [Ue] rated operational voltage
      • power circuit: <= 690 V AC 25...400 Hz
      • power circuit: <= 300 V DC
        • [Ie] rated operational current
        • 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
        • 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
          • Motor power kW
          • 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
          • 4 kW at 380...400 V AC 50/60 Hz (AC-3)
          • 4 kW at 415...440 V AC 50/60 Hz (AC-3)
          • 5.5 kW at 500 V AC 50/60 Hz (AC-3)
          • 5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
          • 2.2 kW at 400 V AC 50/60 Hz (AC-4)
            • Motor power hp
            • 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
            • 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
            • 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
            • 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
            • 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
            • 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
              • Control circuit type
                DC low consumption
                [Uc] control circuit voltage
                12 V DC
                Auxiliary contact composition
                1 NO + 1 NC
                [Uimp] rated impulse withstand voltage
                6 kV conforming to IEC 60947
                Overvoltage category
                III
                [Ith] conventional free air thermal current
              • 25 A (at 60 °C) for power circuit
              • 10 A (at 60 °C) for signalling circuit
                • Irms rated making capacity
                • 250 A at 440 V for power circuit conforming to IEC 60947
                • 140 A AC for signalling circuit conforming to IEC 60947-5-1
                • 250 A DC for signalling circuit conforming to IEC 60947-5-1
                  • Rated breaking capacity
                    250 A at 440 V for power circuit conforming to IEC 60947
                    [Icw] rated short-time withstand current
                  • 105 A 40 °C - 10 s for power circuit
                  • 210 A 40 °C - 1 s for power circuit
                  • 30 A 40 °C - 10 min for power circuit
                  • 61 A 40 °C - 1 min for power circuit
                  • 100 A - 1 s for signalling circuit
                  • 120 A - 500 ms for signalling circuit
                  • 140 A - 100 ms for signalling circuit
                    • Associated fuse rating
                    • 10 A gG for signalling circuit conforming to IEC 60947-5-1
                    • 25 A gG at <= 690 V coordination type 1 for power circuit
                    • 20 A gG at <= 690 V coordination type 2 for power circuit
                      • Average impedance
                        2.5 mOhm - Ith 25 A 50 Hz for power circuit
                        [Ui] rated insulation voltage
                      • power circuit: 690 V conforming to IEC 60947-4-1
                      • power circuit: 600 V CSA certified
                      • power circuit: 600 V UL certified
                      • signalling circuit: 690 V conforming to IEC 60947-1
                      • signalling circuit: 600 V CSA certified
                      • signalling circuit: 600 V UL certified
                        • Electrical durability
                        • 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
                        • 2 Mcycles 9 A AC-3 at Ue <= 440 V
                          • Power dissipation per pole
                          • 1.56 W AC-1
                          • 0.2 W AC-3
                            • Protective cover
                              with
                              Mounting support
                            • plate
                            • rail
                              • Standards
                              • CSA C22.2 No 14
                              • EN 60947-4-1
                              • EN 60947-5-1
                              • IEC 60947-4-1
                              • IEC 60947-5-1
                              • UL 508
                                • Product certifications
                                • LROS (Lloyds register of shipping)
                                • CCC
                                • UL
                                • GL
                                • BV
                                • RINA
                                • DNV
                                • GOST
                                • CSA
                                  • Connections - terminals
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
                                  • control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
                                  • control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
                                    • Tightening torque
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                    • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                      • Operating time
                                      • 65.45...88.55 ms closing
                                      • 20...30 ms opening
                                        • Safety reliability level
                                        • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                        • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
                                          • Mechanical durability
                                            30 Mcycles
                                            Maximum operating rate
                                            3600 cyc/h 60 °C
                                            Coil technology
                                            built-in bidirectional peak limiting diode suppressor
                                            Time constant
                                            40 ms
                                            Inrush power in W
                                            2.4-2.4 W (at 20 °C)
                                            Hold-in power consumption in W
                                            2.4-2.4 W at 20 °C
                                            Auxiliary contacts type
                                          • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                          • type mirror contact 1 NC conforming to IEC 60947-4-1
                                            • Signalling circuit frequency
                                              25...400 Hz
                                              Minimum switching current
                                              5 mA for signalling circuit
                                              Minimum switching voltage
                                              17 V for signalling circuit
                                              Non-overlap time
                                            • 1.5 ms on de-energisation between NC and NO contact
                                            • 1.5 ms on energisation between NC and NO contact
                                              • Insulation resistance
                                                > 10 MOhm for signalling circuit
                                                Contact compatibility
                                                M5
                                                Compatibility code
                                                LC1D
                                                IP degree of protection
                                                IP20 front face conforming to IEC 60529
                                                Protective treatment
                                                TH conforming to IEC 60068-2-30
                                                Pollution degree
                                                3
                                                Ambient air temperature for storage
                                                -60-80 °C
                                                Operating altitude
                                                3000 m without derating
                                                Fire resistance
                                                850 °C conforming to IEC 60695-2-1
                                                Flame retardance
                                                V1 conforming to UL 94
                                                Mechanical robustness
                                              • vibrations contactor open: 2 Gn, 5...300 Hz
                                              • vibrations contactor closed: 4 Gn, 5...300 Hz
                                              • shocks contactor open: 10 Gn for 11 ms
                                              • shocks contactor closed: 15 Gn for 11 ms
                                                • Height
                                                  77 mm
                                                  Width
                                                  45 mm
                                                  Depth
                                                  95 mm
                                                  Net weight
                                                  0.48 kg
                                                  Unit Type of Package 1
                                                  PCE
                                                  Number of Units in Package 1
                                                  1
                                                  Package 1 Weight
                                                  364 g
                                                  Package 1 Height
                                                  4.9 cm
                                                  Package 1 width
                                                  11.1 cm
                                                  Package 1 Length
                                                  8.9 cm
                                                  Sustainable offer status
                                                  Green Premium product
                                                  REACh free of SVHC
                                                  Yes
                                                  EU RoHS Directive
                                                  Compliant
                                                  Toxic heavy metal free
                                                  Yes
                                                  Mercury free
                                                  Yes
                                                  RoHS exemption information
                                                  Yes
                                                  China RoHS Regulation
                                                   Pro-active China RoHS declaration (out of China RoHS legal scope)
                                                  Environmental Disclosure
                                                  ENVPEP1501004EN
                                                  Circularity Profile
                                                  ENVEOLI1501004EN
                                                  WEEE
                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                  PVC free
                                                  Yes
                                                  California proposition 65
                                                  WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                                                  Warranty
                                                  18 months

