FA175205
04 August 2022
Issue:After replacing the ATV58 with an ATV61 the HOA reference source is working backwards.
Product Line:EconoFlex 58
Environment:All
Cause: Reference analog input programming needs to be changed on the new ATV61 drive.
Resolution:New ATV61 needs to be programmed.
- Menu 1.6 Command menu
- Ref 1 = AI2
- Ref 1 B switching = LI3
- Ref 1 B channel is AI1
- Logic input LI3 is low for auto and high for hand.