Altivar 32, 400V, 0.55 Kw Variable Speed Drives

Product Dimensions

Width icon

Width45 mm

Height icon

Height325 mm

Depth icon

Depth245 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altivar 32

Product or component type

variable speed drive

Product destination

  • asynchronous motors
  • synchronous motors
    • Warranty

      18 months

      Physical

      Function available

      -

      Local signalling

    • 1 LED red for drive voltage
    • 1 LED green for CANopen run
    • 1 LED red for CANopen error
    • 1 LED red for drive fault
      • Supply

        internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection

        Protection type

      • input phase breaks: drive
      • overcurrent between output phases and earth: drive
      • overheating protection: drive
      • short-circuit between motor phases: drive
      • thermal protection: drive
        • Communication port protocol

        • CANopen
        • Modbus
          • Connector type

            1 RJ45 (on front face) for Modbus/CANopen

            Width

            45 mm

            Height

            325 mm

            Depth

            245 mm

            Net weight

            2.5 kg

            Standards

          • EN 61800-3 environments 1 category C2
          • EN 55011 class A group 1
          • EN/IEC 61800-3
          • EN 61800-3 environments 2 category C2
          • EN/IEC 61800-5-1
            • Product certifications

            • CSA
            • UL
            • C-Tick
            • NOM 117
            • GOST
              • Marking

                CE

                IP degree of protection

                IP20 conforming to EN/IEC 61800-5-1

                Relative humidity

              • 5-95 % without condensation conforming to IEC 60068-2-3
              • 5-95 % without dripping water conforming to IEC 60068-2-3
                • Ambient air temperature for operation

                • -10-50 °C without derating
                • 50-60 °C with derating factor
                  • Ambient air temperature for storage

                    -25-70 °C

                    Others

                    Product specific application

                    complex machines

                    Assembly style

                    with heat sink

                    Component name

                    ATV32

                    EMC filter

                    Class C2 EMC filter integrated

                    Network number of phases

                    3 phases

                    [Us] rated supply voltage

                    380...500 V - 15...10 %

                    Supply voltage limits

                    323-550 V

                    Supply frequency

                    50...60 Hz - 5...5 %

                    Network frequency

                    47.5...63 Hz

                    Motor power kW

                    0.55 kW at 380...480 V

                    Motor power hp

                    0.75 hp at 380...480 V

                    Line current

                  • 2.2 A for 500 V 3 phases 0.55 kW / 0.75 hp
                  • 2.8 A for 380 V 3 phases 0.55 kW / 0.75 hp
                    • Apparent power

                      1.9 kVA at 500 V 3 phases 0.55 kW / 0.75 hp

                      Prospective line Isc

                      5 kA for 3 phases

                      Nominal output current

                      1.9 A at 4 kHz 500 V 0.55 kW / 0.75 hp

                      Maximum transient current

                      2.9 A for 60 s 0.55 kW / 0.75 hp

                      Output frequency

                      5.0E-4-0.599 kHz

                      Nominal switching frequency

                      4 kHz

                      Switching frequency

                      2...16 kHz adjustable

                      Speed range

                      1-100 for asynchronous motor in open-loop mode

                      Speed accuracy

                      +/- 10 % of nominal slip 0.2 Tn to Tn

                      Torque accuracy

                      +/- 15 %

                      Transient overtorque

                      170-200 %

                      Braking torque

                      <= 170 % with braking resistor

                      Asynchronous motor control profile

                    • flux vector control without sensor - Energy Saving, NoLoad law
                    • voltage/frequency ratio - Energy Saving, quadratic U/f
                    • voltage/frequency ratio, 2 points
                    • flux vector control without sensor, standard
                    • voltage/frequency ratio, 5 points
                      • Synchronous motor control profile

                        vector control without sensor

                        Regulation loop

                        adjustable PID regulator

                        Motor slip compensation

                      • not available in voltage/frequency ratio (2 or 5 points)
                      • automatic whatever the load
                      • adjustable 0...300 %
                        • Output voltage

                          <= power supply voltage

                          Noise level

                          43 dB conforming to 86/188/EEC

                          Insulation

                          electrical between power and control

                          Electrical connection

                        • screw terminal, clamping capacity: 0.5...1.5 mm², AWG 18...AWG 14 (control)
                        • removable screw terminals, clamping capacity: 1.5...2.5 mm², AWG 14...AWG 12 (motor/braking resistor)
                        • screw terminal, clamping capacity: 1.5...4 mm², AWG 14...AWG 10 (power supply)
                          • Tightening torque

                          • 0.5 N.m, 4.4 lb/ft (control)
                          • 0.7 N.m, 7.1 lb/ft (motor/braking resistor)
                          • 0.6 N.m, 5.3 lb/ft (power supply)
                            • Analogue input number

