Variable speed drive ATV12
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
LEXIUM 32_Memory Card |
Variable speed drive ATV12
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
LEXIUM 32_Memory Card |

Altivar 12 Variable Speed Drive ATV12, 0.37kW, 0.55hp, 200..240V, 1ph

Catalogue Number: ATV12H037M2
Variable speed drive ATV12
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
LEXIUM 32_Memory Card |
Variable speed drive ATV12
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
Variable speed drive with heatsink, single-phase 200,,,240 V 50/60 Hz, 0,37 kW
LEXIUM 32_Memory Card |
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
Altivar 12
Product or component type
variable speed drive
Product destination
asynchronous motors
Product specific application
simple machine
Assembly style
with heat sink
Component name
ATV12
Quantity per set
set of 1
EMC filter
integrated
Built-in fan
without
Network number of phases
1 phase
[Us] rated supply voltage
200...240 V - 15...10 %
Motor power kW
0.37 kW
Motor power hp
0.55 hp
Communication port protocol
Modbus
Line current
  • 5.9 A at 200 V
  • 4.9 A at 240 V
    • Speed range
      1-20
      Transient overtorque
      150-170 % of nominal motor torque depending on drive rating and type of motor
      Asynchronous motor control profile
    • sensorless flux vector control
    • voltage/frequency ratio (V/f)
    • quadratic voltage/frequency ratio
      • IP degree of protection
        IP20 without blanking plate on upper part
        Noise level
        0 dB
        Supply frequency
        50/60 Hz +/- 5 %
        Connector type
        1 RJ45 (on front face) for Modbus
        Physical interface
        2-wire RS 485 for Modbus
        Transmission frame
        RTU for Modbus
        Transmission rate
      • 4800 bit/s
      • 9600 bit/s
      • 19200 bit/s
      • 38400 bit/s
        • Number of addresses
          1-247 for Modbus
          Communication service
        • read holding registers (03) 29 words
        • write single register (06) 29 words
        • write multiple registers (16) 27 words
        • read/write multiple registers (23) 4/4 words
        • read device identification (43)
          • Prospective line Isc
            1 kA
            Continuous output current
            2.4 A at 4 kHz
            Maximum transient current
            3.6 A for 60 s
            Speed drive output frequency
            0.5-400 Hz
            Nominal switching frequency
            4 kHz
            Switching frequency
          • 2...16 kHz adjustable
          • 4...16 kHz with derating factor
            • Braking torque
              up to 70 % of nominal motor torque without braking resistor
              Motor slip compensation
            • adjustable
            • preset in factory
              • Output voltage
                200...240 V 3 phases
                Electrical connection
                terminal, clamping capacity: 3.5 mm², AWG 12 (L1, L2, L3, U, V, W, PA, PC)
                Tightening torque
                0.8 N.m
                Insulation
                electrical between power and control
                Supply
              • internal supply for reference potentiometer: 5 V DC (4.75-5.25 V), <10 mA, protection type: overload and short-circuit protection
              • internal supply for logic inputs: 24 V DC (20.4-28.8 V), <100 mA, protection type: overload and short-circuit protection
                • Analogue input number
                  1
                  Analogue input type
                • configurable current AI1 0...20 mA 250 Ohm
                • configurable voltage AI1 0...10 V 30 kOhm
                • configurable voltage AI1 0...5 V 30 kOhm
                  • Discrete input number
                    4
                    Discrete input type
                    programmable LI1...LI4 24 V 18...30 V
                    Discrete input logic
                  • negative logic (sink), > 16 V (state 0), < 10 V (state 1), input impedance 3.5 kOhm
                  • positive logic (source), 0...< 5 V (state 0), > 11 V (state 1)
                    • Sampling duration
                    • 20 ms, tolerance +/- 1 ms for logic input
                    • 10 ms for analogue input
                      • Linearity error
                        +/- 0.3 % of maximum value for analogue input
                        Analogue output number
                        1
                        Analogue output type
                      • AO1 software-configurable voltage: 0...10 V, impedance: 470 Ohm, resolution 8 bits
                      • AO1 software-configurable current: 0...20 mA, impedance: 800 Ohm, resolution 8 bits
                        • Discrete output number
                          2
                          Discrete output type
                        • logic output LO+, LO-
                        • protected relay output R1A, R1B, R1C 1 C/O
                          • Minimum switching current
                            5 mA at 24 V DC for logic relay
                            Maximum switching current
                          • 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms logic relay
                          • 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms logic relay
                          • 3 A 250 V AC resistive cos phi = 1 L/R = 0 ms logic relay
                          • 4 A 30 V DC resistive cos phi = 1 L/R = 0 ms logic relay
                            • Acceleration and deceleration ramps
                            • linear from 0 to 999.9 s
                            • S
                            • U
                              • Braking to standstill
                                by DC injection, <30 s
                                Protection type
                              • line supply overvoltage
                              • line supply undervoltage
                              • overcurrent between output phases and earth
                              • overheating protection
                              • short-circuit between motor phases
                              • against input phase loss in three-phase
                              • thermal motor protection via the drive by continuous calculation of I²t
                                • Frequency resolution
                                • analog input: converter A/D, 10 bits
                                • display unit: 0.1 Hz
                                  • Time constant
                                    20 ms +/- 1 ms for reference change
                                    Marking
                                    CE
                                    Operating position
                                    vertical +/- 10 degree
                                    Height
                                    143 mm
                                    Width
                                    72 mm
                                    Depth
                                    121.2 mm
                                    Net weight
                                    0.7 kg
                                    Functionality
                                    basic
                                    Specific application
                                    commercial equipment
                                    Discrete and process manufacturing
                                    Power range
                                    0-0.5 kW at 200-240 V 1 phase
                                    Motor starter type
                                    variable speed drive
                                    Electromagnetic compatibility
                                  • electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4
                                  • electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2
                                  • immunity to conducted disturbances level 3 conforming to EN/IEC 61000-4-6
                                  • radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3
                                  • surge immunity test level 3 conforming to EN/IEC 61000-4-5
                                  • voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11
                                    • Electromagnetic emission
                                    • radiated emissions environment 1 category C2 conforming to EN/IEC 61800-3 2...16 kHz shielded motor cable
                                    • conducted emissions with integrated EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <5 m
                                    • conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2...12 kHz shielded motor cable <5 m
                                    • conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2, 4 and 16 kHz shielded motor cable <10 m
                                    • conducted emissions with additional EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m
                                    • conducted emissions with additional EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m
                                    • conducted emissions with additional EMC filter environment 2 category C3 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m
                                      • Product certifications
                                      • GOST
                                      • C-Tick
                                      • UL
                                      • CSA
                                      • NOM
                                        • Vibration resistance
                                        • 1 gn (f = 13-200 Hz) conforming to EN/IEC 60068-2-6
                                        • 1.5 mm peak to peak (f = 3-13 Hz) - drive unmounted on symmetrical DIN rail - conforming to EN/IEC 60068-2-6
                                          • Shock resistance
                                            15 gn conforming to EN/IEC 60068-2-27 for 11 ms
                                            Relative humidity
                                          • 5-95 % without condensation conforming to IEC 60068-2-3
                                          • 5-95 % without dripping water conforming to IEC 60068-2-3
                                            • Ambient air temperature for storage
                                              -25-70 °C
                                              Ambient air temperature for operation
                                            • -10-40 °C protective cover from the top of the drive removed
                                            • 40-60 °C with current derating 2.2 % per °C
                                              • Operating altitude
                                              • > 1000...2000 m with current derating 1 % per 100 m
                                              • <= 1000 m without
                                                • Sustainable offer status
                                                  Green Premium product
                                                  REACh Regulation
                                                  Free of Substances of Very High Concern above the threshold
                                                  EU RoHS Directive
                                                  Pro-active compliance (Product out of EU RoHS legal scope)
                                                  Mercury free
                                                  Yes
                                                  RoHS exemption information
                                                  Yes
                                                  China RoHS Regulation
                                                  X
                                                  Environmental Disclosure
                                                  ENVPEP090201EN
                                                  Circularity Profile
                                                  ENVEOLI100204EN
                                                  WEEE
                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                  California proposition 65
                                                  WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                                                  Warranty
                                                  18 months

