Acti9 iC60N Miniature Circuit Breaker 2P 50A D

Home ProductsCircuit ProtectionActi 9Miniature Circuit Breaker

Acti9 iC60N Miniature Circuit Breaker 2P 50A D

Item Number: A9F45250

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Depth icon

Depth78.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Range of product

Acti9

Product or component type

miniature circuit-breaker

Physical

[in] rated current

50 A

[ue] rated operational voltage

440 V AC 50/60 Hz

Control type

toggle

Local signalling

trip indicator

Mounting mode

clip-on

Mounting support

rail

Height

85 mm

Width

36 mm

Depth

78.5 mm

Net weight

0.25 kg

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Connections - terminals

single terminal (top or bottom) 1-35 mm² rigid|single terminal (top or bottom) 1-25 mm² flexible

Wire stripping length

14 mm for top or bottom connection

Standards

EN/IEC 60947-2|EN/IEC 60898-1

Ip degree of protection

IP20 conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-35...70 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Package 1 bare product quantity

1

Product name

Disbo iC60

Device short name

IC60N

Poles description

2P

Number of protected poles

2

Network type

AC

Trip unit technology

thermal-magnetic

Curve code

D

Breaking capacity code

N

Breaking capacity

10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2|6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1|36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2|20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2|10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2|6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation category

category A conforming to EN/IEC 60947-2

Network frequency

50/60 Hz

Magnetic tripping limit

12 x In +/- 20 %

[ics] rated service breaking capacity

27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz|15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz|7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz|4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz|6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz|6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC

Limitation class

3 conforming to EN/IEC 60947-2

[ui] rated insulation voltage

500 V AC 50/60 Hz

[uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

yes

Connection pitch

18 mm between phases

9 mm pitches

4

Total power losses

8.0 W

Power losses per pole

4.0 W

Provision for padlocking

padlockable

Tightening torque

3.5...3.5 N.m top or bottom

Earth-leakage protection

separate block

Compatibility code

iC60

Pollution degree

3 conforming to EN/IEC 60947-2

Tropicalisation

2 conforming to IEC 60068-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

3.6 cm

Package 1 width

7.5 cm

Package 1 length

9 cm

Package 1 weight

254 g

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins