Quantcast

Push Button LED 2 Gang Architrave Switch Impress

White Electric | Push Button LED 2 Gang Architrave Switch Impress

Push Button LED 2 Gang Architrave Switch Impress

Item Number: 2032APBL-WE

Retail
N/A
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • Series 2000
  • Impress
    • Product or component type

      push-button

      Product brand

      Clipsal

      Physical

      Device presentation

      basic element with full cover plate

      Actuator

      push-button

      Local signalling

      indicator light

      Fixing mode

      by screws

      [Ue] rated operational voltage

      250 V AC

      Inrush current

      20 A

      Depth

      30 mm

      Width

      34 mm

      Length

      86 mm

      Fixing center

      70 mm

      Mounting position

      vertical

      EU RoHS Directive

      Under investigation

      Material

      Material

      plastic

      Others

      Package 1 Height

      30 mm

      Package 1 Length

      86 mm

      Package 1 width

      34 mm

      Package 1 Weight

      0.07 kg
      Show all specifications

      Frequently Asked Questions

      hide show

      What is the part number for a replacement cover plate for the 4062PBL?

      The part number for a replacement cover plate for the 4062PBL is - 4062PBC

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=4062PBC
      User-added image

      False Events When Using A SEL 2020/2030 and ION Enterprise

      Goals and Symptoms

      Summary

      SEL 2030 devices are used to communicate with Schweitzer Engineering Laboratories (SEL) relays. The relays only communicate with SEL proprietary protocol. The 2030 can convert this to Modbus for the use of PRODUCTS such as ION Enterprise 5.0.
      We use the name SEL 2030 but this article also applies to other modules in this product family including the SEL 2020 and SEL 2032.

      ION Enterprise 5.0 is configured to translate the Modbus data into the ION network. Within this network a Virtual ION Processor (VIP) can be used to perform logical actions based on the information obtained from the relay.

      One common action is to detect a change in state of a Boolean value. A series of VIP Setpoint modules can be configured to monitor the state of each value.  When the state changes the VIP Setpoint module records an event but can also be used to trigger an action.

      Symptoms

      The VIP Setpoint module shows repeated events without an actual change in the relay state.  This may always appear as an OFF event.

      Causes and Fixes

      Cause

      The ION Enterprise Modbus master repeatedly asks the SEL 2030 for updates.  If the SEL 2030 is providing the data directly from the port which the relay is attached to (as opposed to the port the master is attached to) then the SEL 2030 will randomly reply with Modbus exceptions. These happen when the incoming request happens at the same time as the relay is updating its information in the SEL 2030.

      These Modbus exceptions may cause a VIP Setpoint module to incorrectly register an event.

      Workaround

      There are two ways to work around this problem.

      On newer SEL 2030 devices the master port can be configured to not send exceptions when it is busy. In the port set-up configure the "BUSY_DIS" setting to "Yes" from the default "No"

      On all SEL 2030 devices you can use Memory Move commands to remap the individual relay's data into the memory used by the Modbus master. 

      Attachments

       

      • (Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/dc5af2e8c4694664c125765d001625da/fl_block_5/0.1AF2?OpenElement&FieldElemFormat=gif)

        Original article#10181

        All content © 1992-2007 Schneider Electric


      Legacy KB System (APS) Data: RESL186793 V2.0, Originally authored by KBAdPM on 07/10/2007, Last Edited by DaMi on 10/28/2009
      Related ranges: VIP, ION Enterprise V5.0, Modbus / JBus