                                                  Documents & downloads

                                                  hide show
                                                  Filter items
                                                  • All

                                                  • Product Brochures

                                                  • CAD Files and Packs

                                                  • Technical Data Catalogues

                                                  • Technical Leaflet

                                                  • Installation Instruction

                                                  • Product Environmental

                                                  • End of Life Manual

                                                  • Handout

                                                  • Data Bulletin

                                                  • Operating Manuals

                                                  • System User Guide

                                                  • Specifications

                                                  • Specification for Tender

                                                  • Application Solutions

                                                  • Certificates (MSDS)

                                                  • eTechPub

                                                  • White Paper

                                                  • DTM Files

                                                  • Software - Updates

                                                  • Software - Released

                                                  • Training Material

                                                  Frequently Asked Questions

                                                  hide show

                                                  Do we have CAD drawings for the ATV312 drives?

                                                  Issue:
                                                  Do we have CAD drawings for the ATV312 drives?

                                                  Product Line:
                                                  Altivar ATV312 and ATV31

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Cad drawings

                                                  Resolution:
                                                  Use the following link to the CAD Drawings Catalog.

                                                  https://www.schneider-electric.us/sites/us/en/support/product-support-resources/3d-cad.page


                                                  CTA-ID : 2061638

                                                  What is a good source of information for the ATV12?

                                                  Issue:
                                                  What is a good source of information for the ATV12?

                                                  Product Line:
                                                  Altivar 12

                                                  Environment:
                                                  All models and serial numbers

                                                  Cause:
                                                  Information is needed for installation and programming.

                                                  Resolution:
                                                  User manual is document number BBV28581.  This manual includes instructions for installing the drive, connecting the control wiring, programming and troubleshooting.
                                                  https://www.schneider-electric.us/en/download/document/BBV28581/

                                                  What is the din rail mounting kit part number for the ATV312?

                                                  Issue:
                                                  What is the din rail mounting kit part number for the ATV312?

                                                  Product Line:
                                                  ATV312

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Desire to utilize din mounting kit option

                                                  Resolution:
                                                  The part numbers need to order the mounting kit for this drive are VW3A9804 and VW3A9805.

                                                  VW3A9804 covers the following range of drives: ATV312....
                                                  018M2, H037M2, H055M2, H075M2, H018M3, H037M3, H055M3, H075M3

                                                  VW3A9805 covers the following range of drives: ATV312....
                                                  HU11M2, HU15M2, HU11M3, HU15M3, HU22M3, H037N4, H055N4, H075N4, HU11N4, HU15N4, H075S6, HU15S6
                                                  Note: The din rail mounting kits are only available for the above drives. 

                                                  Note: Other drives not list above do not have a din rail kit.

                                                  Can the ATV312 be powered by an external 24V only?