                              3

                              Analogue input type

                            • AI1 voltage: 0...10 V DC, impedance: 30000 Ohm, resolution 10 bits
                            • AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30000 Ohm, resolution 10 bits
                            • AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits
                              • Sampling duration

                              • 2 ms (AI1, AI2, AI3) - analog input(s)
                              • 2 ms (AO1) - analog input(s)
                                • Response time

                                • LI1...LI6 8 ms, tolerance +/- 0.7 ms for logic output(s)
                                • R1A, R1B, R1C 2 ms for relay output(s)
                                • R2A, R2C 2 ms for relay output(s)
                                  • Accuracy

                                  • +/- 0.2 % (AI1, AI2, AI3) for a temperature of -10...60 °C
                                  • +/- 0.5 % (AI1, AI2, AI3) for a temperature of 25 °C
                                  • +/- 1 % (AO1) for a temperature of 25 °C
                                  • +/- 2 % (AO1) for a temperature of -10...60 °C
                                    • Linearity error

                                    • +/- 0.2...0.5 % of maximum value (AI1, AI2, AI3)
                                    • +/- 0.3 % (AO1)
                                      • Analogue output number

                                        1

                                        Analogue output type

                                      • AO1 software-configurable current 0...20 mA, impedance: 800 Ohm, resolution 10 bits
                                      • AO1 software-configurable voltage 0...10 V, impedance: 470 Ohm, resolution 10 bits
                                        • Discrete output number

                                          3

                                          Discrete output type

                                        • configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
                                        • configurable relay logic: (R2A, R2B) NO - 100000 cycles
                                        • logic: (LO)
                                          • Minimum switching current

                                            5 mA at 24 V DC for configurable relay logic

                                            Maximum switching current

                                          • R1: 3 A at 250 V AC resistive load, cos phi = 1
                                          • R1: 4 A at 30 V DC resistive load, cos phi = 1
                                          • R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4
                                          • R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4
                                          • R2: 5 A at 250 V AC resistive load, cos phi = 1
                                          • R2: 5 A at 30 V DC resistive load, cos phi = 1
                                            • Discrete input number

                                              7

                                              Discrete input type

                                            • programmable (sink/source) (LI1...LI4)24...30 V DC, with level 1 PLC
                                            • programmable as pulse input 20 kpps (LI5)24...30 V DC, with level 1 PLC
                                            • switch-configurable PTC probe (LI6)24...30 V DC
                                            • safe torque off (STO)24...30 V DC - 1500 Ohm
                                              • Discrete input logic

                                              • negative logic (sink) (LI1...LI6), > 19 V (state 0), < 13 V (state 1)
                                              • positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1)
                                                • Acceleration and deceleration ramps

                                                • ramp switching
                                                • linear
                                                • S
                                                • CUS
                                                • deceleration ramp automatic stop DC injection
                                                • U
                                                • deceleration ramp adaptation
                                                  • Braking to standstill

                                                    by DC injection

                                                    Physical interface

                                                    2-wire RS 485 for Modbus

                                                    Transmission frame

                                                    RTU for Modbus

                                                    Type of polarization

                                                    no impedance for Modbus

                                                    Number of addresses

                                                  • 1-127 for CANopen
                                                  • 1-247 for Modbus
                                                    • Method of access

                                                      slave CANopen

                                                      Electromagnetic compatibility

                                                    • 1.2/50 µs - 8/20 µs surge immunity test, level 3 conforming to IEC 61000-4-5
                                                    • conducted radio-frequency immunity test, level 3 conforming to IEC 61000-4-6
                                                    • electrical fast transient/burst immunity test, level 4 conforming to IEC 61000-4-4
                                                    • electrostatic discharge immunity test, level 3 conforming to IEC 61000-4-2
                                                    • radiated radio-frequency electromagnetic field immunity test, level 3 conforming to IEC 61000-4-3
                                                    • voltage dips and interruptions immunity test conforming to IEC 61000-4-11
                                                      • Option card

                                                      • communication card for CANopen daisy chain
                                                      • communication card for CANopen open style
                                                      • communication card for DeviceNet
                                                      • communication card for Ethernet/IP
                                                      • communication card for Profibus DP V1
                                                        • Functionality

                                                          mid

                                                          Specific application

                                                          other applications

                                                          Pollution degree

                                                          2 conforming to EN/IEC 61800-5-1

                                                          Vibration resistance

                                                        • 1 gn (f = 13-200 Hz) conforming to EN/IEC 60068-2-6
                                                        • 1.5 mm peak to peak (f = 3-13 Hz) conforming to EN/IEC 60068-2-6
                                                          • Shock resistance

                                                            15 gn for 11 ms conforming to EN/IEC 60068-2-27

                                                            Operating altitude

                                                          • <= 1000 m without derating
                                                          • 1000...3000 m with current derating 1 % per 100 m
                                                            • Operating position

