How is damper control configured on the ATV212 series drive?

FA245977

28 September 2021

Issue:
Damper control configuration on the ATV212 series drive

Product Line:
Altivar 212 series drives.
 
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
 
Cause:
Damper control configuration assistance needed with this drive.
 
Resolution:
 
Damper control on the ATV212 drive requires 3 settings to be adjusted.   You need to configure a relay output to control the damper, then you need to configure a logic input to monitor the damper status via the damper end switch, and finally the parameter F580 needs to be configured for the type of feedback switch your damper has.  See details from the ATV212 Programming manual below: