Is there a difference in the P24 and +24 terminals on the ATV630 drives?

Issue:
Difference between the P24 and +24 terminals on the ATV630 drives. 

Product Line:
ATV630

Environment:
All serial numbers

Cause:
N/A 

Resolution: 
P24 Output power supply for digital inputs and STO  +24 Vdc  Tolerance: –15...+20%  Current: maximum 1.1 A 
+24 Digital input power supply   +24 Vdc input supply  Tolerance: –15...+20%  Current: 100 mA

What is the max current for the P24 external supply on the ATV340 drive?

Issue :
Maximum current, P24 external supply?

Product Line :
Altivar Machines, Altivar 340

Environment :
All models and serial number

Cause :
N/A

Resolution : 
The P24 terminal is only available on the Frame Size 4 and 5 drives, ATV340D30N4 to ATV340D75N4
Max current is 0.8 A
Tolerance is minimum 19VDC and maximum 30VDC

Information is listed from the ATV340 Installation Manual NVE61069

Reject: FA274804 How is a "Run Forward" command issued to an Altivar drive that is in 2 wire terminal control mode?

Issue:
Give a "Run Forward" Command when in 2 wire control. 

Product Line:
All current production models of Altivar drives.

Environment:
All current production models of Altivar drives, all serial numbers.

Cause:
Customer is sending a run forward command via the terminals but the drive stays in Rdy status.

Resolution:
A "Run Forward" command is issued on the terminals by closing a connection between +24V terminal (P24 on the ATV212) to the LI1 terminal (F on the ATV212).  Note that other programmed functions or conditions (freewheel stop, run permissive, active fault code) can prevent the drive from running when this signal is connected.'

You can use an external 24v and LI1 for the hot wire and 0V for your neutral. (F terminal for the hot wire to CC terminal for the neutral for ATV212)
 

Video: Can the ATV320 be programmed using an external 24Vdc source?

Issue:
Programming an ATV320 using an external 24Vdc source

Product line:
Altivar 320

Environment:
External 24v
 
Cause:
Need power the ATV320 with external 24Vdc so that it can be programmed

Resolution:
Yes, an external 24Vdc can be provided to the ATV320 in order to power up the display and program the drive.  

To connect an external 24VDC supply to the ATV320, the P24 terminal must be used.
The P24 is an input and output:
- When there is no external supply connected to this terminal, the P24 is an output and delivers 24VDC to the STO circuit.
- When there is an external supply connected to this terminal, the P24 is an input and the drive is supplied by the external supply.
 
The +24 terminal is used to provide 24VDC to the drive digital inputs.
+24 is not designed to be used as an input to supply the control block.

 

Can you power up the ATV32 with an external 24Vdc supply?

Issue
ATV32 power up with an external 24Vdc supply

Product Line:
ATV32 

Environment:
All serial numbers

Cause:
To maintain control power to the drive. 

Resolution: 
Yes, the P24 terminal and COM are the connections that can be used for external 24VDC. 
  **NOTE:  This does not apply to the ATV320, the P24 terminal on ATV320 is only used to supply the STO (Safe Torque Off) terminal, P24 will not accept 24v.

Where do I connect an external +24vdc power supply on the ATV630 process drive?

Issue:
External power supply connection
 
Product Line:
ATV630
 
Environment:
All models and serial numbers
 
Cause:
None
 
Resolution: 
The external +24vdc power supply must be connected to terminals P24 and 0v.  The positive is P24 and the negative is 0v.  DO NOT connect the external power supply to +24v.