FA246405
26 August 2022
Issue:The ATS22 softstart unit trips on Ground Fault (GrdF).
Product Line:ATS22
Environment:All
Cause:Tripping the unit
Resolution:This is a Ground Leakage current detected fault.
Check the motor and wires insulation.
Check for proper installation and Grounding.
Check the settings Grdd, Grdt parameters in PrO menu.