                                                  Issue:
                                                   Powering the  ATV312 by an external 24V only

                                                  Product Line:
                                                   ATV312

                                                  Environment:
                                                   External 24v supply

                                                  Cause:
                                                  n/a
                                                   
                                                  Resolution:
                                                  No, this drive must have line voltage applied.  The voltage must be within -15% to +10% of the rated line voltage. 

                                                   

                                                  What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

                                                  Issue:
                                                  What input is designed for a bipolar -10v to +10v input on the ATV32 drives?

                                                  Product Line:
                                                  Altivar ATV32

                                                  Environment:
                                                  All

                                                  Cause:
                                                  AI2 is default for -10v to +10v input.

                                                  Resolution:
                                                  IO menu AI2 set up

                                                   Bipolar analog input 0 ± 10 V (maximum voltage ± 30 V)

                                                  The + or - polarity of the voltage on AI2 affects the direction of the set point and therefore the direction of operation.

                                                  • Impedance 30 kÙ
                                                  • Resolution: 10 bits
                                                  • Precision ±0.5% in 50/60 Hz for 25 °C, ±0.2% in 50/60 Hz for –10 to +60 °C at Äè = 60°C,
                                                  • Linearity ± 0.2% (max. ± 0.5%), of max. value
                                                  • Sampling time 2 ms

                                                  Do any of the ATV31 drives Not have an internal fan ?

                                                   

                                                  Issue:   Do any of the ATV31 drives Not have an internal fan ?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  ATV31H018M2 & ATV31H018M2A & ATV31H018M3X & ATV31H018M3XA
                                                  ATV31H037M2 & ATV31H037M2A & ATV31H037M3X & ATV31H037M3XA
                                                  ATV31H055M2 & ATV31H055M2A & ATV31H055M3X & ATV31H055M3XA
                                                  ATV31H075M2 & ATV31H075M2A & ATV31H075M3X & ATV31H075M3XA
                                                   
                                                  Cause:   No heatsink fan
                                                   
                                                  Resolution:   Yes, the following do not have a heatsink fan:
                                                  ATV31H018M2 & ATV31H018M2A & ATV31H018M3X & ATV31H018M3XA
                                                  ATV31H037M2 & ATV31H037M2A & ATV31H037M3X & ATV31H037M3XA
                                                  ATV31H055M2 & ATV31H055M2A & ATV31H055M3X & ATV31H055M3XA
                                                  ATV31H075M2 & ATV31H075M2A & ATV31H075M3X & ATV31H075M3XA

                                                  What is the part number for the remote keypad for the ATV31?

                                                  Issue:   What is the part number for the remote keypad for the ATV31?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Remote keypad kit
                                                   
                                                  Resolution:   The Altivar 31 remote mount keypad kit is VW3A31101.
                                                  The kit includes a keypad, mounting hardware and a 3 meter cable.


                                                   

                                                  Are the EMC filters for ATV31 drives UL or cUL listed?

                                                  Issue:   Are the EMC filters for ATV31 drives UL or cUL listed?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   UL/CUL listing
                                                   
                                                  Resolution:   No. VW3A31401, VW3A31402, VW3A31403, VW3A31404, VW3A31405, VW3A31406, VW3A31407, VW3A31408 and VW3A31409 are not UL or CUL listed.

                                                   

                                                  What is the part number of the replacement fan for an ATV16, ATV18, ATV28, ATV31, ATV11?

                                                  Issue:
                                                  What is the part number of the replacement fan for an ATV16, ATV18, ATV28, ATV31, ATV11?
                                                   
                                                  Product Line:
                                                  ATV16 ATV18 ATV28 ATV31 ATV11
                                                   
                                                  Environment:
                                                  All
                                                   
                                                  Cause:
                                                  Replacement parts
                                                   
                                                  Resolution: 
                                                  Field replacement parts are not offered for these drives. 
                                                  The drive may be sent in for depot analysis, repair and/or exchange within the warranty period.
                                                  Contact any SquareD distributor for assistance.
                                                  Distributors can contact customer service for RMA.


                                                   

                                                  Can Class T fuses be used with Altivar 31 drives? The manual only references Class CC or J.

                                                  The ATV31 units were tested with the Class J fuses however the 600V version of the Class T fuses have equivalent ratings. So can use the 600V Class T fuses but not the 300V Class T fuses.

                                                  Is there a password to protect parameters in the ATV31 drive?

                                                  Issue:   Is there a password to protect parameters in the ATV31 drive?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Password
                                                   
                                                  Resolution:   Yes.
                                                  In the SUP menu, the COd parameter can be used to enter a numerical code that restricts access to adjustment parameters in the drive.  Only the display parameters are accessible, with only a temporary choice of the parameter displayed.

                                                   

                                                  How is the ATV31 set up to operate by remote keypad?

                                                  Issue:   How is the ATV31 set up to operate by remote keypad?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Remote keypad operation
                                                   
                                                  Resolution:   With the VW3A31101 remote keypad kit installed, go to menu CtL and set parameter LCC to YES.
                                                  NOTE:  LCC can only be accessed if the drive controller is equipped with a remote keypad display, and if LAC = L1 or L2.
                                                  This function enables control of the drive with the STOP/RESET, RUN, and FWD/REV buttons on the remote keypad display.
                                                  The speed reference is given by parameter LFr in the SEt- menu.
                                                  Only the freewheel stop, fast stop, and DC injection stop commands remain active on the terminal block.
                                                  If the remote keypad display is not connected, the drive controller will lock on an SLF fault.

