TeSys GV2 Motor circuit breaker TeSys Deca,3P,6-10A,thermal magnetic,screw clamp terminals,toggle handle

Home ProductsIndustrialTeSysMotor circuit breaker

TeSys GV2 Motor circuit breaker TeSys Deca,3P,6-10A,thermal magnetic,screw clamp terminals,toggle handle

Item Number: GV2RT14

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth78.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys Deca

Range of product

  • TeSys GV2
  • TeSys Deca

Product or component type

motor circuit breaker

Device application

  • motor protection
  • transformer

Warranty

18 months

Physical

Control type

toggle

[in] rated current

10 A

[ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

100000 cycles

Electrical durability

  • 100000 cycles for AC-3 at 415 V In
  • 100000 cycles for AC-3e at 415 V In

Connections - terminals

  • power circuit: screw clamp terminal 2 cable(s) 1-6 mm²solid
  • power circuit: screw clamp terminal 2 cable(s) 1.5-6 mm²flexible without cable end
  • power circuit: screw clamp terminal 2 cable(s) 1-4 mm²flexible with cable end

Fixing mode

  • 35 mm symmetrical DIN rail: clipped
  • panel: screwed (with adaptor plate)

Mounting position

  • horizontal
  • vertical

Width

45 mm

Height

89 mm

Depth

78.5 mm

Standards

  • EN/IEC 60947-2
  • EN/IEC 60947-4-1

Product certifications

  • CCC
  • UL
  • CSA
  • EAC
  • LROS (Lloyds register of shipping)
  • BV
  • UKCA

Ik degree of protection

IK04

Ip degree of protection

IP20 conforming to IEC 60529

Climatic withstand

conforming to IACS E10

Ambient air temperature for storage

-40...80 °C

Ambient air temperature for operation

-20...60 °C

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP121004

Eu rohs directive

Compliant with Exemptions

Reach regulation

Reference contains Substances of Very High Concern above the threshold

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Legacy weee scope

In

Package 1 bare product quantity

1

Average percentage of recycled plastic content

0 %

At least in Europe

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product name

TeSys GV2

Device short name

GV2RT

Trip unit technology

thermal-magnetic

Poles description

3P

Network type

AC

Utilisation category

  • category A conforming to IEC 60947-2
  • AC-3 conforming to IEC 60947-4-1
  • AC-3e conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-2

Motor power kw

  • 1.5...1.5 kW at 220/230 V AC 50/60 Hz motor protection high peak current
  • 2.2.2 kW at 220/230 V AC 50/60 Hz motor protection high peak current
  • 3 kW at 400/415 V AC 50/60 Hz motor protection high peak current
  • 4 kW at 400/415 V AC 50/60 Hz motor protection high peak current
  • 4 kW at 440 V AC 50/60 Hz motor protection high peak current
  • 4 kW at 500 V AC 50/60 Hz motor protection high peak current
  • 5.5.5 kW at 500 V AC 50/60 Hz motor protection high peak current
  • 5.5.5 kW at 690 V AC 50/60 Hz motor protection high peak current
  • 7.5...7.5 kW at 690 V AC 50/60 Hz motor protection high peak current
  • 2.5...2.5 kW at 230/240 V AC 50/60 Hz transformer protection
  • 4 kW at 400/415 V AC 50/60 Hz transformer protection
  • 5 kW at 400/415 V AC 50/60 Hz transformer protection
  • 5 kW at 440 V AC 50/60 Hz transformer protection
  • 5 kW at 500 V AC 50/60 Hz transformer protection
  • 6.3...6.3 kW at 500 V AC 50/60 Hz transformer protection

Breaking capacity

  • 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

Thermal protection adjustment range

6...10 A conforming to IEC 60947...2

Magnetic tripping current

200 A

[ith] conventional free air thermal current

10 A conforming to IEC 60947-2

[ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Suitability for isolation

yes conforming to IEC 60947-1

Power dissipation per pole

2.5 W

Maximum operating rate

25 cyc/h

Rated duty

uninterrupted conforming to IEC 60947-4-1

Tightening torque

1.7 N.m - on screw clamp terminal

Compatibility code

GV2RT

Fire resistance

960 °C conforming to IEC 60695-2-11

Mechanical robustness

  • shocks: 30 Gn for 11 ms
  • vibrations: 5 Gn, 5...150 Hz

Operating altitude

<= 2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.7 cm

Package 1 width

9.5 cm

Package 1 length

8.5 cm

Package 1 weight

278 g

Unit type of package 2

S02

Number of units in package 2

24

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

6.953 kg

Unit type of package 3

P06

Number of units in package 3

288

Package 3 height

75 cm

Package 3 width

60 cm

Package 3 length

80 cm

Package 3 weight

92.872 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

42 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

1.215349398124056

Carbon footprint of the manufacturing phase [a1 to a3]

1 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.06632991538488069

Carbon footprint of the distribution phase [a4]

0.1 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.024988562296268852

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

40.392

Carbon footprint of the use phase [b2, b3, b4, b6]

40 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.5315281159831791

Carbon footprint of the end-of-life phase [c1 to c4]

0.5 kg CO2 eq.

F-gas free

N/A

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

42.230195991788385

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Scip number

26be41f9-3f94-42e0-8ac0-5c45e1766355

End of life manual availability

ENVEOLI121004

Take-back

No

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Data Bulletin

  • Installation Instruction

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.