Specifications

Design

Warranty

18 months

Range of product

Phaseo

Product or component type

redundancy module

Physical

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Mercury free

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

X

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

RoHS exemption information

Yes

Connections - terminals

  • for output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
  • for input connection: screw type terminals, connection capacity: 4 x 0.5...4 x 10 mm² AWG 20...AWG 8
  • for diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² AWG 14
    • Fixing mode

    • by clips on 35 mm symmetrical DIN rail, operating position: horizontal
    • by clips on 35 mm symmetrical DIN rail, operating position: vertical
      • Marking

        CE

        Local signalling

      • 1 LED per input (green) for power supply status
      • 1 relay for power supply status
        • Net weight

          0.7 kg

          Product certifications

        • EAC
        • RCM
          • Standards

          • CSA C22.2 No 60950-1
          • UL 508
            • Ambient air temperature for operation

              -25-60 °C

              Ambient air temperature for storage

              -40-85 °C

              Environmental characteristic

            • EMC conforming to EN 61000-6-3
            • EMC conforming to EN/IEC 61000-6-2
            • safety conforming to EN/IEC 60950-1
            • safety conforming to EN/IEC 61204
              • IP degree of protection

                IP20 conforming to EN/IEC 60529

                Relative humidity

              • 0-90 % during operation
              • 0-95 % during storage
                • Others

                  Package 1 Height

                  7 cm

                  Package 1 Length

                  16.6 cm

                  Package 1 Weight

                  644 g

                  Package 1 width

                  16.8 cm

                  Package 2 Height

                  30 cm

                  Package 2 Length

                  40 cm

                  Package 2 Weight

                  6.881 kg

                  Package 2 width

                  30 cm

                  Package 3 Height

                  80 cm

                  Package 3 Length

                  60 cm

                  Package 3 Weight

                  65.16 kg

                  Package 3 width

                  80 cm

                  Number of Units in Package 1

                  1

                  Number of Units in Package 2

                  10

                  Number of Units in Package 3

                  80

                  PVC free

                  Yes

                  Unit Type of Package 1

                  PCE

                  Unit Type of Package 2

                  S03

                  Unit Type of Package 3

                  P06

                  Input voltage

                  24...28.8 V DC

                  Output voltage

                  (Uin-0.2) V DC

                  Maximum output current

                  40 A

                  Input voltage limits

                  22...30 V

                  Input current

                  20 A

                  Number of output channels

                  1

                  Output protection type

                • against overload, protection technology: external protection by power supply
                • against short-circuits, protection technology: external protection by power supply
                  • Output coupling

                    parallel

                    Operating altitude

                    2000 m

                    Name of test

                  • electrostatic discharges conforming to EN/IEC 61000-4-2
                  • emission conforming to EN 61000-6-3
                  • induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3
                  • radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3
                  • rapid transient conforming to IEC 61000-4-4 level 3
                  • surge conforming to EN/IEC 61000-4-5 level 2
                  • conducted/radiated emissions conforming to EN 55022 class B
                  • emission conforming to EN 50081-1
                    • Compatibility code

                      ABL8R

                      Dielectric strength

                    • 500 V between input and ground
                    • 500 V between output and ground
                      • Overvoltage category

                        class II conforming to VDE 0106-1

                        MTBF reliability

                        2488391 H at 24 V DC with UTE C80-810 calculation method

                        Vibration resistance

                      • 2 gn (f= 11.9-150 Hz) conforming to EN/IEC 61131-2
                      • 3.5 mm (f= 3-11.9 Hz) conforming to EN/IEC 61131-2
                        • Show all specifications

                          Frequently Asked Questions

                          hide show

                          What is the mean time between failures (MTBF) for ABL8RPM24200?

                          The 2 MTBF values for ABL8RPM24200 are;

                          • 717000h for 100Vac
                          • 695000h for 240Vac

                           
                           
                           
                           

                          What is the replacement for ABL4RPM24100?

                          ABL8RPS24100

                          What is the operating temperature range on the ABL8WPS24200 and ABL8WPS24400 power supplies?

                          Issue:
                          Needs environmental data for ABL8WPS24200 and ABL8WPS24400.

                          Product Line:
                          Relays and Timers

                          Environment:
                          ABL Phaseo Power Supplies
                           
                          Resolution:
                          Per expanded catalog DIA3ED207041EN-US, page 30, "-13°F to 140°F with derating from 122 °F or  (-25 to +60 derating from 50°C)".

                          What is the alternative for ABL4RSM24100 Power Supply ?

                          Code = ABL8RPS24100
                           

                          What is the replacement power supply for the ABl7RE2410

                          The part code ABL4RSM24100

                          What is the alternate code for a ABL7RE2410

                          End of life 30/03/2008. Use a ABL8RPS24100.
                          Show More