Quantcast

Phaseo Redondancy Module, 40A, for Regulated SMPS

Phaseo Redondancy Module, 40A, for Regulated SMPS

Phaseo Redondancy Module, 40A, for Regulated SMPS

Item Number: ABL8RED24400

Retail
$748.69
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Phaseo

Product or component type

redundancy module

Warranty

18 months

Physical

Connections - terminals

  • for output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
  • for input connection: screw type terminals, connection capacity: 4 x 0.5...4 x 10 mm² AWG 20...AWG 8
  • for diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² AWG 14
    • Fixing mode

    • by clips on 35 mm symmetrical DIN rail, operating position: horizontal
    • by clips on 35 mm symmetrical DIN rail, operating position: vertical
      • Marking

        CE

        Local signalling

      • 1 LED per input (green) for power supply status
      • 1 relay for power supply status
        • Net weight

          0.7 kg

          Product certifications

        • EAC
        • RCM
          • Standards

          • CSA C22.2 No 60950-1
          • UL 508
            • Ambient air temperature for operation

              -25-60 °C

              Ambient air temperature for storage

              -40-85 °C

              Environmental characteristic

            • EMC conforming to EN 61000-6-3
            • EMC conforming to EN/IEC 61000-6-2
            • safety conforming to EN/IEC 60950-1
            • safety conforming to EN/IEC 61204
              • IP degree of protection

                IP20 conforming to EN/IEC 60529

                Relative humidity

              • 0-90 % during operation
              • 0-95 % during storage
                • REACh Regulation

                  Free of Substances of Very High Concern above the threshold

                  REACh free of SVHC

                  Yes

                  EU RoHS Directive

                  Pro-active compliance (Product out of EU RoHS legal scope)

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                  X

                  California proposition 65

                  WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

                  Others

                  Input voltage

                  24...28.8 V DC

                  Output voltage

                  (Uin-0.2) V DC

                  Maximum output current

                  40 A

                  Input voltage limits

                  22...30 V

                  Input current

                  20 A

                  Number of output channels

                  1

                  Output protection type

                • against overload, protection technology: external protection by power supply
                • against short-circuits, protection technology: external protection by power supply
                  • Output coupling

                    parallel

                    Operating altitude

                    2000 m

                    Name of test

                  • electrostatic discharges conforming to EN/IEC 61000-4-2
                  • emission conforming to EN 61000-6-3
                  • induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3
                  • radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3
                  • rapid transient conforming to IEC 61000-4-4 level 3
                  • surge conforming to EN/IEC 61000-4-5 level 2
                  • conducted/radiated emissions conforming to EN 55022 class B
                  • emission conforming to EN 50081-1
                    • Compatibility code

                      ABL8R

                      Dielectric strength

                    • 500 V between input and ground
                    • 500 V between output and ground
                      • Overvoltage category

                        class II conforming to VDE 0106-1

                        MTBF reliability

                        2488391 H at 24 V DC with UTE C80-810 calculation method

                        Vibration resistance

                      • 2 gn (f= 11.9-150 Hz) conforming to EN/IEC 61131-2
                      • 3.5 mm (f= 3-11.9 Hz) conforming to EN/IEC 61131-2
                        • Unit Type of Package 1

                          PCE

                          Number of Units in Package 1

                          1

                          Package 1 Weight

                          644 g

                          Package 1 Height

                          7 cm

                          Package 1 width

                          16.8 cm

                          Package 1 Length

                          16.6 cm

                          Unit Type of Package 2

                          S03

                          Number of Units in Package 2

                          10

                          Package 2 Weight

                          6.881 kg

                          Package 2 Height

                          30 cm

                          Package 2 width

                          30 cm

                          Package 2 Length

                          40 cm

                          Unit Type of Package 3

                          P06

                          Number of Units in Package 3

                          80

                          Package 3 Weight

                          65.16 kg

                          Package 3 Height

                          80 cm

                          Package 3 width

                          80 cm

                          Package 3 Length

                          60 cm

                          PVC free

                          Yes
                          Show all specifications

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • CAD Files and Packs

                          • Product Brochures

                          • Technical Data Catalogues

                          • Installation Instruction

                          • End of Life Manual

                          • Product Environmental

                          • Technical Drawing

                          • eTechPub

                          • Certificates (MSDS)

                          Frequently Asked Questions

                          hide show

                          What is the replacement for ABL4RSM24200?

                          Replacement is the ABL8RPM24200 .

                          What is the operating temperature range on the ABL8WPS24200 and ABL8WPS24400 power supplies?

                          Issue:
                          Needs environmental data for ABL8WPS24200 and ABL8WPS24400.

                          Product Line:
                          Relays and Timers

                          Environment:
                          ABL Phaseo Power Supplies
                           
                          Resolution:
                          Per expanded catalog DIA3ED207041EN-US, page 30, "-13°F to 140°F with derating from 122 °F or  (-25 to +60 derating from 50°C)".

                          What is the alternative to ABL4WSR24200?

                          Replacement is ABL8WPS24200

                          What can cause a ILF fault on the ATV71 drive with an VW3A3501 CIC card installed?

                          Issue:
                          ILF fault on the ATV71 with an  VW3A3501 CIC card installed.

                          Product line:
                          Altivar ATV71

                          Environment:
                          All models, all serial numbers 

                          Cause:
                          If the CIC card is missing the external +24vdc pwr supply the drive will trigger an ILF fault after 1 sec of being powered up.      

                          Resolution:
                          Per the CIC installation manual document, atv71_controller_inside_EN_V3 page 10, it is recommended to add an external power supply part number ABL7RE2402 to the controller inside cards +24vdc and com terminals to resolve issue.