Quantcast

Motor Breaker GV4P Thermal/Magnetic 50A 25kA Everlink Terminal

Motor Breaker GV4P Thermal/Magnetic 50A 25kA Everlink Terminal

Motor Breaker GV4P Thermal/Magnetic 50A 25kA Everlink Terminal

Item Number: GV4P50B

Retail
$1,919.90
RRP (Inc. GST)

Product Dimensions

Width icon

Width81 mm

Height icon

Height155 mm

Depth icon

Depth165 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Protection type

  • phase loss
  • ground fault protection
  • short-circuit
  • phase unbalance
  • overload
  • short time short-circuit protection
    • [Ue] rated operational voltage

      690 V AC 50/60 Hz conforming to IEC 60947-2

      [In] rated current

      50 A

      Mechanical durability

      40000 cycles

      Electrical durability

    • 20000 cycles for AC-3 at 440 V In/2
    • 10000 cycles for AC-3 at 440 V In
      • Control type

        rotary handle

        Local signalling

      • flashing LED (green)ready:
      • LED (red)alarm (T° >95%):
      • green indicatorpresence of auxiliary contacts:
        • Standards

        • UL 60947-4-1
        • EN/IEC 60947-2
        • EN/IEC 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • IEC
          • UL
          • CSA
          • CCC
          • EAC
          • ATEX
          • EU-RO MR
            • Mounting mode

            • by screws
            • by clips
              • Mounting support

              • 75 mm symmetrical DIN rail
              • 35 mm symmetrical DIN rail
              • plate
                • Connections - terminals

                • top 1 EverLink BTR screw connectors wire size 1.5-70 mm², solid
                • top 1 EverLink BTR screw connectors wire size 1.5-50 mm², flexible
                • bottom 1 EverLink BTR screw connectors wire size 2.5-95 mm², solid
                • bottom 1 EverLink BTR screw connectors wire size 2.5-70 mm², flexible
                  • Wire stripping length

                    20 mm

                    Width

                    81 mm

                    Height

                    155 mm

                    Depth

                    165 mm

                    Net weight

                    1.6 kg

                    Ambient air temperature for storage

                    -50-85 °C

                    Ambient air temperature for operation

                    -25-70 °C

                    IP degree of protection

                    IP40 front face conforming to IEC 60529

                    IK degree of protection

                    IK07 conforming to IEC 62262

                    REACh Regulation

                    Free of Substances of Very High Concern above the threshold

                    EU RoHS Directive

                    Compliant

                    Mercury free

                    Yes

                    RoHS exemption information

                    Yes

                    China RoHS Regulation

                    Product out of China RoHS scope. Substance declaration for your information

                    Environmental Disclosure

                    ENVPEP1704004EN

                    Circularity Profile

                    ENVEOLI1704004EN

                    Others

                    Product name

                    TeSys GV4

                    Device short name

                    GV4P

                    Utilisation category

                    category A

                    Suitability for isolation

                    yes conforming to IEC 60947-1

                    Poles description

                    3P

                    Trip unit technology

                  • thermal-magnetic
                  • electronic
                    • Magnetic tripping current

                      850-850 A

                      [Isd] short-time pick-up adjustment range

                      13 x Ir

                      Thermal protection adjustment range

                      20-50 A

                      Motor tripping class

                    • 10
                    • 20
                      • Phase failure sensitivity

                        yes conforming to IEC 60947-4-1

                        Breaking capacity

                      • Icu 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                      • Icu 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                      • Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                      • Icu 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                      • 35 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
                      • 35 kA at 240 V AC 50/60 Hz conforming to UL 60947
                      • 18 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
                      • 14 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
                        • [Ics] rated service breaking capacity

                        • 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                        • 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                        • 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                        • 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                          • [Uimp] rated impulse withstand voltage