                                                   

                                                  Does it matter where the pull up / pull down resistors are located within the ATV31 multiple drive network?

                                                  Issue:   Does it matter where the pull up / pull down resistors are located within the ATV31 multiple drive network?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Terminating resistor
                                                   
                                                  Resolution:   Not really.
                                                    
                                                  The ATV31 does not have internal pull up / down resistors for the rs-485 communications. Therefore, if it is used on a network with PLC that also does not have pull up-down resisitors for the RS485 resistors must be added at one of the devices.
                                                  At one drive add:
                                                  10k resistor between +10 (RJ45 pin 7) and D_B (Communication +, RJ45 pin 4)
                                                  10k resistor between D_B and COM (RJ45 pin 8)
                                                  4.7k resistor between COM and D_A (RJ57 pin 5)


                                                   

                                                  Why does RDY flash on the ATV31?

                                                  Issue:   
                                                  Why does RDY flash on the ATV31?
                                                   
                                                  Product Line:   
                                                  ATV31
                                                   
                                                  Environment:  
                                                  All serial numbers
                                                   
                                                  Cause:  
                                                  Customer said drive was flashing RDY.
                                                   
                                                  Resolution:   
                                                  Flashing display normally indicated current limit mode. However, if this is occurring in the ready mode, it is likely due to incorrect motor parameter settings.
                                                  Specifically, it could be that the COS (motor power factor) is set to 1.
                                                  OR
                                                  Check the +10 and +24 VDC power supplies. It could be that they are being pulled down.


                                                   

                                                  What are the dimensions for the ATV31 keypad in the VW3A31101 remote mount kit?

                                                  Issue:   What are the dimensions for the ATV31 keypad in the VW3A31101 remote mount kit?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  VW3A31101
                                                   
                                                  Cause:   Dimensions
                                                   
                                                  Resolution:   The keypad is 2.77(H) and 1.98(W) inches.
                                                  The exterior dimensions for the mounting bracket is 4.19 (4 - 3/16) inches tall, 2.625 (2 - 5/8) inches wide


                                                   

                                                  What is the part number for the Ethernet / Modbus bridge adapter for the ATV31?

                                                  Issue:   What is the part number for the Ethernet / Modbus bridge adapter for the ATV31?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Ethernet / Modbus bridge
                                                   
                                                  Resolution:   The part 174CEV30020 is obsolete.
                                                  Use TSXETG100


                                                   

                                                  How is the ATV31 setup for AI3 input to be the primary speed reference?

                                                  Issue:   How is the ATV31 setup for AI3 input to be the primary speed reference?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Speed reference
                                                   
                                                  Resolution:   In the CtL menu, set the Fr1 parameter to AI3.

                                                   

                                                  What is an ATV31****378?

                                                  Issue:  
                                                  What is an What is an ATV31****378?
                                                   
                                                  Product Line: 
                                                  ATV31
                                                   
                                                  Environment:
                                                  N/A

                                                   
                                                  Cause:   N/A
                                                   
                                                  Resolution:   
                                                  This is a special drive for Buhler Company. The 378 suffix indicates that logic input LI6 can be used as a 24vdc pulsed speed reference. Would need to obtain a replacement from Buhler Company. May also be identified as S378 suffix.

                                                  Can the ATV31 be set up to operate with remote keypad command and still use an external speed pot to control the speed?

                                                  Issue:   
                                                  Can the ATV31 be set up to operate with remote keypad command and still use an external speed pot to control the speed?
                                                   
                                                  Product Line: 
                                                   ATV31
                                                   
                                                  Environment:  
                                                  All
                                                   
                                                  Cause:  
                                                  N/A
                                                   
                                                  Resolution:  
                                                   Yes. The drive can be set up to run by remote keypad to start and stop the unit while taking a speed reference from the Analog Input, AI1.
                                                  This function can be set up in the CtL menu.  Set parameter LAC to L3.  Set Fr1 to AI1,  CHCF to SEP, and Cd1 to LCC.  

                                                  See the Altivar 31 Adjustable Speed Drive Controllers Programming Manual, VVDED303042US, for details.

                                                   

                                                  What can cause the InF fault in the Altivar 31 and Altivar 312 drives?

                                                  Issue:
                                                  What can cause the InF fault in the Altivar 31 and ATV312 drives?

                                                  Product Line:
                                                  Altivar 31 and ATV312 drives

                                                  Environment:
                                                  All 

                                                  Cause:
                                                  Internal fault 

                                                  Resolution:
                                                  InF indicates an internal fault.  
                                                  It can occur if there are loose connections inside the drive or if the drive is subjected to electromagnetic interference.  Check the line voltage to the drive.
                                                  Also, check the voltages on the control terminals, +10 to COM and 24V to COM.  It has been observed that improper wiring of the inputs or external potentiometer can overload the internal power supplies of the drive. This may result in InF fault.
                                                  Incorrect connections on the RJ45 ModBus/CANopen port can also cause this.  Verify wiring, particularly to pin 7 (10VDC supply for external keypad).



                                                   

                                                  ATV31 drive is set up to run with 2 preset speeds and will only run at 10Hz regardless of the programmed value for SP2 (ex. SP2=60Hz).

