Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range

TeSys

Product or component type

circuit breaker

Device application

motor protection

Physical

Circularity Profile

ENVEOLI1704004EN

Environmental Disclosure

ENVPEP1704004EN

Mercury free

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

EU RoHS Directive

Compliant

RoHS exemption information

Yes

Protection type

  • phase loss
  • overload
  • phase unbalance
  • short time short-circuit protection
  • ground fault protection
  • short-circuit
    • [Ue] rated operational voltage

      690 V AC 50/60 Hz conforming to IEC 60947-2

      [In] rated current

      80 A

      Mechanical durability

      40000 cycles

      Electrical durability

    • 14000 cycles for AC-3 at 440 V In/2
    • 7000 cycles for AC-3 at 440 V In
      • Control type

        rotary handle

        Local signalling

      • flashing LED (green) for ready
      • LED (red) for alarm (T° >95%)
      • green indicator for presence of auxiliary contacts
        • Standards

        • CSA C22.2 No 60947-4-1
        • EN/IEC 60947-2
        • EN/IEC 60947-4-1
        • UL 60947-4-1
          • Product certifications

          • IEC
          • UL
          • CSA
          • CCC
          • EAC
          • ATEX
          • EU-RO MR
            • Mounting mode

            • by clips
            • by screws
              • Mounting support

              • 35 mm symmetrical DIN rail
              • plate
              • 75 mm symmetrical DIN rail
                • Connections - terminals

                  lugs-ring terminals

                  Width

                  81 mm

                  Height

                  155 mm

                  Depth

                  165 mm

                  Net weight

                  1.6 kg

                  Ambient air temperature for storage

                  -50-85 °C

                  Ambient air temperature for operation

                  -25-70 °C

                  IP degree of protection

                  IP40 front face conforming to IEC 60529

                  IK degree of protection

                  IK07 conforming to IEC 62262

                  Others

                  Halogen content performance

                  Halogen free plastic parts product

                  Package 1 Height

                  12.5 cm

                  Package 1 Length

                  22 cm

                  Package 1 Weight

                  1.602 kg

                  Package 1 width

                  9 cm

                  PVC free

                  Yes

                  WEEE

                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                  Product name

                  TeSys GV4

                  Device short name

                  GV4P

                  Utilisation category

                  category A

                  Suitability for isolation

                  yes conforming to IEC 60947-1

                  Poles description

                  3P

                  Trip unit technology

                • electronic
                • thermal-magnetic
                  • Magnetic tripping current

                    1360-1360 A

                    [Isd] short-time pick-up adjustment range

                    13 x Ir

                    Thermal protection adjustment range

                    40-80 A

                    Motor tripping class

                  • 10
                  • 20
                    • Phase failure sensitivity

                      yes conforming to IEC 60947-4-1

                      Breaking capacity

                    • Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                    • Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                    • Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                    • Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                    • 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
                    • 65 kA at 240 V AC 50/60 Hz conforming to UL 60947
                    • 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
                    • Icu 8 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                    • Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                    • 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
                      • [Ics] rated service breaking capacity

                      • 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                      • 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                      • 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                      • 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                      • 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                      • 2 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                        • [Uimp] rated impulse withstand voltage

                          [Ui] rated insulation voltage

                          800 V conforming to IEC 60947-2

                          Motor power kW

                        • 37-37 kW at 400...415 V AC 50/60 Hz
                        • 45-45 kW at 500 V AC 50/60 Hz
                        • 22-22 kW at 400...415 V AC 50/60 Hz
                        • 30-30 kW at 500 V AC 50/60 Hz
                        • 37-37 kW at 660...690 V AC 50/60 Hz
                        • 45-45 kW at 660...690 V AC 50/60 Hz
                        • 55-55 kW at 660...690 V AC 50/60 Hz
                        • 30-30 kW at 400...415 V AC 50/60 Hz
                        • 37-37 kW at 500 V AC 50/60 Hz
                          • Rotary handle padlocking

                            padlock in OFF or ON position

                            Number of slots

                          • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                          • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                          • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                            • Quality labels

                              CE

                              Connection pitch

                              27 mm

                              Tightening torque

                            • 9-9 N.m for 16-95 mm²
                            • 5-5 N.m for 1.5-10 mm²
                              • Operating altitude

                              • 0...2000 m without derating
                              • 2000...5000 m with derating
                                • Pollution degree

                                  3 conforming to IEC 60947-1

                                  Tropicalisation

                                  2 conforming to IEC 68-2

                                  Mechanical robustness

                                • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                • shocks: 15 gn 11 ms conforming to IEC 60068-2-27