Quantcast

Chassis C120 3-Phase 250A 42P

Chassis C120 3-Phase 250A 42P

Chassis C120 3-Phase 250A 42P

Item Number: C125423

Retail
$1,125.99
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Product or component type

chassis

Device application

distribution

Physical

Range compatibility

Acti 9 Isobar B distribution board

[In] rated current

250 A

Number of poles

42 27 mm

Length

569 mm

Width

215 mm

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Device short name

MSC 27

Short-circuit withstand

25 kA 0.1 s

[Icw] rated short-time withstand current

25 kA

Number of ways

  • 1 way (incomer) - 3P
  • 42 (outgoer)
    • Busbar pitch

      27 mm

      Package 1 Weight

      4.9 kg

      Package 1 Height

      215 mm

      Package 1 width

      1 mm

      Package 1 Length

      757 mm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      What is the part number for a 22mm blanking plug?

      Issue
      22mm blanking plug part number.

      Product Line:
      22mm operators, XB4/XB5 line

      Environment:
      Push Buttons and Operator Interface

      Resolution:
      ZB4SZ3 is metal round, chromium plated - also requires ZB4BZ009 mounting collar
      ZB5SZ3 is plastic round, black - includes mounting nut

      What distribution board is required for the CH25843 chassis?

      For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

      What is the function of an SDX switch?


      Issue:
      What is the function of the SDX relay module for Powerpact H J and L circuit breakers?

      Product Line:
      Circuit Breakers

      Environment:
      Powerpact H, J, and L circuit breakers with advanced Micrologic trip units

      Resolution:
      Circuit breakers equipped with Micrologic 3, 5, and 6 trip units can take the optional SDx Module.
      The SDx Module receives data from the trip unit through a fiber optic link.

      Default alarms are as follows
      • Micrologic 5 trip unit:
      — Output 1 is the thermal fault indication (SDT).
      — Output 2 is the long-time pre-alarm (PAL Ir).
      • Micrologic 6 trip unit:
      — Output 1 is the thermal fault indication (SDT) for electrical distribution applications.
      — Output 1 is None for motor-feeder applications.
      — Output 2 is the ground-fault indication (SDG).
      • For Micrologic 3 trip units, the SDx is nonconfigurable and indicates thermal trip alarm

      • For Micrologic 5 and 6, SDx can be configured for different alarms.
      Note that the SDX can be used for ground fault alarm on non configurable 6 (LSIG) trip units, but it will not provide ground fault alarm on a Micrologic 5 (LSI) trip unit.  Therfore, GF alarm without tripping is not possible.
      All alarms on a trip, failure, and maintenance event and all alarms associated with a measurement previously activated in the Alarms tab can be assigned to an SDx Module output.
       For complete list, refer to Alarms section of  manual 48940-312-01.
      To set alarms, access the SDx Module output settings using the RSU software under the Output tab.