                                                  Issue:   ATV31 drive is set up to run with 2 preset speeds and will only run at 10Hz regardless of the programmed value for SP2 (ex. SP2=60Hz).
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Preset speeds
                                                   
                                                  Resolution:   Verify that the logic input used for PS2 is not set to perform another function. For example, when ATV31 drive is configured for 3-wire control, LI4 will be set for JOG. The jog function will have priority.  If jog function is not required, JOG in the FUn menu needs to be set to nO.
                                                  The functions of each logic input can be verified in the SUP menu. Go to sub-menu LIA. Scroll to the desired input (LI1A, LI2A. . . ) Enter to see to what the function of the input is assigned. Scroll up and down to see if there are additional functions assigned.

                                                   

                                                  What is part number VW3A4416?

                                                  Issue:
                                                  What is part number for an EMC filter for the Altivar 12 drives?

                                                  Product Line:
                                                  Altivar 12, ATV12, ATV11

                                                  Environment: 
                                                  ATV12H018F1
                                                  ATV12H037F1
                                                  ATV12H018M2
                                                  ATV12H037M2
                                                  ATV12H055M2
                                                  ATV12H075M2
                                                  ATV12P037F1
                                                  ATV12P037M2
                                                  ATV12P055M2
                                                  ATV12P075M2

                                                  Cause:
                                                  EMC Filter

                                                  Resolution:
                                                  Part number VW3A4416 is an externally mounted EMC filter that will fit these drives.

                                                  Want is the part number for the remote mount keypad for the ATV31?

                                                  Issue:   Want is the part number for the remote mount keypad for the ATV31?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Remote keypad
                                                   
                                                  Resolution:   VW3A31101. This kit includes a remote keypad, remote mount hardware seal and screws for IP65 mounting on enclosure door and 3 meter cable fitted with 2 connectors.

                                                   

                                                  What are the specifications for ATV31 drive output relays?

                                                  Issue:   What are the specifications for ATV31 drive output relays?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:    Relay specs

                                                  Resolution:   There are two relays in the drive.
                                                  Relay R1 has three terminals to provide a Normally Open (NO) and a Normally Closed contact from a common.
                                                  R1A is a N.O. contact.
                                                  R1B is a N.C. contact.
                                                  R1C is the common.
                                                  R1 is a programmable relay.  When programmed as the factory default, drive fault relay, R1A is closed and R1B is open when the controller is powered and not faulted. Both contacts will change state when the drive faults.

                                                  Relay R2 has two terminals to provide a NO contact, R2A & R2C.  This relay is also programmable.

                                                  Electrical Characteristics are as follows:
                                                  Min. switching capacity: 10 mA for 5 Vdc
                                                  Max. switching capacity on a resistive load (power factor = 1 and L/R time constant = 0 ms): 5 A for 250 Vac and 30 Vdc
                                                  Max. switching capacity on an inductive load (power factor = 0.4 and L/R time constant = 7 ms): 1.5 A for 250 Vac and 30 Vdc
                                                  Sampling time: 8 ms
                                                  Service life: 100,000 operations at maximum switching power;
                                                                     1,000,000 operations at minimum switching power.

                                                   

                                                  How is the maximum speed changed in the ATV31 or ATV312 drive so that the motor can operate above 60Hz?

                                                  Issue:   
                                                  How is the maximum speed changed in the ATV31 or ATV312 drive so that the motor can operate above 60Hz?
                                                   
                                                  Product Line:   
                                                  ATV31 ATV312
                                                   
                                                  Environment:  
                                                  All
                                                   
                                                  Cause:  
                                                  Changing high speed / max frequency
                                                   
                                                  Resolution:   
                                                  Parameter HSP determines the maximum speed the drive can operate.  Parameter tFr determines the maximum value that HSP can be adjusted.  

                                                  By default, tFr is set to 60Hz.  When changing the Motor Frequency - bFr this changes tFr to 72Hz.  

                                                  To increase the maximum speed above 72Hz - Go to the drc menu and Set parameter tFr.  This can be adjusted up to 500Hz.  After saving the change, go to the SEt menu > HSP and adjust up to the desired speed.  

                                                  If your motor is a specialty motor that is rated for a frequency other than 50Hz. or 60Hz. such as a 300Hz. rated spindle motor, change paramter FrS under the DRC menu to match the rated frequency of the motor.

                                                   

                                                  What should be checked if an Altivar 61 or 71 display is showing NLP?

                                                  Issue:
                                                  What should be checked if an Altivar 61 or 71 display is showing NLP?

                                                  Product Line:
                                                  ATV61/71 drives

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Drive displays 'NLP'

                                                  Resolution:
                                                  NLP indicates that no line power is present on the L1, L2 & L3 input terminals of the drive controller.

                                                  Check voltage at the L1, L2 & L3 terminals.
                                                  Check for open circuits on line contactors, circuit breakers, disconnect switches, or fuses.

                                                  If NLP state does not change with correct voltage present on L1, L2, & L3, remove the control board and check for loose connections of ribbon cables inside the drive.
                                                  WARNING: This step should be performed while the drive is powered down, and proper personal protective equipment should be worn. 

                                                  For example: In an ATV71HC25N4 a customer found a loose X3 connector from the control board to the board behind and above the control board. This connector was on a ribbon cable that was about 1 inch by 1 inch. Drive ran OK after this was reseated.

                                                  What is the part number for the conduit entry kit for the ATV312HU11M2, ATV312HU15M2, ATV312HU22M3, ATV312H037N4, ATV312H055N4, ATV312H075N4, ATV312HU11N4, ATV312HU15N4, ATV312H075S6 or ATV312HU15S6?

