Quantcast

Terminal Block

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

Linergy

Product or component type

combination block

Product compatibility

LC1D09...D38

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Range compatibility

  • TeSys GV2
  • TeSys D
    • [Ie] rated operational current

      32 A

      Quantity per set

      set of 10

      Net weight

      0.016 kg

      REACh Regulation

      Free of Substances of Very High Concern above the threshold

      REACh free of SVHC

      Yes

      EU RoHS Directive

      Compliant

      Toxic heavy metal free

      Yes

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      X

      Environmental Disclosure

      ENVPEP111252EN

      Others

      Product name

      FT

      Device short name

      GV2AF

      Accessory / separate part category

      connection accessory

      Poles description

      3P

      Compatibility code

      GV2AF

      Unit Type of Package 1

      PCE

      Number of Units in Package 1

      1

      Package 1 Weight

      22 g

      Package 1 Height

      9.5 cm

      Package 1 width

      10 cm

      Package 1 Length

      15 cm

      Unit Type of Package 2

      BB1

      Number of Units in Package 2

      10

      Package 2 Weight

      260 g

      Package 2 Height

      9.5 cm

      Package 2 width

      10 cm

      Package 2 Length

      15 cm

      Unit Type of Package 3

      S03

      Number of Units in Package 3

      140

      Package 3 Weight

      4.094 kg

      Package 3 Height

      30 cm

      Package 3 width

      30 cm

      Package 3 Length

      40 cm

      WEEE

      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Product Brochures

      • Technical Data Catalogues

      • Product Environmental

      • Installation Instruction

      • Data Bulletin

      • Certificates (MSDS)

      • eTechPub

      Frequently Asked Questions

      hide show

      What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

      Issue:
      Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

      Product Line:
      Contactors and Starters IEC

      Environment:
      Tesys D contactors and GV manual starters

      Cause:
      Spacer required

      Resolution:
      Compensation plate catalog number GV1F03, requires 2 pieces snap together.

      What is the hole size of the padlock provision for a GV2P starter?

      Issue:
      Padlock hole diameter on GV2P

      Product Line:
      GV2 Manual Motor Protectors

      Environment:
      All GV2P, rotary handle. 

      Cause:
      n/a

      Resolution:
      There are provisions for one padlock only, the hole size is approximately 6mm.  You can add a GV2V03 padlock attachment that will allow up to 6 padlocks for Lock out Tag out applications.

      Can the GV* starters be used on 50 hertz applications?

      Issue:
      GV* Starter for 50/60hz application

      Product Line:
      Motor Starters and Protectors

      Environment:
      PowerPact™ Manual Starters

      Resolution:
      Yes, these starters are rated for 50/60 hertz.

      This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

      Do the GV7 and the LR9F trip on phase loss?

      Yes they do, though their trip time for "unbalanced phases" is much faster than that of the conventional thermal magnetic overloads, such as GV2/3 series or LRD series.

      The GV7 and LR9F series will both trip after 4 seconds (+ or - 20%) on phase loss where an LRD or GV2/3 can keep running for up to 2 hours unless an overload is detected in the remaining phases.

      What is the operation of the GV2AD fault signalling contacts of the GV2 motor protection circuit breakers?

      GV2ME, GV2P, GV2L, GV2LE, GV3P and GV3L Motor protection circuit breakers (MPCB) can be fitted with the following optional fault indicating contact blocks:
       

      GVAD0110
      GVAD0101
      GVAD1010
      GVAD1001

      These blocks comprise of fault signalling contacts and instantaneous auxiliary contacts

      GVAD0110

      A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized

      A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

      GVAD0101

      A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energised and open when the device is energised.

      A N/C fault signalling contact (terminals 95-96), closed if there is no fault, open when a fault (magnetic or thermal) occurs. 

      GVAD1010 

      A N/O instantaneous auxiliary contact (terminals 53-54), closed when the device is energized and open when the device is de-energized.

      A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
       

      GVAD1001

      A N/C instantaneous auxiliary contact (terminals 51-52), closed when the device is de-energized and open when the device is energized.

      A N/O fault signalling contact (terminals 97-98), open if there is no fault, closed when a fault (magnetic or thermal) occurs. 
       


      The instantaneous auxiliary contact test is performed by creating a state of transition of the handle actuator between the de-energized position and the energized position.