Quantcast

PowerTag C IO 230V

Product Dimensions

Width icon

Width18 mm

Height icon

Height85 mm

Depth icon

Depth62 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

PowerTag

Product or component type

input and ouput module

Physical

Circularity Profile

ENVEOLI1812012EN

Environmental Disclosure

ENVPEP1812012EN

Mercury free

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

EU RoHS Directive

Compliant

RoHS exemption information

Yes

Range compatibility

  • impulse relay
  • contactor
  • iACTs remote indication auxiliary
  • iATLs remote indication auxiliary
    • Mechanical durability

      100000 cycles for output

      Mounting mode

      clip-on

      Mounting support

      DIN rail

      Local signalling

      green, orange and red LED for product status

      Height

      85 mm

      Width

      18 mm

      Depth

      62 mm

      Net weight

      80 g

      Connections - terminals

    • tunnel type terminals (top) - 1 cable(s) 1-16 mm² (AWG 18...AWG 16) - rigid
    • tunnel type terminals (top) - 1 cable(s) 0.5-10 mm² (AWG 21...AWG 8) - flexible
    • tunnel type terminals (bottom) - 1 cable(s) 1-6 mm² (AWG 18...AWG 10) - rigid
    • tunnel type terminals (bottom) - 1 cable(s) 0.5-4 mm² (AWG 21...AWG 12) - flexible
    • tunnel type terminals (bottom) - 1 cable(s) 0.5-4 mm² (AWG 21...AWG 12) - flexible with ferrule
    • tunnel type terminals (bottom) - 2 cable(s) 1.5-2.5 mm² (AWG 16...AWG 14) - rigid
    • tunnel type terminals (bottom) - 2 cable(s) 1.5-2.5 mm² (AWG 16...AWG 14) - flexible
      • Wire stripping length

      • 14 mm for top connection
      • 9 mm for bottom connection
        • Standards

        • EN/IEC 61010-1
        • ETSI EN 300 328
        • EN/IEC 62479
        • ETSI EN 301 489-17
        • ETSI EN 301 489-1
        • EN/IEC 61010-2-201
        • EN/IEC 61326-1
          • IP degree of protection

          • IP20 casing: conforming to IEC 60529
          • IP40 front face: conforming to IEC 60529
            • IK degree of protection

              IK05

              Relative humidity

              0-93 % at 40-40 °C conforming to IEC 60068-2-78

              Ambient air temperature for operation

              -25-60 °C

              Ambient air temperature for storage

              -40-85 °C

              Material

              Material

              PA6 GF30

              Others

              Number of Units in Package 1

              1

              Number of Units in Package 2

              80

              Number of Units in Package 3

              640

              Package 1 Height

              3 cm

              Package 1 Length

              11.5 cm

              Package 1 Weight

              116 g

              Package 1 width

              8 cm

              Package 2 Height

              30 cm

              Package 2 Length

              40 cm

              Package 2 Weight

              9.65 kg

              Package 2 width

              30 cm

              Package 3 Height

              80 cm

              Package 3 Length

              60 cm

              Package 3 Weight

              80.24 kg

              Package 3 width

              80 cm

              Unit Type of Package 1

              PCE

              Unit Type of Package 2

              S03

              Unit Type of Package 3

              P06

              WEEE

              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

              Device short name

              PowerTag C IO 230V

              Product name

              PowerTag Control

              Concentrator compatibility

            • Acti9 PowerTag Link C
            • Wiser IP module
            • Acti9 PowerTag Link
            • Acti9 PowerTag Link HD
              • Communication mode

                [Us] rated supply voltage

                230 V AC (+/- 20 %)

                Network frequency

                50/60 Hz

                Power consumption in VA

                2 VA

                Digital input number

                1

                Input type

                dry contact 230 V AC 2 mA

                Voltage state 1 guaranteed

                >= 164 V for digital input

                Voltage state 0 guaranteed

                <= 40 V for digital input

                Current state 1 guaranteed

                >= 2 mA (digital input)

                Current state 0 guaranteed

                <= 0.5 mA (digital input)

                Digital output number

                1

                Output type

                dry contact 230 V 0.01...2 A AC

                Discrete output type

                configurable relay logic

                Output function

                NO/NC programmable

                Impulse duration

                300 ms by default - 0 ms, + 300 ms

                Time between 2 impulse

                100 ms minimum - tolerance: - 0 ms, + 300 ms

                9 mm pitches

                2

                Tightening torque

              • power supply: 2-2 N.m top
              • digital input/output: 1-1 N.m bottom
                • Pollution degree

                  3

                  Overvoltage category

                  III conforming to IEC 61010-1

                  Operating altitude

                  0...2000 m

                  Fire resistance

                  960 °C / 30 s conforming to UL 94 V0
                  Show all specifications

                  Documents & downloads

                  hide show
                  Filter items
                  • All

                  • CAD Files and Packs

                  • Product Brochures

                  • Product Data Sheets

                  • Installation Instruction

                  • End of Life Manual

                  • Product Environmental

                  • Operating Manuals

                  • Application Solutions

                  • Declaration of Conformity

                  • Certificates (MSDS)

                  Frequently Asked Questions

                  hide show

                  Is it possible to send control command to PowerTag C A9XMC1D3 and A9XMC2D3 devices through PowerTag Link web page ?

                  Command with web page is not possible due to Cybersecurity reasons (HTTP requests).

                  You send a command with the following methods :
                  • EcoStruxure Power Commissioning
                  • Modbus write requests on Register Adress 0x90BA (Register Number 37051)

                  Is it possible to connect PowerTag C devices (I/O and 2DI) to SmartLink SI B or SI D ?

                  PowerTag C A9XMC1D3 and A9XMC2D3 cannot be connected to a Smartlink A9XMZA08 or A9XMWA20.
                  PowerTag C devices are only compatible with PowerTag Link gateways A9XMWD20 or A9XMWD100 with FW 1.4.5.