Zelio Logic Discrete I/O extension module 6 I/O, 100...240V AC

Home ProductsIndustrialZelio LogicDiscrete I/O extension module

Zelio Logic Discrete I/O extension module 6 I/O, 100...240V AC

Item Number: SR3XT61FU

This Zelio Logic SR3 discrete I/O extension module smart relays uses a supply voltage of 100V-240V alternating current. It has 6 inputs / outputs contact with screw-clamp terminals. It enables simple ladder programming, adapted for non-specialists.

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Zelio Logic

Product or component type

discrete I/O extension module

Warranty

18 months

Physical

Backup time

10 years at 25 °C

Electrical durability

  • AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1
  • AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1
  • DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1
  • DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1

Mechanical durability

10000000 cycles for relay output

Connections - terminals

  • screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
  • screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid

Net weight

0.125 kg

Product certifications

  • CSA
  • GOST
  • C-Tick
  • UL
  • GL

Standards

  • IEC 61000-4-11
  • IEC 60068-2-27 Ea
  • IEC 61000-4-4 level 3
  • IEC 61000-4-5
  • IEC 61000-4-12
  • IEC 60068-2-6 Fc
  • IEC 61000-4-2 level 3
  • IEC 61000-4-3
  • IEC 61000-4-6 level 3

Ip degree of protection

  • IP20 (terminal block) conforming to IEC 60529
  • IP40 (front panel) conforming to IEC 60529

Environmental characteristic

  • EMC directive conforming to IEC 61000-6-2
  • EMC directive conforming to IEC 61000-6-3
  • EMC directive conforming to IEC 61000-6-4
  • EMC directive conforming to IEC 61131-2 zone B
  • low voltage directive conforming to IEC 61131-2

Ambient air temperature for operation

  • -20...40 °C in non-ventilated enclosure conforming to IEC 60068...2-1 and IEC 60068...2-2
  • -20...55 °C conforming to IEC 60068...2-1 and IEC 60068...2-2

Ambient air temperature for storage

-40...70 °C

Relative humidity

95 % without condensation or dripping water

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP2011013EN

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Reach regulation

Reference contains Substances of Very High Concern above the threshold

China rohs regulation

X

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope

In

Average percentage of recycled plastic content

0 %

At least in Europe

Package 2 bare product quantity

48

Package 1 bare product quantity

1

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Number or control scheme lines

120 with ladder programming

Cycle time

6...90 ms

Clock drift

12 min/year at 0-55 °C

Checks

program memory on each power up

[us] rated supply voltage

100...240 V AC

Supply voltage limits

85...264 V

Supply frequency

50/60 Hz

Reverse polarity protection

with

Discrete input number

4

Discrete input voltage

100...240 V AC

Discrete input current

0.6 mA

Discrete input frequency

  • 57...63 Hz
  • 47...53 Hz

Voltage state 1 guaranteed

>= 79 V for discrete input

Voltage state 0 guaranteed

<= 40 V for discrete input

Current state 1 guaranteed

>= 0.17 mA (discrete input)

Current state 0 guaranteed

<= 0.5 mA (discrete input)

Input impedance

350 kOhm for discrete input

Number of outputs

2 relay

Output voltage limits

  • 5...30 V DC (relay output)
  • 24...250 V AC

Contacts type and composition

NO for relay output

Output thermal current

8 A for all 2 outputs for relay output

Switching capacity in ma

>= 10 mA at 12 V (relay output)

Operating rate in hz

  • 0.1 Hz (at Ie) for relay output
  • 10 Hz (no load) for relay output

[uimp] rated impulse withstand voltage

4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1

Response time

  • 50 ms with ladder programming (from state 0 to state 1) for discrete input
  • 50 ms with ladder programming (from state 1 to state 0) for discrete input
  • 50...255 ms with FBD programming (from state 0 to state 1) for discrete input
  • 50...255 ms with FBD programming (from state 1 to state 0) for discrete input
  • 10 ms (from state 0 to state 1) for relay output
  • 5 ms (from state 1 to state 0) for relay output

Tightening torque

0.5 N.m

Overvoltage category

III conforming to IEC 60664-1

Disturbance radiated/conducted

class B conforming to EN 55022-11 group 1

Pollution degree

2 conforming to IEC 61131-2

Operating altitude

2000 m

Maximum altitude transport

3048 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

6.000 cm

Package 1 width

6.500 cm

Package 1 length

11.000 cm

Package 1 weight

118.000 g

Unit type of package 2

S03

Number of units in package 2

48

Package 2 height

30.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

6.149 kg

Total lifecycle carbon footprint

101 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

14.9756558824

Carbon footprint of the manufacturing phase [a1 to a3]

15 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.0150957529

Carbon footprint of the distribution phase [a4]

0 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.0008631847

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

85.84

Carbon footprint of the use phase [b2, b3, b4, b6]

86 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.0923990294

Carbon footprint of the end-of-life phase [c1 to c4]

0.1 kg CO2 eq.

Pvc free

Yes

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

100.9240138494

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Scip number

ab7a5df6-4d23-4fb1-96de-7c15d64130aa

Pvc free

Yes

End of life manual availability

ENVEOLI2011013EN

Take-back

No

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • End of Life Manual

  • Operating Manuals

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Declaration of Conformity (Sustainability)

  • Software - Release

Important: Some software files may need a mySchneider or Club login to download.