Canalis KDP, Distribution flexible length, 20A, 192m, 1.50m between tap-offs

Home ProductsCable ManagementCanalis KDPDistribution flexible length

Canalis KDP, Distribution flexible length, 20A, 192m, 1.50m between tap-offs

Item Number: KDP20ED4192150

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Canalis

Range of product

Canalis

Product or component type

busbar trunking

Product compatibility

KDP

Device application

power socket distribution|lighting

Warranty

18 months

Physical

[ue] rated operational voltage

230...400 V

[ie] rated operational current

20 A at 35 °C

Type of packing

reel

Standards

EN/IEC 60439-2|EN/IEC 61439-6

Length

192 m

Net weight

61.44 kg

Ip degree of protection

IP55 conforming to IEC 60529

Ik degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

35...40 °C (93 % of In)|40...45 °C (85 % of In)|45...50 °C (76 % of In)|50...55 °C (66 % of In)|0...35 °C (100 % of In)

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Environmental disclosure

ENVPEP061103EN

Others

Device short name

KDP

Busbar description

flexible bar

[uimp] rated impulse withstand voltage

4 kV

[ui] rated insulation voltage

690 V

[icw] rated short-time withstand current

0.34 kA

[ipk] rated peak withstand current

3.6 kA

Network frequency

50/60 Hz

Maximum radiated magnetic field

2 pT

Thdi

0...15 % 20 A|15...33 % 16 A|33...100 % 14 A

Maximum voltage drop

<0.72 V with power factor = 1 at 50 Hz with 1A for 100 m long| <0.65 V with power factor = 0.9 at 50 Hz with 1A for 100 m long| <0.58 V with power factor = 0.8 at 50 Hz with 1A for 100 m long| <0.5 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Linear resistance

6.8 mΩ/m R20 20 °C phase conductor|0.85 mΩ/m X0 20 °C symmetrical components method Ph/PE|27.22 mΩ/m Z0 20 °C symmetrical components method Ph/PE|13.61 mΩ/m Rb0 20 °C impedance method Ph/Ph|13.61 mΩ/m Rb0 20 °C impedance method Ph/N|13.61 mΩ/m Rb0 20 °C impedance method Ph/PE|16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/Ph|16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/N|16.6 mΩ/m Rb1 35 °C at Inc with impedance method Ph/PE|0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/Ph|0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/N|8.3 mΩ/m R1 35 °C at Inc and 50 Hz phase conductor|0.04 mΩ/m Xb 35 °C at Inc and 50 Hz with impedance method Ph/PE|0.02 mΩ/m X1 35 °C at Inc and 50 Hz phase conductor|8.3 mΩ/m Z1 35 °C at Inc and 50 Hz phase conductor|7.25 mΩ/m 20 °C protective conductor|27.21 mΩ/m R0 20 °C symmetrical components method Ph/N|0.85 mΩ/m X0 20 °C symmetrical components method Ph/N|27.22 mΩ/m Z0 20 °C symmetrical components method Ph/N|27.21 mΩ/m R0 20 °C symmetrical components method Ph/PE

Busbar trunking polarity

L2 + L1 + L3 + N + PE

Tap-off unit interval

1500 mm
Show all specifications