TeSys LR.D Thermal Overload Relays TeSys Deca, 63...80A, class 10A

Home ProductsIndustrialTeSysThermal Overload Relays

TeSys LR.D Thermal Overload Relays TeSys Deca, 63...80A, class 10A

Item Number: LRD3363

Datasheet

Product Dimensions

Width icon

Width70 mm

Height icon

Height81 mm

Depth icon

Depth115 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

differential thermal overload relay

Product compatibility

  • LC1D80
  • LC1D95

Warranty

18 months

Physical

Mounting support

  • plate, with specific accessories
  • rail, with specific accessories
  • under contactor

[ue] rated operational voltage

1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

Control type

  • red push-button: stop
  • blue push-button: reset

Connections - terminals

  • power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible without cable end
  • power circuit: screw clamp terminals 1 cable(s) 4-35 mm² flexible with cable end
  • power circuit: screw clamp terminals 1 cable(s) 4-35 mm² solid without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible without cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² flexible with cable end
  • control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm² solid without cable end

Height

81 mm

Width

70 mm

Depth

115 mm

Net weight

0.51 kg

Climatic withstand

conforming to IACS E10

Ip degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for operation

-20...60 °C without derating conforming to IEC 60947...4-1

Ambient air temperature for storage

-60...70 °C

Standards

  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
  • GB/T 14048.5
  • EN 50495

Product certifications

  • IEC
  • UL
  • CSA
  • CCC
  • EAC
  • ATEX INERIS
  • UKCA

Reach free of svhc

Yes

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP110101EN

Eu rohs directive

Compliant

Reach regulation

Free of Substances of Very High Concern above the threshold

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

12

Legacy weee scope

In

At least in Europe

Package 3 bare product quantity

192

Average percentage of recycled plastic content

0 %

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product name

  • TeSys LRD
  • TeSys Deca

Device short name

LRD

Relay application

motor protection

Network type

  • DC
  • AC

Thermal overload class

class 10A conforming to IEC 60947-4-1

Thermal protection adjustment range

63...80 A

[ui] rated insulation voltage

  • power circuit: 1000 V conforming to IEC 60947-4-1
  • power circuit: 600 V conforming to CSA
  • power circuit: 600 V conforming to UL

Network frequency

0...400 Hz

Tripping threshold

1.14 +/- 0.06 Ir conforming to IEC 60947-4-1

Auxiliary contact composition

1 NO + 1 NC

[ith] conventional free air thermal current

5 A for signalling circuit

Permissible current

  • 0.72 A at 500 V AC-15 for signalling circuit
  • 0.06 A at 440 V DC-13 for signalling circuit

Associated fuse rating

  • 4 A gG for signalling circuit
  • 4 A BS for signalling circuit

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

Phase failure sensitivity

tripping current 130 % of Ir on two phase, the last one at 0

Temperature compensation

-20...60 °C

Tightening torque

  • control circuit: 1.7 N.m - on screw clamp terminals
  • power circuit: 9 N.m - on screw clamp terminals

Compatibility code

LRD

Flame retardance

V1 conforming to UL 94

Mechanical robustness

  • vibrations: 6 Gn conforming to IEC 60068-2-6
  • shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength

2.2 kV at 50 Hz conforming to IEC 60947-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

8.000 cm

Package 1 width

9.000 cm

Package 1 length

12.000 cm

Package 1 weight

512.000 g

Unit type of package 2

S02

Number of units in package 2

12

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

6.470 kg

Unit type of package 3

P06

Number of units in package 3

192

Package 3 height

75.000 cm

Package 3 width

60.000 cm

Package 3 length

80.000 cm

Package 3 weight

114.468 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

6 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

3.012824590856316

Carbon footprint of the manufacturing phase [a1 to a3]

3 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.11399705911971895

Carbon footprint of the distribution phase [a4]

0.1 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.06103430356206878

Carbon footprint of the installation phase [a5]

0.1 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

1.8963357840065684

Carbon footprint of the use phase [b2, b3, b4, b6]

2 kg CO2 eq.

Sustainable packaging

Yes

Carbon footprint of the end-of-life phase [c1 to c4]

0.8942442055865407

Carbon footprint of the end-of-life phase [c1 to c4]

0.9 kg CO2 eq.

F-gas free

N/A

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

5.978435943131213

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

End of life manual availability

ENVEOLI1101001

Take-back

No

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Installation Instruction

  • Declaration of Conformity

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.