Modbus serial device configured to EcoStruxure Panel Server – Universal indicates ‘Connected’, but NO upstream access and communication to the device. What to check?

FAQ000230043

04 January 2022

Added Modbus serial devices to EcoStruxure Panel Server are considered as ‘Connected’ when;
- EcoStruxure Panel Server  sends Modbus request to Slave Device
- If the Slave Device answers something (Modbus Exception included), then slave is considered as ‘Connected’

Therefore, it is possible for you to see the serial slave device as ‘Connected’ but no upstream communication or measurements visible due to settings issue.
In this scenario, please double check the Modbus serial settings on both the slave device and EcoStruxure Panel Server are matching.