Mounting Block, 1 Gang, Intermediate Plate

White Electric | Mounting Block, 1 Gang, Intermediate Plate

Mounting Block, 1 Gang, Intermediate Plate

Item Number: 70B-WE

Retail
N/A
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Product or component type

mounting block

Sustainable offer status

Green Premium product

Physical

Fixing center

55 mm

Depth

25 mm

Length

99 mm

Width

52 mm

Number of gangs

1 gang

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP120506EN

Material

Material

PVC (polyvinyl chloride)

Others

Shape

rectangular

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

42 g

Package 1 Height

25 mm

Package 1 width

52 mm

Package 1 Length

99 mm
Show all specifications

Frequently Asked Questions

hide show

Where can I find programming assistance to set up an ATV61/ATV71 drive with an VW3A3316 Ethernet IP card using assemblies 20 and 70?

Issue:
Set up an ATV61/ATV71 drive with an VW3A3316 Ethernet IP card using assemblies 20 and 70?

Product Line:
Altivar ATV61 and ATV71 with Ethernet VW3A3316 option card.

Environment:
All

Cause:
Needs to set up an ATV61 drive with Ethernet IP card to use Assemblies 20 and 70.

Resolution:
PLC's Ethernet scanner module needs to be configured as follows
Assembly 20  2 words or 4 bytes (output table)
Assembly 70  2 words or 4 bypes (input table)
Configuration size 6
Single INT

Drives programming needs to be excactly like this there are no exceptions
Menu 1.6
Command menu
Reference 1 channel = Com card or NET
Profile= Seperate control
Command swtiching= C312
Command channel 1= Com card or NET
Command channel 2= terminal control
Reference 2 swtiching= C313
Reference 2 channel= AI2 or AI1 ( you choose)

Menu 1.7
Ref 1b switching = channel 1 active (applies only to the ATV61)

See the tables below for the assembly mapping for the Command word and for reading the ETA status.


Addtional important information about setting the speed referece from the network.


 

What is the temperature rating of a 9013FSG2J20? Will it work in hot water at 140 F?

 
Issue: 
What is the temperature rating of a 9013FSG2J20? Will it  work in hot water at 140 F?

Product Line:
Pressure Switches

Environment:
Pressure switches commercialized in the US

Cause:
What is the temperature rating of a 9013FSG2J20? Will it  work in hot water at 140 F?
 
Resolution:
The Media temperature for all 9013 F & G switches is minimum -30C (-22F) and maximum 125C (257F).

The ambient temperature is a minimum of -30C (-22F) and a maximum of 70C (158F).

Does a circuit breaker close if the UVR (MN) is not energized?

Issue:
Does a circuit breaker close if the UVR (MN) is not energized?

Product Line:
Masterpact, Powerpact, Legacy Circuit Breakers

Environment:
UVR not energized.


Resolution:
No. This release instantaneously opens the circuit breaker when the supply voltage drops below a value between 35% and 70% of rated voltage. If the release is not energized, the circuit breaker cannot be closed (either manually or electrically). Any attempt to close it will have no effect on the main contacts. Closing is possible when the release voltage reaches 85% of its rated value.

What is the line dip ride through time for the ATV61 and ATV71 drives?

Issue:
What is the line dip ride through time for the ATV61 and ATV71 drives?

Product Line:
Altivar 61 and Altivar 71 

Environment:
All

Cause:
Need to know how long the drive will 'ride through' a dip in line power

Resolution:

Maximum running time (without fault) at Under Voltage with Nominal Torque is:

1. 1000 msec. with a voltage 70% of nominal voltage
 
2. 500msec. with a voltage 40% of nominal voltage

Can I use an ATS48 type starter to supply a slip-ring motor?

The ATS48 could be used with Slip Ring motor, but due to the fact a Slip Ring motor is designed for high torque applications the most efficient answer would be to use an ATV71 / ATV930 / ATV950 constant torque variable speed drive. 

If a Soft Start Unit is to be used to start a Slip Ring Motor there are a number of things to be considered.

The resistors are to be removed and the Rota shorted out, but engineers agree that a small amount of resistance should be maintained.  This is usually achieved in the cables.

 

This has in theory turned the motor into a Squirrel cage motor with HIGH TORQUE starting.  To use a soft start on a high torque application the current limit must be set to maximum this would mean the motor would be able to pull high current to get it away.   The average starting current for a Slip Ring Motor is 250% of its Full Load Current where as if using a Soft Start it would be 700% of Full Load Current.   Using a 55Kw motor as an example at 400V

 

                                                     SLIP RING

                                                  FLC x 250 =      100 x 2.5 = 250A

 

                                                    SOFT START

                                                  FLC x 700 =      100 x 7 = 700A

 

As can be seen from the above calculations all the wiring and circuit equipment will have to be changed to be able to cope with the higher currents

 

So as previously stated the best option if you are replacing a Slip Ring Starter is to use an Altivar Variable Speed Drive from the ATV71 / ATV930 / ATV950 range