TeSys LR9 Overload relay TeSys LRD, motor protection, withstand 6kV impulse and 2kV surge, 1.6A to 8A, electronic, thermal

TeSys LR9 Overload relay TeSys LRD, motor protection, withstand 6kV impulse and 2kV surge, 1.6A to 8A, electronic, thermal

Item Number: LR9D08

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height72.5 mm

Depth icon

Depth79.9 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

electronic thermal overload relay

Product compatibility

  • LC1D12
  • LC1D32
  • LC1D38
  • LC1D09
  • LC1D25
  • LC1D18

Physical

Power consumption in w

300 mW

Mounting support

  • under contactor
  • plate, with specific accessories
  • rail, with specific accessories

[ue] rated operational voltage

  • 690 V for power circuit
  • 660 V for signalling circuit

Control type

  • red push-button: stop and manual reset
  • white 2 microswitches: adjustable trip class
  • red knob: automatic reset
  • white dial: full-load current adjustment

Connections - terminals

  • control circuit: screw clamp terminals 1 cable 2.5-2.5 mm² - cable stiffness: solid or flexible - without cable end
  • power circuit: screw clamp terminals 1 cable 16-16 mm² - cable stiffness: solid or flexible - without cable end

Height

72.5 mm

Width

45 mm

Depth

79.9 mm

Net weight

0.18 kg

Standards

  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
  • GB/T 14048.5

Product certifications

  • IECEE CB Scheme
  • UL
  • CSA
  • CCC

Ip degree of protection

IP20 front face conforming to IEC 60529

Ambient air temperature for operation

-25...70 °C conforming to IEC 60255...8

Ambient air temperature for storage

-55...80 °C

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Circularity profile

N/A

California proposition 65

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Others

Life cycle assessment data

No

If one of the deliverables is not relevant please give the reason

Brand Label

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 2 bare product quantity

30

Product name

TeSys LRD

Device short name

LR9D

Relay application

motor protection

Thermal overload class

class 5…30

Thermal protection adjustment range

1.6...8 A

[ui] rated insulation voltage

  • power circuit: 1000 V
  • signalling circuit: 690 V

Tripping threshold

1.25 In conforming to IEC 60947-4-1

Time range

1.5...4 min - automatic reset time

[ith] conventional free air thermal current

5 A for signalling circuit

Associated fuse rating

  • 5 A gG for signalling circuit
  • 5 A BS for signalling circuit

[uimp] rated impulse withstand voltage

6 kV

Phase failure sensitivity

phase difference > 40% 3-3 s conforming to IEC 60947-4-1

Electromagnetic compatibility

  • surge withstand: 2 kV common mode conforming to IEC 61000-4-5
  • resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2
  • immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3
  • immunity to fast transients: 2 kV conforming to IEC 61000-4-4

Tightening torque

  • control circuit: 0.8 N.m on screw clamp terminals
  • power circuit: 3.1 N.m on screw clamp terminals

Operating altitude

2000 m without derating

Mechanical robustness

  • vibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6
  • shocks 11 ms: 15 gn conforming to IEC 60068-2-7

Dielectric strength

6 kV 50 Hz conforming to IEC 60255-5

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

5.300 cm

Package 1 width

7.600 cm

Package 1 length

9.100 cm

Package 1 weight

209.000 g

Unit type of package 2

S02

Number of units in package 2

30

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

6.668 kg

Packaging made with recycled cardboard

No

Packaging without single use plastic

No

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

F-gas usage performance

N/A

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Minimum percentage of recycled plastic content

0
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity