Acti9 iID Residual current circuit breaker (RCCB) 2P, 80A, A type, 100mA

Home ProductsCircuit ProtectionActi9Residual current circuit breaker (RCCB)

Acti9 iID Residual current circuit breaker (RCCB) 2P, 80A, A type, 100mA

Item Number: A9R22280

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Embedding depth icon

Embedding depth44 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product iID
Range Acti9
Product or component type residual current circuit breaker (RCCB)
Market segment small commercial
Warranty 18 months

Physical

[in] rated current 80 A
[ue] rated operational voltage 230...240 V AC 50/60 Hz
Control type toggle
Mounting mode clip-on
Mounting support 35 mm DIN rail
Height 85 mm
Width 36 mm
Depth 69 mm
Embedding depth 44 mm
Net weight 210 g
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals
  • single terminal top or bottom 1-35 mm² rigid
  • single terminal top or bottom 1-25 mm² flexible
  • single terminal top or bottom 1-25 mm² flexible with ferrule
Wire stripping length 14 mm for top or bottom connection
Standards
  • AS/NZS 61008.1
  • IEC 61008-2-1
Ip degree of protection
  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...85 °C
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1409014EN
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Package 1 bare product quantity 1
Package 2 bare product quantity 54
Legacy weee scope In
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Average percentage of recycled plastic content 0 %
At least in Europe
Product name Acti9 iID
Device short name iID
Poles description 2P
Neutral position left
Network type AC
Earth-leakage sensitivity 100 mA
Earth-leakage protection time delay instantaneous
Earth-leakage protection class type A
Quality labels
  • RCM
  • VDE
Device location in system outgoer
Network frequency 50/60 Hz
Residual current tripping technology voltage independent
Rated breaking and making capacity
  • Idm 1500 A
  • Im 1500 A
Rated conditional short-circuit current 10 kA
[ui] rated insulation voltage 500 V AC 50/60 Hz
[uimp] rated impulse withstand voltage 6 kV
Contact position indicator yes
Comb busbar and distribution block compatibility top or bottom: tooth
Connection pitch 18 mm between phase and neutral
9 mm pitches 4
Power losses per pole 5.6 W
Locking options description padlocking device
Tightening torque 3.5...3.5 N.m top or bottom
Compatibility code iID
Pollution degree 3
Electromagnetic compatibility 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 4.200 cm
Package 1 width 8.300 cm
Package 1 length 9.900 cm
Package 1 weight 218.000 g
Unit type of package 2 S03
Number of units in package 2 54
Package 2 height 30.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 12.220 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 33 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 1.8483865475955814
Carbon footprint of the manufacturing phase [a1 to a3] 2 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.04700361817642444
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.020849790844422712
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 30.159641595598565
Carbon footprint of the use phase [b2, b3, b4, b6] 30 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 0.5430050471072231
Carbon footprint of the end-of-life phase [c1 to c4] 0.5 kg CO2 eq.
Energy efficiency optimized False
F-gas free N/A
Updatability N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 32.61888659932222
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
Scip number b078722f-7853-4e1e-a05b-29638f57b0ab
End of life manual availability N/A
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18