Motor Breaker GV4LE Magnetic 3.5A 50kA Everlink Terminal

Motor Breaker GV4LE Magnetic 3.5A 50kA Everlink Terminal

Motor Breaker GV4LE Magnetic 3.5A 50kA Everlink Terminal

Item Number: GV4LE03N

Retail
$974.64
RRP (Inc. GST)

Product Dimensions

Width icon

Width81 mm

Height icon

Height155 mm

Depth icon

Depth116 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Protection type

short-circuit

[In] rated current

3.5 A

Control type

toggle

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mounting mode

  • by screws
  • by clips
    • Mounting support

    • plate
    • 75 mm symmetrical DIN rail
    • 35 mm symmetrical DIN rail
      • Mechanical durability

        40000 cycles

        Electrical durability

      • 40000 cycles for AC-3 at 440 V In/2
      • 40000 cycles for AC-3 at 440 V In
        • Local signalling

          green indicatorpresence of auxiliary contacts:

          Connections - terminals

        • top 1 EverLink BTR screw connectors wire size 1.5-70 mm², solid
        • top 1 EverLink BTR screw connectors wire size 1.5-50 mm², flexible
        • bottom 1 EverLink BTR screw connectors wire size 2.5-95 mm², solid
        • bottom 1 EverLink BTR screw connectors wire size 2.5-70 mm², flexible
          • Wire stripping length

            20 mm

            Standards

          • EN/IEC 60947-4-1
          • EN/IEC 60947-2
            • Height

              155 mm

              Width

              81 mm

              Depth

              116 mm

              Net weight

              1.5 kg

              Product certifications

            • IEC
            • CCC
            • EAC
            • EU-RO MR
              • IP degree of protection

                IP40 front face conforming to IEC 60529

                IK degree of protection

                IK07 conforming to IEC 62262

                Ambient air temperature for operation

                -25-70 °C

                Ambient air temperature for storage

                -50-85 °C

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1704004EN

                Circularity Profile

                ENVEOLI1704004EN

                Others

                Product name

                TeSys GV4

                Device short name

                GV4L

                Poles description

                3P

                Utilisation category

                category A

                Trip unit technology

              • magnetic
              • electronic
                • Breaking capacity

                • Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 8 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                  • [Ics] rated service breaking capacity

                  • 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                  • 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                  • 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                  • 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                  • 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                  • 2 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                    • Trip unit rating

                      21-49 A

                      Motor power kW

                    • 0.55-0.55 kW at 400...415 V AC 50/60 Hz
                    • 0.75-0.75 kW at 400...415 V AC 50/60 Hz
                    • 0.75-0.75 kW at 500 V AC 50/60 Hz
                    • 1.1-1.1 kW at 500 V AC 50/60 Hz
                    • 1.1-1.1 kW at 660...690 V AC 50/60 Hz
                    • 1.5-1.5 kW at 660...690 V AC 50/60 Hz
                    • 1.5-1.5 kW at 500 V AC 50/60 Hz
                    • 2.2-2.2 kW at 660...690 V AC 50/60 Hz
                    • 1.1-1.1 kW at 400...415 V AC 50/60 Hz
                      • [Uimp] rated impulse withstand voltage

                        [Ui] rated insulation voltage

                        800 V conforming to IEC 60947-2

                        Suitability for isolation

                        yes conforming to IEC 60947-1

                        Number of slots

                      • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                      • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                      • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                        • Connection pitch

                          27 mm

                          Tightening torque

                        • 9-9 N.m for 16-95 mm²
                        • 5-5 N.m for 1.5-10 mm²
                          • Quality labels

                            CE

                            Tropicalisation

                            2 conforming to IEC 68-2

                            Pollution degree

                            3 conforming to IEC 60947-1

                            Mechanical robustness

                          • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                          • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                          • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                            • Operating altitude

                            • 0...2000 m without derating
                            • 2000...5000 m with derating
                              • Package 1 Weight

                                1.73 kg

                                Package 1 Height

                                21 cm

                                Package 1 width

                                11 cm

                                Package 1 Length

                                22 cm

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                PVC free

                                Yes

                                Halogen content performance

                                Halogen free plastic parts product
                                Show all specifications

                                Frequently Asked Questions

                                hide show

                                Will the Tesys GV2ME starters install into old style enclosures designed for the GV2M, GV2MC01 and GV2MC02 enclosures?

                                Issue:
                                GV2ME compatibility with old enclosure 

                                Product Line:

                                Motor Starters and Protectors

                                Environment:
                                TeSys™ GV Manual Starters and Protectors
                                 
                                Resolution:
                                No, Order new enclosures using the same catalog numbers. The current enclosure has an updated DIN attachement which will accept the Tesys GV2ME starters but will not accept the old GV2M starters.

                                What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                                Issue:
                                Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                                Product Line:
                                Contactors and Starters IEC

                                Environment:
                                Tesys D contactors and GV manual starters

                                Cause:
                                Spacer required

                                Resolution:
                                Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                                Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                                Issue:
                                Mounting adaptor for GV2 and LC1D contactor

                                Product Line:
                                Motor Starters and Protectors

                                Environment:
                                TeSys GV Manual Starter and Protectors
                                Tesys D Contactors
                                 
                                Resolution:
                                The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                                Are explosion proof enclosures available for GV manual motor starters.

                                Issue:
                                NEMA 7/9 rated enclosure for GV manual motor starters

                                Product Line:
                                Tesys GV Motor Starters and Protectors

                                Environment:
                                TeSys™ GV Manual Starters and Protectors

                                Resolution:
                                No hazardous duty enclosures are available for the GV product line.
                                For explosion proof applications consider the Class 2510 Type M or Type T offering.

                                Can the GV* starters be used on 50 hertz applications?

                                Issue:
                                GV* Starter for 50/60hz application

                                Product Line:
                                Motor Starters and Protectors

                                Environment:
                                PowerPact™ Manual Starters

                                Resolution:
                                Yes, these starters are rated for 50/60 hertz.

                                This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                                Is a padlocking device available for the GV2MC** type enclosures?

                                Issue:
                                Padlocking device for GV2MC Enclosures

                                Product Line:
                                TeSys GV2 Manual Starters and Protectors

                                Environment:
                                n/a

                                Resolution:
                                Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.