Quantcast

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, with Pulse, MID

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, with Pulse, MID

iEM2000 Series Modular Single Phase Power Meter, 230V, 63A, with Pulse, MID

Item Number: A9MEM2110

Retail
$573.32
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height90 mm

Depth icon

Depth64 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti 9

Product or component type

energy meter

Market segment

  • buildings small building cost management: billing: panelboard
  • buildings medium building cost management: billing: panelboard
  • buildings large building cost management: billing: panelboard
  • buildings multi-site cost management: billing: panelboard
  • datacenter cost management: billing: panelboard
  • healthcare cost management: billing: panelboard
  • industry cost management: billing: panelboard
  • buildings small building cost management: cost allocation: panelboard
  • buildings medium building cost management: cost allocation: panelboard
  • buildings large building cost management: cost allocation: panelboard
  • buildings multi-site cost management: cost allocation: panelboard
  • datacenter cost management: cost allocation: panelboard
  • healthcare cost management: cost allocation: panelboard
  • industry cost management: cost allocation: panelboard
    • Device application

    • sub billing
    • partial meter
    • multi-tariff
      • Physical

        [In] rated current

        63 A

        Rated voltage

        230-230 V +/- 20 %

        Communication port protocol

        -

        Local signalling

        red LED: accuracy checking 1...1000 p/kWh

        Mounting mode

        clip-on

        Mounting support

        DIN rail

        Connections - terminals

      • power circuit: tunnel type terminals (bottom) 1 1.65-33 mm² cable(s) solid
      • power circuit: tunnel type terminals (bottom) 1 1.65-33 mm² cable(s) stranded with cable end
      • pulse output: screw clamp terminals (top) 1 1-4 mm² cable(s) solid
      • pulse output: screw clamp terminals (top) 1 1-2.5 mm² cable(s) stranded with cable end
        • Wire stripping length

        • power circuit: 17 mm
        • pulse output: 6 mm
          • Standards

          • IEC 62053-31
          • IEC 62052-31
          • IEC 62053-21
          • IEC 62053-23
          • IEC 62052-11
            • Product certifications

            • MID conforming to EN 50470-1
            • MID conforming to EN 50470-3
            • CE
              • IP degree of protection

                IP20 conforming to IEC 60529

                Ambient air temperature for operation

                -25-55 °C

                Ambient air temperature for storage

                -25-70 °C

                Relative humidity

                0-95 %

                Width

                36 mm

                Height

                90 mm

                Depth

                64 mm

                Net weight

                0.175 kg

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                X

                Others

                Product name

                Acti 9 iEM2100

                Device short name

                iEM2110

                Poles description

                1P + N

                Type of measurement

              • active and reactive energy
              • active and reactive power
              • current
              • voltage
                • Metering type

                  active, reactive, apparent energy (signed, four quadrant)

                  Accuracy class

                • class 1 active energy conforming to IEC 62053-21
                • class B active energy conforming to EN 50470-3
                • class 2 reactive energy conforming to IEC 62053-23
                  • Analogue input type

                    direct input

                    Network frequency

                  • 60 Hz
                  • 50 Hz
                    • Frequency measurement range

                      45-65 Hz

                      Technology type

                      electronic

                      Display type

                      LCD display

                      Sampling rate

                      32 samples/cycle

                      Measurement current

                      0-63 A

                      Display digits

                      8

                      Maximum value measured

                      999999.99 kWh

                      Information displayed

                      tariff (2)

                      Communication port support

                      -

                      Number of inputs

                      1-1 digital

                      Number of outputs

                      2 pulse

                      Output voltage

                    • 3...33 V AC@90 mA
                    • 5...70 V DC@90 mA
                      • Impulse duration

                        30...100 ms

                        [Us] rated supply voltage

                        96...276 V AC 50 Hz

                        Maximum power consumption in VA

                        2 VA

                        Maximum power consumption in W

                        1 W

                        [Uimp] rated impulse withstand voltage

                        6 kV 1.2/50 µs

                        Tightening torque

                      • power circuit: 2-2 N.m PZ2 screwdriver
                      • pulse output: 0.5-0.5 N.m3.5 mm
                        • Compatibility code

                          iEM2110

                          Overvoltage category

                          III

                          Pollution degree

                          2

                          Flame retardance

                          V0 conforming to UL 94

                          9 mm pitches

                          4

                          Unit Type of Package 1

                          PCE

                          Number of Units in Package 1

                          1

                          Package 1 Weight

                          216 g

                          Package 1 Height

                          5.2 cm

                          Package 1 width

                          8 cm

                          Package 1 Length

                          9.8 cm

                          Unit Type of Package 2

                          S02

                          Number of Units in Package 2

                          29

                          Package 2 Weight

                          6.719 kg

                          Package 2 Height

                          15 cm

                          Package 2 width

                          30 cm

                          Package 2 Length

                          40 cm
                          Show all specifications

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • Product Brochures

                          • Technical Data Catalogues

                          • Technical Leaflet

                          • Installation Instruction

                          • Operating Manuals

                          • Certificates (MSDS)

                          • Declaration of Conformity

                          Frequently Asked Questions

                          hide show

                          Is the Acti 9 A9MEM3110 3 phase?

                          Yes, the iEM3110 kWh meter with pulse output, is a 3 phase digital meter for direct connection up to 63Amps.

                          Wiring diagram for iEM2000.

                          What is the product code for the iEM2000 Acti9 230V 40A din rail mount energy monitor?

                          The product code is A9MEM2000. Please see the attached datasheet for more information.
                           

                          What is the alternate part number for 17072

                           Replacement is a A9MEM3210

                          What is the alternative code for 17072?

                          A9MEM3210

                          ETSNZ - What Single Phase Check Meter does not Require a Neutral Through Connection

                          The New range of Acti9  A9MEM2150 for example only needs a N connection  - it does not require to pass the N current through it.
                          Show More