                                                  Issue:   What is the part number for the conduit entry kit for the ATV312HU11M2, ATV312HU15M2, ATV312HU22M3, ATV312H037N4, ATV312H055N4, ATV312H075N4, ATV312HU11N4, ATV312HU15N4, ATV312H075S6 or ATV312HU15S6?
                                                   
                                                  Product Line:   ATV312
                                                   
                                                  Environment:   ATV312HU11M2, ATV312HU15M2, ATV312HU22M3, ATV312H037N4, ATV312H055N4, ATV312H075N4, ATV312HU11N4, ATV312HU15N4, ATV312H075S6 or ATV312HU15S6
                                                   
                                                  Cause:   Conduit entry kit
                                                   
                                                  Resolution:   
                                                  VW3A31814


                                                   

                                                  Is there a problem using Altivar 61 or Altivar 71 drives delta power system?

                                                  Issue:
                                                  IWants to use Altivar 61 or Altivar 71 drives on delta power system.

                                                  Product Line:
                                                  Altivar ATV61 and ATV71

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Needs to know if the RFI filter needs to be disabled when using a corner grounded delta system?

                                                  Resolution:
                                                  As long as the input voltage remains within the normal range there should not be a problem.
                                                  This should be treated the same way as an impedance grounded system.
                                                  Remove the jumper to the left of the power terminal.
                                                  See the section of the installation manual for Operation on an IT (Isolated or impedance grounded neutral) system for details.
                                                  See the drives installation manual for more information and location of the RFI's filter tab.

                                                  The figure 1 example below is for the low horsepower ATV61 and ATV71 drives.


                                                                                                     Figure 1.

                                                   

                                                  Can the analog output of the ATV61 or ATV71 be set up as 0-10 VDC instead of 4-20 mA?

                                                  Issue:
                                                  Can the analog output of the ATV61 or ATV71 be set up as 0-10 VDC instead of 4-20 mA?

                                                  Product Line:
                                                  ATV61 and ATV71

                                                  Environment:
                                                  All

                                                  Cause:
                                                  NA

                                                  Resolution:
                                                  Yes.
                                                  Go to the Input/Output menu (1.5) and set AO1 type to voltage (0-10v range). Set AO1 assignment to the proper setting. The minimum and maxim range can also be adjusted inside the 0-10 V or 4-20  mA ranges.


                                                   

                                                  Are the ATV61 or ATV71 drives available in type 4 or 4X enclosure?

                                                  Issue:
                                                  Are the ATV61 or ATV71 drives available in type 4 or 4X enclosure?

                                                  Product Line:
                                                  Altivar ATV61 and ATV71 open type drives

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Needs to get the ATV61 and ATV71 drive in a NEMA 4 or 4X stand alone enclosure.

                                                  Resolution:
                                                  There is not a standard offering for type 4 or 4X enclosures for our drives.
                                                  It may be possible to install the drive in a properly selected enclosure by a local panel builder or contractor.
                                                  Or, contact a local SquareD field office for assistance. They may be able to offer assistance with other options.


                                                   

                                                  Why is the keypad not included with ATV61 and ATV71 drives?

                                                  Issue:
                                                  Why is the keypad not included with ATV61 and ATV71 drives?

                                                  Product Line:
                                                  Altivar 61 and 71 drives

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Customer concerned whether the HMI came with the drive

                                                  Resolution:
                                                  For all ATV61 and ATV71 drives without the letter Z at the end of the part number the keypad is included.
                                                  However, it is easy to not notice the keypad in the packaging material. The keypad is located inside folded cardboard that also functions as packing material. Check inside all folded cardboard packing materials. There is no sticker to indicate that the keypad is inside.

                                                  ATV61 & ATV71 drives with the letter Z at the end of the part number do not include the removable LCD HMI keypad display. These units do have a simplified LED display and programming keys on the face of the control board itself. The removable LCD HMI keypad display may be installed on these units.


                                                   

                                                  What is the recommended Fuse or Circuit Breaker (OCPD) size for Altivar 61 drives?

                                                  Refer to the attached Quick Start Annex, document S1B86981. 
                                                   

                                                  Which ATV71 drives have the built in braking transistor?

                                                  Models with a rating of 160KW (250HP) or less have a built-in braking transistor.
                                                  ATV71H...M3, ATV71H...M3X and ATV71H075N4 to HC16N4 drives have a built-in dynamic brake transistor.
                                                  For ATV71HC20N4 to HC50N4 drives, a separate braking unit must be used.


                                                  CTA-ID : 2026409

                                                  Do the electronic boards of the Altivar 61 and Altivar 71 drives have conformal coating?

                                                  Issue:
                                                  Do the electronic boards of the Altivar 61 and Altivar 71 drives have conformal coating?

                                                  Product Line:
                                                  Altivar ATV61 and ATV71

                                                  Environment:
                                                  Suffix S337 only

                                                  Cause:
                                                  Needs to know if you can order the ATV61 ATV71 drive with conformal coating?

                                                  Resolution:
                                                  For the ATV61 & ATV71 drives there is an option to have product treated for increased protection for dusty and corrosive environments. This product is not stocked. Add 'S337' to the end of the catalog number and multiply the listed price by 1.2 to obtain new price. With this option, exposed copper is tinned, circuit boards are conformal coated in critical areas and plastics are treated to better withstand the corrosive nature of certain oils. This option is standard on 55kW/75HP @ 230 Vac and higher & 90kW/125HP @ 460 Vac and higher.

