Control Circuit Breaker

Product Dimensions

Width icon

Width15 mm

Height icon

Height74 mm

Depth icon

Depth67 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

control

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Mounting mode

by clips

Mounting support

  • plate
  • rail
    • Mounting position

    • horizontal
    • vertical
      • Control type

        toggle

        [In] rated current

        0.5 A

        [Ue] rated operational voltage

      • 250 V AC 50/60 Hz conforming to IEC 60947-2
      • 277 V AC 60 Hz conforming to CSA C22.2 No 235
      • 277 V AC 60 Hz conforming to UL 1077
      • 48 V DC
        • Mechanical durability

          8000 cycles

          Electrical durability

          8000 cycles

          Connections - terminals

        • connector 1 cable(s) 0.75-6 mm²solid without cable end
        • connector 2 cable(s) 0.75-4 mm²solid without cable end
        • connector 1 cable(s) 0.75-4 mm²flexible with cable end
        • connector 2 cable(s) 0.75-2.5 mm²flexible with cable end
          • Quantity per set

            set of 6

            Height

            74 mm

            Width

            15 mm

            Depth

            67 mm

            Net weight

            0.07 kg

            Standards

          • EN/IEC 60947-1
          • EN/IEC 60947-2
          • CSA C22.2 No 235
          • UL 1077
            • Product certifications

            • UL
            • CSA
              • IP degree of protection

                IP20 conforming to IEC 60529

                Ambient air temperature for operation

                -20-60 °C

                Ambient air temperature for storage

                -40-80 °C

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP110308EN

                California proposition 65

                WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov

                Others

                Product name

                TeSys GB2

                Device short name

                GB2

                Poles description

                1P + N

                Network type

                AC/DC

                Utilisation category

              • category A conforming to IEC 60947-2
              • DC-12 conforming to IEC 60947-5-1
              • DC-13 conforming to IEC 60947-5-1
                • Network frequency

                  50/60 Hz conforming to IEC 60947-2

                  Breaking capacity

                • 50 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-2
                • 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
                • 1.5 kA Icu at 24 V DC conforming to IEC 60947-2
                • 1 kA Icu at 48 V DC conforming to IEC 60947-2
                  • [Ics] rated service short-circuit breaking capacity

                  • 100 % at 110 V AC 50/60 Hz conforming to IEC 60947-2
                  • 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
                    • Trip unit technology

                      thermal-magnetic

                      Magnetic tripping current

                      6.6-6.6 A

                      [Uimp] rated impulse withstand voltage

                      Power dissipation per pole

                      2 W

                      Tightening torque

                      1.2 N.m on connector

                      Mechanical robustness

                    • shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27
                    • vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6
                      • 9 mm pitches

                        2

                        Compatibility code

                        GB2

                        Protective treatment

                        TC

                        Fire resistance

                        960 °C conforming to IEC 60695-2-1

                        Operating altitude

                        3000 m

                        Unit Type of Package 1

                        PCE

                        Number of Units in Package 1

                        1

                        Package 1 Weight

                        59 g

                        Package 1 Height

                        1.5 cm

                        Package 1 width

                        7 cm

                        Package 1 Length

                        7.5 cm

                        Unit Type of Package 2

                        BB1

                        Number of Units in Package 2

                        6

                        Package 2 Weight

                        382 g

                        Package 2 Height

                        8 cm

                        Package 2 width

                        10 cm

                        Package 2 Length

                        8 cm

                        Unit Type of Package 3

                        S02

                        Number of Units in Package 3

                        72

                        Package 3 Weight

                        5.003 kg

                        Package 3 Height

                        15 cm

                        Package 3 width

                        30 cm

                        Package 3 Length

                        40 cm

                        WEEE

                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                        Show all specifications

                        Frequently Asked Questions

                        hide show

                        Are the heads of XY2CDxx trip-wire switches available separately?

                        Yes, the head for  XY2CDxx trip-wire switches can be ordered as a spare part, number XY2CD01

                        Can the GV* starters be used on 50 hertz applications?

                        Issue:
                        GV* Starter for 50/60hz application

                        Product Line:
                        Motor Starters and Protectors

                        Environment:
                        PowerPact™ Manual Starters

                        Resolution:
                        Yes, these starters are rated for 50/60 hertz.

                        This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                        GV2P disconnect options

                        Issue:
                        What is the product number for a complete through-the-door disconnect device for a GV2P

                        Product Line:
                        GV2P Manual Starters and Protectors

                        Environment:
                        US product

                        Cause:
                        Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                        Resolution:
                        There are three devices which include mechanism, shaft and handle:
                        GV2APN01 has a NEMA 1, 12 rating and is black
                        GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                        GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                        Issue:
                        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                        Product Line:
                        Contactors and Starters IEC

                        Environment:
                        Tesys D contactors and GV manual starters

                        Cause:
                        Spacer required

                        Resolution:
                        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                        Is a padlocking device available for the GV2MC** type enclosures?

                        Issue:
                        Padlocking device for GV2MC Enclosures

                        Product Line:
                        TeSys GV2 Manual Starters and Protectors

                        Environment:
                        n/a

                        Resolution:
                        Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                        Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                        Issue:
                        Mounting adaptor for GV2 and LC1D contactor

                        Product Line:
                        Motor Starters and Protectors

                        Environment:
                        TeSys GV Manual Starter and Protectors
                        Tesys D Contactors
                         
                        Resolution:
                        The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                        Are explosion proof enclosures available for GV manual motor starters.

                        Issue:
                        NEMA 7/9 rated enclosure for GV manual motor starters

                        Product Line:
                        Tesys GV Motor Starters and Protectors

                        Environment:
                        TeSys™ GV Manual Starters and Protectors

                        Resolution:
                        No hazardous duty enclosures are available for the GV product line.
                        For explosion proof applications consider the Class 2510 Type M or Type T offering.

                        Which operators can be mounted in a XACA pendant station?

                        Issue:
                        Compatible operators for XACA pendant station

                        Product Line:
                        Harmony XAC

                        Environment:
                        Pendant control station XACA

                        Resolution:
                        All ZA2 non-illuminated operators can be mounted in the cover or the bottom except for 60mm mushroom buttons. Also 3 position selector switches can not be used in the bottom. There are no contact blocks that will work with the 3 position selector switch in the bottom. Pilot lights and the XACA booted operators can be mounted in the cover only.