Specifications

hide show
Range of product
TeSys D
Range
TeSys
Device short name
LA9D
Product or component type
mechanical interlock
Accessory / separate part category
interlocking accessory
Interlocking type
electrical and mechanical
Poles description
  • 4P
  • 3P
    • Electrical circuit type
    • reversing
    • changeover
      • Range compatibility
        TeSys D contactor
        Product compatibility
      • LC1D80 AC
      • LC1D95 AC
        • Net weight
          0.17 kg
          Compatibility code
          LA9D
          REACh Regulation
          Free of Substances of Very High Concern above the threshold
          REACh free of SVHC
          Yes
          EU RoHS Directive
          Compliant
          Toxic heavy metal free
          Yes
          Mercury free
          Yes
          RoHS exemption information
          Yes
          China RoHS Regulation
           Pro-active China RoHS declaration (out of China RoHS legal scope)
          WEEE
          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
          Warranty
          18 months

          Documents & downloads

          hide show
          Filter items
          • All

          • CAD Files and Packs

          • Product Brochures

          • Technical Data Catalogues

          • Installation Instruction

          Frequently Asked Questions

          hide show

          What is needed to interlock two LC1D80 or two LC1D95 contactors for a reversing application?

          Issue:
          Mechanical and electrical interlock for LC1D80** and LC1D95**

          Product Line:
          Tesys D line Contactors

          Environment:
          Contactor Accessories

          Resolution:
          For LC1D80 or LC1D95 with AC coils
          LA9D4002 mechanical interlock with integral electrical interlocking
          LA9D50978 mechanical interlock without electrical interlocking
          LA9D8069 - 3 pole power connectors***

          For LC1D80 or LC1D95 with DC coils
          LA9D8002 mechanical interlock with integral electrical interlocking
          LA9D80978 mechanical interlock without electrical interlocking
          LA9D8069 - 3 pole power connectors***

          ***Connectors for 4 pole contactor set is LA9D8070.

          What is the code for a 20A 10mA RCBO

          The code is A9D40620

          Will the mechanical interlock LA9D0902 work on the new style Telemecanique contactors?

          Issue:
          Will the new style Tesys Contactors still utilize the old style mechanical interlocks?

          Product Line:
          IEC contactors and starters

          Environment:
          Products sold and used in the United States

          Cause:
          Identifying product compatibility

          Resolution:
          No, it will not.  Refer to the current Digest  for the selection of mechanical interlock components for current style Tesys D-line contactors.  


           

          What code is a mechanical interlock for the 4pole LC1D1150046 contactor?

          LA9D11502 will fit the 4p LC1D115 and LC1D150 contactors

          What are the codes for a 20A 10mA 1pole rcbo ?

          4rcbe220/10
          or
          A9D40620

          What modification do I choose for an Ethernet IP on an M-Flex?

          Issue:
          What modification do I choose for an Ethernet IP on an M-Flex?

          Product Line:
          M-Flex

          Environment:
          All MFD Types

          Cause:
          None

          Resolution:
          Ethernet IP is option R09 on an M-Flex drive.
           

          What is the thread size of the LA9F701 and LA9F702?

          The thread size of the LA9F701 terminal covers is 6mm and the thread size of the LA9F702 is 8mm.

          Data sheets on the items...https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f701 
          ..........................................https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=la9f702

           

          4300 ACM Device Type

          Issue
          When attempting to add a 4300 ACM device to the ION Enterprise/SPM/PME network using Management Console, the 4300 ACM does not show up in the drop down list of possible device types.

          Product Line
          Ion Enterprise
          StruxureWare Power Monitoring (SPM)
          Power Monitoring Expert (PME)
          4300 ACM

          Environment
          Management Console

          Cause
          The 4300 ACM is not on the 'official' list of supported device types in the ION_Network database.

          Resolution
          When adding a 4300 ACM, select the 3300 ACM device type.  Once added as a 3300 device type, it will communicate properly in all versions of ION Enterprise/SPM/PME.
          The dropdown list can also be modified to include the 4300 by follow the instructions in article FA209317

          Can IFE be used as a Modbus gateway for none trip units?

          Issue
          Customers are trying to connect PowerLogic and ION meters to an IFE with the expectation that it can act as a Modbus Gateway.

          Product
          IFE
          PowerLogic and ION Meters

          Environment
          Communications

          Resolution
          Yes, with the LV434002.

          More Information:
          The basic IFE, LV434001 (previously LV434010), is only a Modbus TCP gateway for the single circuit breaker connected to its ULP port.  The IFE Switchboard Server, LV434002 (previously LV434011), has the same function, but is also able to be a Modbus RTU gateway for additional devices connected through its stacking connector, such as IFMs. So in order to get the Modbus serial line (RS485) accessible, an IFM is required to be stacked to the IFE-SS through the DIN rail connection which then makes 2-wire Modbus available from the IFM’s top connector.  So if there are multiple circuit breakers, an IFE-SS and enough IFMs can be stacked on the DIN rail to accommodate them, and then Modbus can be daisy chained from the last IFM to a meter or any other Modbus device.

          Is it possible to add side instantaneous auxiliary contacts blocks to the TeSys D DC coil contactors and relays?

          No, with the TeSYS D range, the DC coil contactors (both standard and low consumption) only allow front mountable auxiliaries.
          The part numbers LAD8N11, LAD8N20 and LAD8N02 will fit only the contactors with AC coils.

          Can the old D-line front mount attachments fit on the new CAD relays?

          Issue: 
          Can the old D-line attachments fit the new CAD relays
           
          Product Line:
          IEC Contactors

          Environment:
          Tesys D contactors and relays
           
          Cause:
          Using old accessories with new CAD relays

          Resolution:
           Yes, the old style front mount latch attachments, timing attachments, and auxiliary contacts will mount on the new Tesys D-line relays.

          What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

          Issue:
          What terminal protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays?

          Product Line:
          TeSys F-Line Contactors

          Environment:
          All Product Lines

          Cause:
          Can not find it in the Digest

          Resolution:
          The LA9F702 protection shrouds fit the LR9F5*63, LR9F5*67, and LR9F5*69 overload relays
          Show More