Quantcast

Acti9, Contactor iCT - 3 poles - 3 NO - 25 A - 220..240 V AC

Acti9, Contactor iCT - 3 poles - 3 NO - 25 A - 220..240 V AC

Acti9, Contactor iCT - 3 poles - 3 NO - 25 A - 220..240 V AC

Item Number: A9C20833

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height81 mm

Depth icon

Depth60 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

iCT

Range

Acti9

Product or component type

contactor

Device application

motor-heating-lighting

Product compatibility

  • iACTc
  • iACTp
  • iACTs
  • iATEt

Market segment

  • small commercial
  • residential

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ie] rated operational current

  • 25 A AC-7A
  • 8.5 A AC-7B

Control type

remote control

[Ue] rated operational voltage

400 V AC 50 Hz

Control signal type

maintained

Local signalling

action indicator

Mounting mode

clip-on

Mounting support

35 mm symmetrical DIN rail

Height

81 mm

Width

36 mm

Depth

60 mm

Mechanical durability

1000000 cycles

Electrical durability

  • 100000 cycles IEC/EN 61095 25 A 50 Hz AC-7A
  • 30000 cycles IEC/EN 61095 8.5 A 50 Hz AC-7B
  • 30000 cycles IEC/EN 61095 50 Hz AC-7C
  • 100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
  • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
  • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
  • 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b

Connections - terminals

  • control circuit: tunnel type terminals2 cable(s) 1.5-1.5 mm² rigid
  • power circuit: tunnel type terminals1 cable(s) 1-4 mm² flexible
  • power circuit: tunnel type terminals1 cable(s) 1.5-6 mm² rigid
  • control circuit: tunnel type terminals1 cable(s) 1.5-2.5 mm² rigid
  • control circuit: tunnel type terminals2 cable(s) 1.5-2.5 mm² flexible

Standards

IEC/EN 61095

IP degree of protection

  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-40...70 °C

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP110308EN

Others

Certification Number

DC-E-S26-076.1 - IRAM

Package 1 Bare Product Quantity

1

Product name

Acti9 iCT

Device short name

iCT

Poles description

3P

Pole contact composition

3 NO

Network type

AC

[Uc] control circuit voltage

220...240 V AC 50 Hz

Network frequency

50 Hz

Maximum power

1.6 W at 400 V AC

[Ui] rated insulation voltage

500 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

4 kV

Switching frequency

100 switching operations/day

Hold-in power consumption in VA

4.6...4.6 VA

Inrush power in VA

34 VA

9 mm pitches

4

Tightening torque

  • control circuit: 0.8...0.8 N.m
  • power circuit: 0.8...0.8 N.m

Compatibility code

iCT

Noise level

30 dB

Heat dissipation

1.6...1.6 W at 50/60 Hz

Pollution degree

2

Tropicalisation

  • 2 conforming to EN 60947-4-1
  • 2 conforming to EN 61095
  • 2 conforming to IEC 1095

Operating altitude

2000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4 cm

Package 1 Width

11.2 cm

Package 1 Length

12.2 cm

Package 1 Weight

227 g

Unit Type of Package 2

BB1

Number of Units in Package 2

6

Package 2 Height

11.5 cm

Package 2 Width

12.5 cm

Package 2 Length

25 cm

Package 2 Weight

1.437 kg

Unit Type of Package 3

S03

Number of Units in Package 3

36

Package 3 Height

30 cm

Package 3 Width

30 cm

Package 3 Length

40 cm

Package 3 Weight

9.043 kg
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Environmental Disclosure

  • Specifications

  • Application Notes

  • Declaration of Conformity

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Can we recommend using the Acti9 iCT contactor range as an emergency stop contactor?

Acti9 iCT contactors (ex:A9C2083) are only certified according to IEC 61095 Std for household and similar purposes.

They are not compliant according to IEC 60947-4-1 Std and we can not recommend to use in emergency stop function as they are not suitable for isolation in OFF position, nor in motor starting application.

For this kind of application we can recommend to use dedicated Motor Management solutions of TeSys range.