                                                              vertical +/- 10 degree

                                                              Package 1 Weight

                                                              2.381 kg

                                                              Package 1 Height

                                                              0.85 dm

                                                              Package 1 width

                                                              2.75 dm

                                                              Package 1 Length

                                                              3.3 dm
                                                              Show all specifications

                                                              Documents & downloads

                                                              hide show
                                                              Filter items
                                                              • All

                                                              • CAD Files and Packs

                                                              • Product Brochures

                                                              • Technical Data Catalogues

                                                              • Product Environmental

                                                              • End of Life Manual

                                                              • Installation Instruction

                                                              • Operating Manuals

                                                              • Certificates (MSDS)

                                                              • eTechPub

                                                              • EDS Files

                                                              • GSD files

                                                              Frequently Asked Questions

                                                              hide show

                                                              Are drive thermal output ratings available in BTU?

                                                              Issue:
                                                              Are drive thermal output ratings available in BTU?

                                                              Product Line:
                                                              Altivar Machines

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Documentation

                                                              Resolution:
                                                              Heat dissipation is listed in Watts only.
                                                              See the drive catalog or installation guide for details on the heat dissipation.
                                                              1 watt is approximately 3.41 BTU/h
                                                              1000 BTU/h is approximately 293 W


                                                               

                                                              Do we have CAD drawings for the ATV312 drives?

                                                              Issue:
                                                              Getting CAD drawings for the ATV312 drives

                                                              Product Line:
                                                              Altivar ATV312 and ATV31

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Cad drawings

                                                              Resolution:
                                                              Use the following link to the CAD Drawings Catalog.

                                                              https://www.schneider-electric.us/sites/us/en/support/product-support-resources/3d-cad.page


                                                              CTA-ID : 2061638

                                                              What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

                                                              Issue:
                                                              Analog Input designed for a bipolar -10v to +10v input on the ATV32 drives

                                                              Product Line:
                                                              Altivar ATV32

                                                              Environment:
                                                              All

                                                              Cause:
                                                              AI2 is default for -10v to +10v input.

                                                              Resolution:
                                                              IO menu AI2 set up

                                                               Bipolar analog input 0 ± 10 V (maximum voltage ± 30 V)

                                                              The + or - polarity of the voltage on AI2 affects the direction of the set point and therefore the direction of operation.

                                                              • Impedance 30 kÙ
                                                              • Resolution: 10 bits
                                                              • Precision ±0.5% in 50/60 Hz for 25 °C, ±0.2% in 50/60 Hz for –10 to +60 °C at Äè = 60°C,
                                                              • Linearity ± 0.2% (max. ± 0.5%), of max. value
                                                              • Sampling time 2 ms

                                                              What is the din rail mounting kit part number for the ATV312?

                                                              Issue:
                                                              Part number for ATV312 Din rail mounting kit

                                                              Product Line:
                                                              ATV312

                                                              Environment:
                                                              All

                                                              Cause:
                                                              Desire to utilize din mounting kit option

                                                              Resolution:
                                                              The part numbers need to order the mounting kit for this drive are VW3A9804 and VW3A9805.

                                                              VW3A9804 covers the following range of drives: ATV312....
                                                              018M2, H037M2, H055M2, H075M2, H018M3, H037M3, H055M3, H075M3

                                                              VW3A9805 covers the following range of drives: ATV312....
                                                              HU11M2, HU15M2, HU11M3, HU15M3, HU22M3, H037N4, H055N4, H075N4, HU11N4, HU15N4, H075S6, HU15S6
                                                              Note: The din rail mounting kits are only available for the above drives. 

                                                              Note: Other drives not list above do not have a din rail kit.

                                                              What is the part number for the remote keypad for the ATV31?

                                                              Issue:   
                                                              Remote keypad for the ATV31.
                                                               
                                                              Product Line: 
                                                               ATV31
                                                               
                                                              Environment:
                                                               All
                                                               
                                                              Cause:  
                                                              Remote keypad kit
                                                               
                                                              Resolution:   
                                                              The Altivar 31 remote mount keypad kit is VW3A31101.
                                                              The kit includes a keypad, mounting hardware and a 3 meter cable.


                                                               

                                                              Is there a password to protect parameters in the ATV31 drive?

                                                              Issue:   
                                                              Programming password to protect/block parameters in the ATV21 Drive.
                                                               
                                                              Product Line:   
                                                              ATV31
                                                               
                                                              Environment:  
                                                              All
                                                               
                                                              Cause:  
                                                              Password
                                                               
                                                              Resolution:   
                                                              Yes.
                                                              In the SUP menu, the COd parameter can be used to enter a numerical code that restricts access to adjustment parameters in the drive.  Only the display parameters are accessible, with only a temporary choice of the parameter displayed.

                                                               
                                                              Show More