Acti9 PowerTag Link Display (A9XMWRD) shows only the first 20 PowerTags connected to PowerTag Link HD (A9XMWD100). Is it normal?
FAQ000230491
09 February 2022
Please see below details from the PowerTag Link User Guide (DOCA0157EN
).
Please note that one PowerTag Link HD gateway can only be paired to ONLY ONE PowerTag Link Display (A9XMWRD).
Please see below details from the same user guide.
Therefore, there is no way to display all the PowerTags configured to PowerTag Link HD through PowerTag Link Display (A9XMWRD).As a solution you can;1.Have a separate PowerTag Link Display (A9XMWRD) configured to each gateway with 20 PowerTag sensors.OR2. Have configured one FDM128 display to monitor up to 8 PowerTag Link or PowerTag Link HD gateways.In case of PowerTag Link HD (A9XMWD100) is used as a gateway then max number of 40 PowerTag sensors can be viewed.For example if a customer wants to view details of 100 PowerTags in FDM128 then architecture with 2 PowerTag Link HD (40 sensors per PowerTag Link HD) and 1 PowerTag Link-A9XMWD20 (20 sensors PowerTag Link) can be used.Please see more details in the FDM128 User Guide (DOCA0037EN
).