FAQ000241028
05 August 2022
It is possible to assign a separate logic input to activate fire mode if required. For forced fire function, there is a function F659 that allows it to be enabled via logic input.
- When parameter F659 is set to 1, if the logic input is set to 0 the function is disabled. If the logic input is set to 1 the function is enable.
- When parameter F659 is set to 2, if the logic input is set to 1 the function is disabled. If the logic input is set to 0 the function is enable.
F111, F112 or F113 – Must be set to 53, this would be the assignment of a logic input to Fire/Forced mode.
53=fire mode , This function enables the "Fire" mode
OFF: No function
ON: Motor runs at speed set by F294
Note: F650, F659 and F294 must be configured to activate this function.
Please refer to ATV212 programming manual in the link: https://www.se.com/ww/en/download/document/S1A53838/