What is the difference between instantaneous auxiliary and fault signaling contacts on the GV2?

FA129611

28 September 2021

Issue:
Difference between instantaneous and fault signaling auxiliary contacts

Product Line: 
Contactors and Starters - IEC 

Environment:
Tesys GV Manual Starter

Resolution:
The instantaneous aux contacts change state to follow the GV2 control as it is mechanically moved to the energized or deenergized position. The fault signaling contacts change state in the event of any fault (i.e. overload or short circuit) condition only. Otherwise, they are not affected by the movement of the control from energized to deenergized state.
;