Quantcast

Terminal Block

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

Linergy

Product or component type

combination block

Product compatibility

  • LC1D09...D38
  • adaptor plate
    • Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Range compatibility

    • TeSys GV2
    • TeSys D
      • Quantity per set

        set of 10

        Net weight

        0.016 kg

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        X

        Environmental Disclosure

        ENVPEP111252EN

        Others

        Product name

        FT

        Device short name

        GV2AF

        Accessory / separate part category

        connection accessory

        Poles description

        3P

        Compatibility code

        GV2AF

        Unit Type of Package 1

        PCE

        Number of Units in Package 1

        1

        Package 1 Weight

        22 g

        Package 1 Height

        9.5 cm

        Package 1 width

        10 cm

        Package 1 Length

        15 cm

        Unit Type of Package 2

        BB1

        Number of Units in Package 2

        10

        Package 2 Weight

        220 g

        Package 2 Height

        9.5 cm

        Package 2 width

        10 cm

        Package 2 Length

        15 cm

        Unit Type of Package 3

        S03

        Number of Units in Package 3

        140

        Package 3 Weight

        3.594 kg

        Package 3 Height

        30 cm

        Package 3 width

        30 cm

        Package 3 Length

        40 cm

        WEEE

        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
        Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • CAD Files and Packs

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        • Data Bulletin

        • eTechPub

        Frequently Asked Questions

        hide show

        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

        Issue:
        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

        Product Line:
        Contactors and Starters IEC

        Environment:
        Tesys D contactors and GV manual starters

        Cause:
        Spacer required

        Resolution:
        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

        Can the GV* starters be used on 50 hertz applications?

        Issue:
        GV* Starter for 50/60hz application

        Product Line:
        Motor Starters and Protectors

        Environment:
        PowerPact™ Manual Starters

        Resolution:
        Yes, these starters are rated for 50/60 hertz.

        This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

        What is the operation of the GV2AD fault signalling contacts of the GV2 motor protection circuit breakers?

        GV2ME, GV2P, GV2L, GV2LE, GV3P and GV3L Motor protection circuit breakers (MPCB) can be fitted with the following optional fault indicating contact blocks:
         

        GVAD0110
        GVAD0101
        GVAD1010
        GVAD1001

        These blocks comprise of fault signalling contacts and instantaneous auxiliary contacts

        GVAD0110

        A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized

        A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

        GVAD0101

        A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energised and open when the device is energised.

        A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

        GVAD1010 

        A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized.

        A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
         

        GVAD1001

        A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energized and open when the device is energized.

        A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
         


        The instantaneous auxiliary contact test is performed by creating a state of transition of the handle actuator between the de-energized position and the energized position.

        The fault contact test is performed by pressing the test button when the handle actuator is in the closed position.