Why for the same apparent power, the nominal current of the transformer and the generators are different in My Ecodial L.

FA135428

16/09/2017

This difference is due to the fact that the nominal current of the transformer is calculated by using the voltage at no-load
and the nominal current of the generator is calculated by using the rated voltage. The use of the voltage at no-load is provided by
the IEC 60076-1 standard.