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • CAD Files and Packs

                                                  • Product Brochures

                                                  • Technical Data Catalogues

                                                  • Product Environmental

                                                  • End of Life Manual

                                                  • Installation Instruction

                                                  • Data Bulletin

                                                  • Certificates (MSDS)

                                                  • Declaration of Conformity

                                                  Frequently Asked Questions

                                                  hide show

                                                  Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                                                  Issue:
                                                  Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                                                  Product Line: 
                                                  Tesys D Contactors

                                                  Environment:
                                                  IEC contactors

                                                  Resolution:
                                                  The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                                                   

                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Issue:​
                                                  What is the altitude derating for a TeSys D-Line contactor?

                                                  Product Line:
                                                  Digest 177 Section 18 : Contactors and Starters, IEC

                                                  Environment:
                                                  North American Products

                                                  Resolution:
                                                  The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                                                  Voltage
                                                  3500m x 0.90
                                                  4000m x 0.80
                                                  4500m x 0.70
                                                  5000m x 0.60

                                                  Current
                                                  3500m x 0.92
                                                  4000m x 0.90
                                                  4500m x 0.88
                                                  5000m x 0.86

                                                  For example, an LC1D80 at 5000 meters:
                                                  - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                                                  - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                                                   

                                                  Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                                  Issue:
                                                  Mounting adaptor for GV2 and LC1D contactor

                                                  Product Line:
                                                  Motor Starters and Protectors

                                                  Environment:
                                                  TeSys GV Manual Starter and Protectors
                                                  Tesys D Contactors
                                                   
                                                  Resolution:
                                                  The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                                  What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                                                  Issue:
                                                  Identifying maximum voltage of an LC1D contactor

                                                  Product Line:
                                                  TeSys D Contactors

                                                  Environment:
                                                  IEC contactors and starters used in North America

                                                  Cause:
                                                  n/a

                                                  Resolution:
                                                  IThe maximum voltage per UL and CSA is 600VAC. 
                                                   

                                                  What is the heat dissipated by the LC1D09 contactor?

                                                  Issue:
                                                  Contactors dissipate heat

                                                  Product Line:
                                                  Tesys D Contactors

                                                  Environment:
                                                  IEC Contactors and Starters

                                                  Resolution:
                                                  Total heat dissipation is 3.60 watts maximum; .20 watts dissipated across each power pole and 2 to 3 watts dissipated by the AC control coil.


