TeSys LR.D Electronic Thermal Overload Relay TeSys Deca, 60...100A, class 10...20

Home ProductsIndustrialTeSysElectronic Thermal Overload Relay

TeSys LR.D Electronic Thermal Overload Relay TeSys Deca, 60...100A, class 10...20

Item Number: LR9D67

Datasheet

Product Dimensions

Width icon

Width115 mm

Height icon

Height118 mm

Depth icon

Depth125 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

electronic thermal overload relay

Product compatibility

  • NSX circuit breaker
  • LC1D115
  • LC1D150

Warranty

18 months

Physical

Mounting support

  • under contactor
  • rail

[ue] rated operational voltage

690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

Control type

  • red push-button: stop
  • blue push-button: reset

Connections - terminals

  • power circuit: bars
  • control circuit: screw clamp terminals 1 cable(s) 0.5-1.5 mm² flexible without cable end
  • control circuit: screw clamp terminals 2 cable(s) 0.5-1.5 mm² flexible without cable end
  • alarm circuit: screw clamp terminals 1 cable(s) 0.5-1.5 mm² flexible without cable end

Height

118 mm

Width

115 mm

Depth

125 mm

Net weight

0.9 kg

Climatic withstand

conforming to IACS E10

Ip degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for operation

-20...60 °C without derating conforming to IEC 60947...4-1

Ambient air temperature for storage

-60...70 °C

Standards

  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
  • GB/T 14048.5

Product certifications

  • UL
  • CSA
  • CCC
  • UKCA

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2212018

Circularity profile

ENVEOLI2212018

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Commercial status history

  • SESA301466
  • Thu Mar 20 03:40:00 CET 2025
  • From Import Local
  • From 08 to 14

Life cycle assessment data

Yes

Substance regulation data deliverable

Yes

Package 1 bare product quantity

1

Package 3 bare product quantity

48

Package 2 bare product quantity

3

Product name

  • TeSys LRD
  • TeSys Deca

Device short name

LR9D

Relay application

motor protection

Network type

AC

Thermal overload class

class 10/20 conforming to IEC 60947-4-1

Signalling function

alarm

Thermal protection adjustment range

60...100 A

[ui] rated insulation voltage

  • power circuit: 1000 V conforming to IEC 60947-4-1
  • power circuit: 600 V conforming to CSA
  • power circuit: 600 V conforming to UL

Network frequency

50...60 Hz

[us] rated supply voltage

24 V DC

Supply voltage limits

17...32 V

Tripping threshold

  • 1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1
  • 1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1

Auxiliary contact composition

1 NO + 1 NC

[ith] conventional free air thermal current

5 A for signalling circuit

Associated fuse rating

  • 4 A gG for signalling circuit
  • 4 A BS for signalling circuit

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

Phase failure sensitivity

tripping in 4 s +/- 20 % conforming to IEC 60947-4-1

Temperature compensation

-20...60 °C

Switching capacity in ma

0...150 mA

Maximum voltage drop

<2.5 V closed state

Tightening torque

  • alarm circuit: 0.45 N.m - on screw clamp terminals
  • power circuit: 18 N.m - on bars M8
  • control circuit: 1.2 N.m - on screw clamp terminals

Compatibility code

LR9D

Operating altitude

<= 2000 m without derating

Mechanical robustness

  • vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
  • shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength

1.89 kV at 50 Hz conforming to IEC 60947-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

15.000 cm

Package 1 width

15.500 cm

Package 1 length

13.000 cm

Package 1 weight

904.000 g

Unit type of package 2

S02

Number of units in package 2

3

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

2.972 kg

Unit type of package 3

P06

Number of units in package 3

48

Package 3 height

75.000 cm

Package 3 width

80.000 cm

Package 3 length

60.000 cm

Package 3 weight

55.552 kg

Packaging without single use plastic

No

Packaging made with recycled cardboard

Yes

Scip number

d5a17874-1166-4927-b008-33d15e304a41

Green premium status for reporting

Green Premium product

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Pvc free

Yes

Pvc free

Yes

F-gas usage performance

N/A

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

133

Global warming ; total life cycle​

133 kg CO2 eq.

Minimum percentage of recycled plastic content

0
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Data Bulletin

  • End of Life Manual

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity