Canalis KBB, Straight length, 25A, 2 circuits 3L+N+PE/L+N+PE, 5 tap-off units, 3m

Canalis KBB, Straight length, 25A, 2 circuits 3L+N+PE/L+N+PE, 5 tap-off units, 3m

Item Number: KBB25ED42305

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Canalis

Range of product

Canalis

Product compatibility

KBB

Product or component type

busbar trunking

Device application

  • power socket distribution
  • lighting

Warranty

18 months

Physical

[ie] rated operational current

25 A at 35 °C

[ue] rated operational voltage

230...400 V

Control type

without

Mounting mode

by screws

Standards

  • EN/IEC 61439-6
  • EN/IEC 61439-1

Width

30 mm

Height

46 mm

Length

3 m

Net weight

4.7 kg

Ip degree of protection

IP55 conforming to EN/IEC 60529

Ik degree of protection

IK06 conforming to EN/IEC 62262

Ambient air temperature for operation

  • 0...35 °C (100 % of In)
  • 35...40 °C (96 % of In)
  • 40...45 °C (93 % of In)
  • 45...50 °C (89 % of In)
  • 50...55 °C (85 % of In)

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Environmental disclosure

ENVPEP061102EN

Others

Device short name

KBB

Busbar description

straight length

Network frequency

50/60 Hz

Busbar trunking polarity

3L + N + PE

Number of circuits

2

Number of tap-off outlets

5

[uimp] rated impulse withstand voltage

4 kV

[ui] rated insulation voltage

690 V

[icw] rated short-time withstand current

0.44 kA

[ipk] rated peak withstand current

4.4 kA

Thermal stress limit

195 kA².s

Maximum radiated magnetic field

2 pT

Thdi

  • 0...15 % 25 A
  • 15...33 % 20 A
  • 33...100 % 16 A

Maximum voltage drop

  • <0.72 V with power factor = 1 at 50 Hz with 1A for 100 m long
  • <0.67 V with power factor = 0.9 at 50 Hz with 1A for 100 m long
  • <0.61 V with power factor = 0.8 at 50 Hz with 1A for 100 m long
  • <0.55 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Linear resistance

  • 6.8 mΩ/m R20 20 °C phase conductor
  • 8.3 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor
  • 0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor
  • 8.33 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor
  • 27.21 mΩ/m R0 20 °C symmetrical components method Ph/N
  • 0.85 mΩ/m X0 20 °C symmetrical components method Ph/N
  • 27.22 mΩ/m Z0 20 °C symmetrical components method Ph/N
  • 13.61 mΩ/m Rb0 20 °C impedance method Ph/Ph
  • 13.61 mΩ/m Rb0 20 °C impedance method Ph/N
  • 0.8 mΩ/m protective conductor
  • 17.28 mΩ/m R0 20 °C symmetrical components method Ph/PE
  • 5.25 mΩ/m X0 20 °C symmetrical components method Ph/PE
  • 18.06 mΩ/m Z0 20 °C symmetrical components method Ph/PE
  • 10.26 mΩ/m Rb0 20 °C impedance method Ph/PE
  • 16.59 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph
  • 16.59 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N
  • 11.77 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE
  • 0.35 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph
  • 0.35 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N
  • 0.07 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE

Unit type of package 1

PCE

Number of units in package 1

1
Show all specifications