                            [Ui] rated insulation voltage

                            800 V conforming to IEC 60947-2

                            Motor power kW

                          • 11-11 kW at 400...415 V AC 50/60 Hz
                          • 15-15 kW at 500 V AC 50/60 Hz
                          • 18.5-18.5 kW at 660...690 V AC 50/60 Hz
                          • 15-15 kW at 400...415 V AC 50/60 Hz
                          • 18.5-18.5 kW at 400...415 V AC 50/60 Hz
                          • 22-22 kW at 400...415 V AC 50/60 Hz
                          • 18.5-18.5 kW at 500 V AC 50/60 Hz
                          • 22-22 kW at 500 V AC 50/60 Hz
                          • 30-30 kW at 500 V AC 50/60 Hz
                          • 22-22 kW at 660...690 V AC 50/60 Hz
                          • 30-30 kW at 660...690 V AC 50/60 Hz
                          • 37-37 kW at 660...690 V AC 50/60 Hz
                          • 45-45 kW at 660...690 V AC 50/60 Hz
                            • Rotary handle padlocking

                              padlock in OFF or ON position

                              Number of slots

                            • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                            • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                            • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                              • Quality labels

                                CE

                                Connection pitch

                                27 mm

                                Tightening torque

                              • 9-9 N.m for 16-95 mm²
                              • 5-5 N.m for 1.5-10 mm²
                                • Operating altitude

                                • 0...2000 m without derating
                                • 2000...5000 m with derating
                                  • Pollution degree

                                    3 conforming to IEC 60947-1

                                    Tropicalisation

                                    2 conforming to IEC 68-2

                                    Mechanical robustness

                                  • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                                  • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                                  • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                                    • Package 1 Weight

                                      1.45 kg

                                      Package 1 Height

                                      20.3 cm

                                      Package 1 width

                                      10 cm

                                      Package 1 Length

                                      22 cm

                                      WEEE

                                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                      PVC free

                                      Yes

                                      Halogen content performance

                                      Halogen free plastic parts product
                                      Show all specifications

                                      Frequently Asked Questions

                                      hide show

                                      what's the difference between the GV3P50 and GV3P501

                                      they are the same Device but the P50 has everlink terminals on top and bottom and the P501 has everlink terminals on top and direct connection on the bottom 

                                      What items does the GV2PC02 enclosure suit?

                                      The GV2PC02 is for GV2P and GV2L, 0.55 to 15kW.

                                      GV2P disconnect options

                                      Issue:
                                      What is the product number for a complete through-the-door disconnect device for a GV2P

                                      Product Line:
                                      GV2P Manual Starters and Protectors

                                      Environment:
                                      US product

                                      Cause:
                                      Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                                      Resolution:
                                      There are three devices which include mechanism, shaft and handle:
                                      GV2APN01 has a NEMA 1, 12 rating and is black
                                      GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                                      GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                                      What is the part number for the replacement GV3 thermal Magnetic C/B - GV3ME63/40?

                                      The part number for the replacement GV3 Thermal Magnetic C/B - GV3ME63/40 is - GV3P50 or GV3P65

                                      For further information, visit links below:-
                                      https://www.schneider-electric.com.au/en/search/GV3P50
                                      https://www.schneider-electric.com.au/en/search/GV3P65
                                      User-added image
                                      User-added image

                                       

                                      Do the GV manual motor starters have repair parts?

                                       

                                      Issue:     
                                      Do the GV manual motor starters have repair parts?
                                      Product Line:
                                      GV manual motor protectors
                                      Environment:
                                      Products sold and used in the United States
                                      Cause:
                                      Need replacement parts for a GV2P GV2ME or GV3P starter

                                      Resolution:

                                      The GV line of manual starters does not have repair parts, the manual motor protector will have to be replaced in it's entirety.

                                      What is the part name for the side mount auxiliary contacts 1 N/C , 1N/O for GV3P40?

                                      The part name for the side mount auxiliary contacts is - GVAN11.
                                      Show More