                                                   

                                                  What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                                                  Issue:
                                                  Identifying replacement coils for tesys D non-reversing and reversing conactors

                                                  Product Line:
                                                  IEC Contactors and Starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Replacement coil is needed

                                                  Resolution:
                                                  DC replacement coils are not available.
                                                  AC Coils are 50/60 hertz for voltages as listed below:

                                                  Volts - Part Number
                                                  12 ____ LXD1J7
                                                  21 ____ LXD1Z7
                                                  24 ____ LXD1B7
                                                  32 ____ LXD1C7
                                                  36 ____ LXD1CC7
                                                  42 ____ LXD1D7
                                                  48 ____ LXD1E7
                                                  60 ____ LXD1EE7
                                                  100 ___ LXD1K7 ( never brought to North America )
                                                  110 ___ LXD1F7
                                                  115 ___ LXD1FE7
                                                  120 ___ LXD1G7
                                                  127 ___ LXD1FC7
                                                  200 ___ LXD1L7
                                                  208 ___ LXD1LE7
                                                  220 ___ LXD1M7
                                                  230 ___ LXD1P7
                                                  240 ___ LXD1U7
                                                  277 ___ LXD1W7
                                                  380 ___ LXD1Q7
                                                  400 ___ LXD1V7
                                                  415 ___ LXD1N7
                                                  440 ___ LXD1R7
                                                  480 ___ LXD1T7
                                                  575 ___ LXD1SC7
                                                  600 ___ LXD1X7
                                                  690 ___ LXD1Y7


                                                  Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                                                  What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

                                                  Issue:
                                                  Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

                                                  Product Line:
                                                  NEMA combination starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Resolution:
                                                  For contactors with screw clamp terminals:
                                                  stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
                                                  stranded cable w/cable end: One or Two #18-10 AWG per terminal.
                                                  solid cable: One or Two #18-8 AWG per terminal.

                                                  Are the D-Line contactors rated to break DC voltages?

                                                  Issue: 
                                                  Can the TeSys D line be used to control DC loads? 

                                                  Product Line:
                                                  Tesys D contactors

                                                  Environment:
                                                  Products sold and used in the United States
                                                   
                                                  Cause:
                                                   DC power circuit
                                                   
                                                  Resolution:
                                                   
                                                  Yes, 75 VDC (125 VDC for D115 & D150) per pole which means that through a four pole device breaking 300 VDC is possible by wiring all four power poles in series. However, be aware that the device current ratings will differ according to the number of poles in series and the type of application.

                                                  Devices are suitable but not UL Listed for DC applications.

                                                  More information on their DC ratings can be found in the current TeSys Motor Control and Protection Compentns catalog: https://www.schneider-electric.us/en/download/document/MKTED210011EN/


                                                   

                                                  What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

                                                  Issue:
                                                  What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

                                                  Product Line:
                                                  IEC Contactors

                                                  Environment:
                                                  Ordering

                                                  Cause:
                                                  Selection

                                                  Resolution:
                                                  The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

                                                  AC Volts ___Code     AC Volts ___Code
                                                  12 ___ J7                   208 ___ LE7
                                                  21 ___ Z7                   220 ___ M7
                                                  24 ___ B7                  230 ___ P7
                                                  32 ___ C7                  240 ___ U7
                                                  36 ___ CC7               277 ___ W7
                                                  42 ___ D7                  380 ___ Q7
                                                  48 ___ E7                   400 ___ V7
                                                  60 ___ EE7                415 ___ N7
                                                  100 ___ K7                440 ___ R7
                                                  110 ___ F7                480 ___ T7
                                                  115 ___ FE7              575 ___ SC7
                                                  120 ___ G7                600 ___ X7
                                                  127 ___ FC7              690 ___ Y7
                                                  200 ___ L7                
                                                                 
                                                  Standard Coil                Low Consumption
                                                  DC Volts ___Code          DC Volts ___Code
                                                  12 ___ JD                           5 ___ AL
                                                  24 ___ BD                         12 ___ JL
                                                  36 ___ CD                         20 ___ ZL
                                                  48 ___ ED                         24 ___ BL
                                                  60 ___ ND                         48 ___ EL
                                                  72 ___ SD                         72 ___ SL
                                                  110 ___ FD                       96 ___ DL
                                                  125 ___ GD                     110 ___ FL
                                                  220 ___ MD                    220 ___ ML
                                                  250 ___ UD                     250 ___ UL
                                                  440 ___ RD                

                                                  What is the part code for the Adaptor to join the GV2P16 to a LC1D09BL

                                                  You can use GV2AF3 or GV2AF4 + LAD31

                                                  What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                                                  Issue:
                                                  Identifying the difference between LAD4TB and LAD4TBDL

                                                  Product Line:
                                                  IEC contactors and starters

                                                  Environment:
                                                  Products sold and used in the United States

                                                  Cause:
                                                  Identifying the difference between two similar part numbers

                                                  Resolution:
                                                  The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.


                                                   

                                                  Is the contactor, LC1D09 available for sale without the coil?

                                                  Our LC1D09 to LC1D1506 have to be ordered with a coil voltage. They are not sold less coil. Coil voltages can be found on H12 in the A4 Catalogue.
                                                  Show More