TeSys D Contactor TeSys Deca, 3P(3NO), AC-3/AC-3e, <=440V, 80A, 24V DC wide range coil

TeSys D Contactor TeSys Deca, 3P(3NO), AC-3/AC-3e, <=440V, 80A, 24V DC wide range coil

Item Number: LC1D80BW

Datasheet

Product Dimensions

Width icon

Width85 mm

Height icon

Height127 mm

Depth icon

Depth186 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 300 V DC 25...400 Hz
  • power circuit: <= 690 V AC
[ie] rated operational current
  • 125 A (at <60 °C) at <= 1000 V AC AC-1 for power circuit
  • 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 10 Mcycles
Electrical durability
  • 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
  • 1.5 Mcycles 80 A AC-3 at Ue <= 440 V
  • 1.5 Mcycles 80 A AC-3e at Ue <= 440 V
Connections - terminals
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end
  • power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end
  • power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end
  • power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end
  • power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end
  • power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • CSA C22.2 No 14
  • UL 60947-4-1
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • IEC 60335-1:Clause 30.2
Product certifications
  • CCC
  • UL
  • CB Scheme
  • CSA
  • CE
  • UKCA
  • Marine
  • EAC
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand conforming to IACS E10 exposure to damp heat
Height 127 mm
Width 85 mm
Depth 186 mm
Net weight 2.59 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1102005EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Legacy weee scope In
At least in Europe
Package 1 bare product quantity 1
Average percentage of recycled plastic content 0 %
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Device short name LC1D
Contactor application
  • motor control
  • resistive load
Utilisation category
  • AC-3
  • AC-3e
  • AC-4
  • AC-1
Poles description 3P
[uc] control circuit voltage 24 V DC
Motor power kw
  • 22 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 37 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 45 kW at 415...440 V AC 50/60 Hz (AC-3)
  • 55 kW at 500 V AC 50/60 Hz (AC-3)
  • 45 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 15 kW at 400 V AC 50/60 Hz (AC-4)
  • 22 kW at 220...230 V AC 50/60 Hz (AC-3e)
  • 37 kW at 380...400 V AC 50/60 Hz (AC-3e)
  • 45 kW at 415...440 V AC 50/60 Hz (AC-3e)
  • 55 kW at 500 V AC 50/60 Hz (AC-3e)
  • 45 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
  • 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
  • 15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 30 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 10 A (at 60 °C) for signalling circuit
  • 125 A (at 60 °C) for power circuit
Irms rated making capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 640 A 40 °C - 10 s for power circuit
  • 990 A 40 °C - 1 s for power circuit
  • 135 A 40 °C - 10 min for power circuit
  • 320 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 200 A gG at <= 690 V coordination type 1 for power circuit
  • 160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
  • 5.1 W AC-3
  • 12.5 W AC-1
  • 5.1 W AC-3e
[ui] rated insulation voltage
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • power circuit: 1000 V conforming to IEC 60947-4-1
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type DC wide range
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.75...1.2 Uc (-40-55 °C):operational DC
  • 0.1...0.3 Uc (-40-70 °C):drop-out DC
  • 1...1.2 Uc (55-70 °C):operational DC
Inrush power in w 22 W (at 20 °C)
Hold-in power consumption in w 22 W at 20 °C
Operating time
  • 95...130 ms closing
  • 20...35 ms opening
Time constant 75 ms
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
  • power circuit: 12 N.m - on connector hexagonal screw head 4 mm
  • control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Contact compatibility M9
Maximum motor phase current 80 A
[uc] control circuit voltage 24 V
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • shocks contactor open (8 Gn for 11 ms)
  • vibrations contactor closed (3 Gn, 5...300 Hz)
  • shocks contactor closed (10 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 11.2 cm
Package 1 width 16.0 cm
Package 1 length 22.6 cm
Package 1 weight 2.659 kg
Unit type of package 2 S02
Number of units in package 2 2
Package 2 height 15.0 cm
Package 2 width 30.0 cm
Package 2 length 40.0 cm
Package 2 weight 5.62 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 176 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 17.19547636535516
Carbon footprint of the manufacturing phase [a1 to a3] 17 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.33922115667609654
Carbon footprint of the distribution phase [a4] 0.3 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.4863785858697323
Carbon footprint of the installation phase [a5] 0.5 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 151.15110507246374
Carbon footprint of the use phase [b2, b3, b4, b6] 151 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 6.414934876649745
Carbon footprint of the end-of-life phase [c1 to c4] 6 kg CO2 eq.
Pvc free Yes
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 175.58711605701447
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Pvc free Yes
End of life manual availability N/A
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • Data Bulletin

  • Technical illustration

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.