How can an ATV212 drive be setup to ignore a com fault and continue running at same speed before the fault?

FA271673

22 July 2022

Issue:
Ignoring a com fault and continue running at same speed before the fault with an ATV212.

Product Line:
ALTIVAR 212

Environment:
All

Cause:
Ride through functionality in case of communications faults.

Resolution:
Set parameter F851 = 1
In case of a network communication loss, the VFD will not go to a fault status, but rather continue with the last commanded operation.  If stopped, it will remain stopped.  If running, it will remain running at the last speed reference given.
Consider safety ramifications for this action.
;