Quantcast

TeSys K Control Relay, 3 NO + 1 NC, <= 690V, 48VDC Standard Coil

TeSys K Control Relay, 3 NO + 1 NC, <= 690V, 48VDC Standard Coil

TeSys K Control Relay, 3 NO + 1 NC, <= 690V, 48VDC Standard Coil

Item Number: CA3KN31ED

Retail
$445.86
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height58 mm

Depth icon

Depth57 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys K control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V <= 400 Hz

Mounting support

  • plate
  • rail
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
      • Mechanical durability

        20 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        58 mm

        Width

        45 mm

        Depth

        57 mm

        Net weight

        0.225 kg

        Standards

      • BS 5424
      • IEC 60947
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • UL
        • CSA
          • IP degree of protection

            IP2x

            Ambient air temperature for operation

            -25-50 °C

            Ambient air temperature for storage

            -50-80 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

             Pro-active China RoHS declaration (out of China RoHS legal scope)

            Environmental Disclosure

            ENVPEP1503003EN

            Circularity Profile

            ENVEOLI1503003EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

            Others

            Number of Units in Package 1

            1

            Number of Units in Package 2

            40

            Package 1 width

            6 cm

            Package 2 Height

            15 cm

            Package 2 Length

            40 cm

            Package 1 Height

            4.8 cm

            Package 1 Length

            6.5 cm

            Package 2 width

            30 cm

            Unit Type of Package 1

            PCE

            Unit Type of Package 2

            S02

            Product name

            TeSys CAK

            Device short name

            CA3K

            Contactor application

            control circuit

            Utilisation category

          • DC-13
          • AC-15
            • Pole contact composition

              3 NO + 1 NC

              Control circuit type

              DC standard

              [Uc] control circuit voltage

              48 V DC

              [Ith] conventional free air thermal current

              10 A (at 50 °C)

              Irms rated making capacity

              110 A conforming to IEC 60947

              Associated fuse rating

            • 10 A gG conforming to IEC 60947
            • 10 A gG conforming to VDE 0660
              • [Ui] rated insulation voltage

              • 690 V conforming to IEC 60947
              • 750 V conforming to VDE 0110 group C
              • 690 V conforming to BS 5424
              • 600 V conforming to CSA C22.2 No 14
                • Tightening torque

                • 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                • 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
                  • Control circuit voltage limits

                  • operational: 0.8...1.15 Uc (at <50 °C)
                  • drop-out: 0.1...0.75 Uc (at <50 °C)
                    • Operating time

                    • 10 ms coil de-energisation and NO opening
                    • 30...40 ms coil energisation and NO closing
                    • 15 ms coil de-energisation and NC closing
                    • 25...35 ms coil energisation and NC opening
                      • Maximum operating rate

                        10000 cyc/h

                        Immunity to microbreaks

                        2 ms

                        Inrush power in W

                        3-3 W (at 20 °C)

                        Hold-in power consumption in W

                        3-3 W at 20 °C

                        Heat dissipation

                        3-3 W

                        Minimum switching voltage

                        17 V

                        Minimum switching current

                        5 mA

                        Non overlap distance

                        0.5 mm

                        Compatibility code

                        CA3K

                        Protective treatment

                        TC conforming to IEC 60068

                        Operating altitude

                        2000 m without derating

                        Flame retardance

                      • V1 conforming to UL 94
                      • requirement 2 conforming to NF F 16-101
                      • requirement 2 conforming to NF F 16-102
                        • Mechanical robustness

                        • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                        • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                          • Package 1 Weight

                            219 g

                            Package 2 Weight

                            9.114 kg

                            WEEE

                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                            Show all specifications

                            Frequently Asked Questions

                            hide show

                            What is the replacement for a CA3KN313BD needed

                             Use a CAD32BD

                            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                            Issue:
                            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                            Product Line:
                            CAD Industrial Relays

                            Environment:
                            Relays and Timers

                            Resolution:
                            Inductive:
                            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                            250V DC - 0.27 Amps make and break, 2.5 amps cont.
                            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                            What is the replacement coil for a CA3DN31BD relay?

                            Issue:
                            What is the replacement coil for a CA3DN31BD  relay?

                            Product Line:
                            Relays and Timers

                            Environment:
                            All Products

                            Cause:
                            Product selection

                            Resolution:
                            Use an LX4D2BD.
                             

                            Alternative part number for relay CA3KN1FD3?

                            The alternative part number is RPM42FD + RPZF4 base.
                             

                            What is the alternative for a CA2KN31 in 48V AC?

                            The alternative would be a CA2KN31E7.

                            For further information please visit Trade - Clipsal by Schneider Electric

                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Issue:
                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Product Line:
                            Tesys Relays

                            Environment:
                            Obsolete relays

                            Cause:
                            Product selection

                            Resolution:
                            The LX1D2T6 coil is obsolete. Need to replace the contactor with the new Tesys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                            See link for further information:https://www.se.com/ww/en/product/CAD32T7/tesys-d-control-relay---3-no-%2B-2-nc---%3C%3D-690-v---480-v-ac-standard-coil/
                            Schneider Electric CAD32T7 Image

                            CTA-ID : 2048217
                            Show More