Quantcast

Clipsal Iconic Deep Mounting Block 1 Gang, 40mm

Vivid White | Clipsal Iconic Deep Mounting Block 1 Gang, 40mm

Clipsal Iconic Deep Mounting Block 1 Gang, 40mm

Item Number: 3000DM-VW

Retail
$11.10
RRP (Inc. GST)
Colour Vivid White (VW)
  • Vivid White 1 PCE

Product Dimensions

Width icon

Width140 mm

Height icon

Height91 mm

Depth icon

Depth40 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Product or component type

mounting block

Physical

Fixing center

84 mm

Depth

40 mm

Length

140 mm

Width

140 mm

Height

91 mm

Net weight

0.08 kg

Number of gangs

1 gang

EU RoHS Directive

Under investigation

Material

Material

  • PC (polycarbonate)
  • HIPS (high impact polystyrene)
    • Others

      Shape

      rectangular

      Package 1 Weight

      0.08 kg

      Package 1 Height

      40 mm

      Package 1 width

      91 mm

      Package 1 Length

      140 mm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Certificates (MSDS)

      Frequently Asked Questions

      hide show

      What is the part number for standard din rail?

      The part number for standard din rail is NSYSDR200B. It is 7.5mm deep by 2000mm long.

      Do you have a 45RU data cabinet 800mm Wide X 1000mm Deep?

      Yes, the part number is 3106N45C810-BK.

      What is the part number for a 45RU data cabinet , 800mm wide and 1000mm deep?

      The part number for a 45Ru data cabinet that has dimensions of W800m x D1000mm is - 3106N45C810

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=3106N45C810

      What is the code for a 2 pole, 10A, MCB suitable for 300Vdc?

      The code will be A9N61528. This is C curve, 6kA, and rated up to 500Vdc

      For more information see below:
      https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9N61528
       

      What is the Pin out detail for the Modbus programming cable 110 XCA 20 3000?

      The pin out details of the Modbus programming cable 110 XCA 20300 is as shown in the attached.

       

      What is the altitude derating for a TeSys D-Line contactor?

      Issue:​
      What is the altitude derating for a TeSys D-Line contactor?

      Product Line:
      Digest 177 Section 18 : Contactors and Starters, IEC

      Environment:
      North American Products

      Resolution:
      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

      Voltage
      3500m x 0.90
      4000m x 0.80
      4500m x 0.70
      5000m x 0.60

      Current
      3500m x 0.92
      4000m x 0.90
      4500m x 0.88
      5000m x 0.86

      For example, an LC1D80 at 5000 meters:
      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



       
      Show More