                                                  The standard ATV61 and ATV71 drives are designed for maximum ambient pollution as follows:
                                                  ATV71:
                                                  H...M3, 71HD11M3X, HD15M3X, H075N4 to HD18N4 are Degree 2 conforming to IEC/EN 61800-5-1
                                                  HD18M3X to HD75M3X, HD22N4 to HC50N4 are Degree 3 conforming to IEC/EN 61800-5-1

                                                  ATV61:
                                                  H...M3, HD11M3X, HD15M3X, H075N4 to HD18N4 are Degree 2 conforming to IEC/EN 61800-5-1
                                                  HD18M3X to HD90M3X, HD22N4 to HC63N4 are Degree 3 conforming to IEC/EN 61800-5-1


                                                   

                                                  What does a P or H symbolize in an ATV12 drive part number?

                                                  Issue:
                                                  What does a P or H symbolize in an ATV12 drive part number?

                                                  Product Line:
                                                  Altivar 12

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Part number

                                                  Resolution:
                                                  The ATV12 drives are available as H or P version.  Part numbers with H are drives with a standard heatsink on the back of the drive.  
                                                  Ex: ATV12H037M2 has a heatsink.  Replace the H with P for drives without a heatsink.  Instead of a heatsink, these drives have a smooth, flat metal back that can be mounted to a thermally conductive machine surface.  
                                                  The P version is available up to 1HP for single phase input voltage and up 5HP for three phase input voltage. 

                                                  H version:     P version:        

                                                  Refer to Installation Manual BBV28587 for further details: https://www.schneider-electric.com/en/download/document/BBV28587/
                                                   

                                                  When do the cooling fans on the ATV212 drives come on?

                                                  Issue:
                                                  When do the cooling fans on the ATV212 drives come on?

                                                  Product Line:
                                                  Altivar 212

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Fan control strategy

                                                  Resolution:
                                                  The fan starts when the drive is in RUN state.
                                                  The fan stops after the STOP command (with a time delay in relation to the thermal state).

                                                  Do we offer any drives rated for 120v or 115v single phase operation that can run a 230vac three phase motor?

                                                  Issue:
                                                  Do we offer any drives rated for 120v or 115v single phase operation that can run a 230vac three phase motor?

                                                  Product Line:
                                                  Altivar ATV12

                                                  Environment:
                                                  All  with suffix F.

                                                  Cause:
                                                  Only has 120vac 1 phase input but needs to run a 3 phase motor.

                                                  Resolution:
                                                  Yes.

                                                  Some of the ATV12 units are rated for 115v single phase input.  

                                                  They are as follows:
                                                  ATV12H018F1 = .25hp / 1.4 amps
                                                  ATV12H037F1 = .5hp / 2.4 amps
                                                  ATV12H075F1= 1hp / 4.2 amps

                                                  CTA-ID : 2011141

                                                  How many drive configuration files can be stored in the ATV71 keypad?

                                                  Issue:   How many drive configuration files can be stored in the ATV61 / ATV71 keypad?
                                                   
                                                  Product Line:   AT61 ATV61 VW3A1101
                                                   
                                                  Environment:  All
                                                   
                                                  Cause:   Number of file storage
                                                   
                                                  Resolution:   
                                                  The keypad can store up to 4 files.
                                                  To access and manage these files go to menu 1.12 (FACTORY SETTINGS) (FCS-)
                                                  See programming manual for details if needed.


                                                  CTA-ID : 2026818

                                                  Does Schneider Electric offer replacement jog dials for the ATV12 drive?

                                                  Issue:
                                                  Replacement jog dial for the ATV12 drive

                                                  Product Line:
                                                  Altivar 12 drives

                                                  Environment:
                                                  All models and serial numbers

                                                  Cause:
                                                  None

                                                  Resolution:
                                                  There are no jog dials available as a spare part for the ATV12 drive.

                                                  Can an ATV212 drive's programming be saved to the HMI keypad (VW3A1101) and transferred to another ATV212?

                                                  Issue:
                                                  Needs the ATV212 drive's programming be saved to the HMI keypad (VW3A1101) and transferred to another ATV212?

                                                  Product Line:
                                                  Altivar 212

                                                  Environment:
                                                  All

                                                  Cause:
                                                  N/A

                                                  Resolution:
                                                  No, the ATV212's programming cannot be saved to any of the keypads available.  

                                                  Programming can be saved by any of three methods:
                                                  - in the drive by setting parameter tYP = 7
                                                  - in the Multiloader tool
                                                  - by using SoMove software, downloading the ATV212 DTM File, and using the TCSMCNAM3M002P - SoMove cable

                                                  Can the ATV31...A model be setup to use the integral speed pot dial for reference adjustment, but use the LI logic input for a run forward command?

                                                  Issue:   Can the ATV31...A model be setup to use the integral speed pot dial for reference adjustment, but use the LI logic input for a run forward command?
                                                   
                                                  Product Line:   ATV31
                                                   
                                                  Environment:  ATV31**A models
                                                   
                                                  Cause:   N/A
                                                   
                                                  Resolution:   Yes.  In the IO menu, set parameter tCC to 2C.  This assigns LI1 as run forward command.  In the CtL menu, set parameter Fr1 to AIP.

                                                   

                                                  What is the part number for an ATV61H075N4, ATV61HU15N4, ATV61HU22N4, ATV71H075N4, ATV71HU15N4, ATV71HU22N4, ATV61H075M3, ATV61HU15M3, ATV71H037M3, ATV71H075M3, ATV71HU15M3 Type 1 Conduit Kit?

