How to display Float data type register value of an external device like PLCs at XBT GT terminal screen correctly.

FA11565

30 September 2021

To display correctly float data type register value on Magelis XBT GT terminal screen, it is required to make sure to select ‘Low Order First’ option under “Double word-word order” drop down under Equipment Configuration tool.

Above said selection can be done while configuring driver settings in Vijeo Designer.
 
After making selection words occupied for Float register gets swapped internally in Vijeo Designer side in order to display correctly float data type register value available from external device like PLCs.