                                                  Issue:   What is the part number for an ATV61H075N4, ATV61HU15N4, ATV61HU22N4, ATV71H075N4, ATV71HU15N4, ATV71HU22N4, ATV61H075M3, ATV61HU15M3, ATV71H037M3, ATV71H075M3, ATV71HU15M3 Type 1 Conduit Kit?
                                                   
                                                  Product Line:   ATV61 ATV71
                                                   
                                                  Environment:   ATV61H075N4, ATV61HU15N4, ATV61HU22N4, ATV71H075N4, ATV71HU15N4, ATV71HU22N4, ATV61H075M3, ATV61HU15M3, ATV71H037M3, ATV71H075M3, ATV71HU15M3 
                                                   
                                                  Cause:   N1 conduit kit selection
                                                   
                                                  Resolution:   
                                                  VW3A9201.


                                                   

                                                  When do the heatsink fans run on the ATV61 / ATV71 series drives?

                                                  Issue:
                                                  When do the heatsink fans run on the ATV61 / ATV71 series drives?

                                                  Product Line:
                                                  Altivar 61 and Altivar 71 series drives

                                                  Environment:
                                                  All models, All serial numbers.

                                                  Cause:
                                                  Information not available in current literature.

                                                  Resolution:
                                                  Heat sink fan operation differs depending on the frame size of the drive:
                                                  - for size 2 to 5B drives, fans start when the drive thermal state reaches a temperature level --> THD parameter = 70%.  The fans turns off when drive thermal is less than 60%
                                                  - for size 6 to 8 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 1 minute after the run command is removed.
                                                  - for size 9 to 15 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 10 minutes after the run command is removed.

                                                  For example, an ATV61HD18M3X drive (size 6), the heatsink fan starts when a Run command is given.


                                                   

                                                  Are the ATV312 drives suited to be highpot tested?

                                                  Issue:
                                                  Are the ATV312 drives suited to be highpot tested?

                                                  Product:
                                                  ATV312

                                                  Environment:
                                                  All 

                                                  Cause:
                                                  None.

                                                  Resolution:
                                                  It is not recommended to High Pot test the VFDs. It may cause damage that will void the warranty.

                                                  How to change the default display to show something other than the output frequency on ATV12 and ATV312 drive?

                                                  Issue:
                                                  How to change the default display to show something other than the output frequency?

                                                  Product Line:
                                                  ATV12, ATV312

                                                  Environment:
                                                  All models and serial numbers.

                                                  Cause:
                                                  None

                                                  Resolution:
                                                  To adjust the display so that other parameters can be viewed besides RFR, go to MON menu. Select a parameter and press and hold the enter key until the display blinks.

                                                  How can one configure the ATV312 to run upon power up and ramp up to full speed (60 hz)?

                                                  Issue:
                                                  How can one configure the ATV312 to run upon power up and ramp up to full speed (60 hz)?

                                                  Product Line:
                                                  Altivar 312, ATV312

                                                  Environment:
                                                  N/A

                                                  Cause:
                                                  N/A

                                                  Resolution:
                                                  Go into I-0- menu.
                                                  Set TCC to 2C.
                                                  Set TCT to LEL.

                                                  Go into SET- menu.
                                                  Set LSP to value desired in hz.  For example, 60 hz is full speed.

                                                  Once programming is complete and drive powered down apply jumper to LI1 and +24V for run command.
                                                  Note: Drive will run motor as soon as power is applied to the drive with this configuration.

                                                  What can cause an CFF fault on the ATV12 drives?

                                                  Issue:
                                                  What can cause an CFF fault  on the ATV12 drives?

                                                  Product Line:
                                                  Altivar ATV12

                                                  Environment:
                                                  All

                                                  Cause:
                                                  Drive is powering up with an CFF fault and will not clear.

                                                  Resolution:
                                                  CFF= incorrect configuration fault.

                                                  Possible causes:
                                                  -HMI block replaced by and HMI block configuration on a drive with a different HP ratings.
                                                  -The current parameter of the customers parameter is inconsistent.

                                                  Remedy:  Try resetting the drive back to a factory default by going into the
                                                  ConF  menu enter
                                                  FCS menu enter
                                                  change FCS menu to InI and hold for 2 seconds.
                                                  Now power cycle the drive.
                                                  If the fault clears now try and reprogram the drive.  If you are still getting the CFF fault you will need to replace the drive.

                                                  Is it possible to power the 230Vac ATV61 drive from DC Bus?

                                                  Issue:
                                                  Is it possible to power the  ATV61 drive 230Vac from DC Bus?

                                                  Product Line:
                                                  Altivar 61 ATV61

                                                  Environment:
                                                  230Vac , All series

                                                  Cause:
                                                  None

                                                  Resolution:
                                                  A separate DC source (approx 325Vdc) can be connected to PA/+ and PC/-  to power up the 230 Vac drive. DC Bus fuses are recommended for short circuit protection. No external Precharge resistor is necessary because it is built-in to the drive.

                                                  Is there a 4.5kw version of ATV12HU22M2?

                                                  No,there is not a 4.5kW version in the Altivar 12 series. 2.2kW is the largest size in the single to three phase range.

                                                  For motors larger than 2.2kW you need to have three phase input.

                                                  For further information please visit https://www.schneider-electric.com.au/documents/catalogue/2013-2014

                                                  What is the replacement for ATV31H055M2 VSD?

                                                   The replacement for ATV31H055M2 is  ATV312H055M2

                                                  ATV312H055M2 
                                                  variable speed drive ATV312 - 0.55kW - 1.4kVA - 46W - 200..240 V- 1-phase supply

                                                  For more information see;=https://www.schneider-electric.com.au/en/search/ATV312H055M2?category=product