TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 40A, 36VDC standard coil
Item Number: LC1D40ACD
Specifications
Design
Range
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
- power circuit: <= 690 V AC 25...400 Hz
- power circuit: <= 300 V DC
[ie] rated operational current
- 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability
Electrical durability
- 0.7 Mcycles 60 A AC-1 at Ue <= 440 V
- 1.5 Mcycles 40 A AC-3 at Ue <= 440 V
- 1.5 Mcycles 40 A AC-3e at Ue <= 440 V
Connections - terminals
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
- power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end
- power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end
- power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end
- power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end
- power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid without cable end
- power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid without cable end
Insulation resistance
Mounting support
- rail
- plate
Standards
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- CSA C22.2 No 14
- UL 60947-4-1
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- IEC 60335-1:Clause 30.2
Product certifications
- CCC
- UL
- CB Scheme
- CSA
- CE
- UKCA
- Marine
- EAC
Ip degree of protection
Climatic withstand
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height
Width
Depth
Net weight
Reach regulation
Reach free of svhc
Eu rohs directive
Mercury free
Rohs exemption information
China rohs regulation
Environmental disclosure
Circularity profile
California proposition 65
Others
Package 1 bare product quantity
Substance regulation data deliverable
Life cycle assessment data
Device short name
Contactor application
- motor control
- resistive load
Utilisation category
- AC-4
- AC-1
- AC-3
- AC-3e
Poles description
[uc] control circuit voltage
Motor power kw
- 18.5 kW at 380...400 V AC 50/60 Hz (AC-3)
- 11 kW at 220...230 V AC 50/60 Hz (AC-3)
- 22 kW at 415...440 V AC 50/60 Hz (AC-3)
- 22 kW at 500 V AC 50/60 Hz (AC-3)
- 30 kW at 660...690 V AC 50/60 Hz (AC-3)
- 9 kW at 400 V AC 50/60 Hz (AC-4)
- 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 11 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 22 kW at 415...440 V AC 50/60 Hz (AC-3e)
- 22 kW at 500 V AC 50/60 Hz (AC-3e)
- 30 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
- 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
- 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 3 hp at 115 V AC 50/60 Hz for 1 phase motors
- 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Compatibility code
Pole contact composition
Protective cover
[ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 60 A (at 60 °C) for power circuit
Irms rated making capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
- 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
[icw] rated short-time withstand current
- 320 A 40 °C - 10 s for power circuit
- 720 A 40 °C - 1 s for power circuit
- 72 A 40 °C - 10 min for power circuit
- 165 A 40 °C - 1 min for power circuit
- 100 A - 1 s for signalling circuit
- 120 A - 500 ms for signalling circuit
- 140 A - 100 ms for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 80 A gG at <= 690 V coordination type 1 for power circuit
- 80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
Power dissipation per pole
- 2.4 W AC-3
- 5.4 W AC-1
- 2.4 W AC-3e
[ui] rated insulation voltage
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- signalling circuit: 690 V conforming to IEC 60947-1
- signalling circuit: 600 V CSA certified
- signalling circuit: 600 V UL certified
- power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category
Pollution degree
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.1...0.3 Uc (-40-70 °C):drop-out DC
- 0.75...1.25 Uc (-40-60 °C):operational DC
- 1...1.25 Uc (60-70 °C):operational DC
Inrush power in w
Hold-in power consumption in w
Operating time
- 50 ±15 % ms closing
- 20 ±20 % ms opening
Time constant
Maximum operating rate
Tightening torque
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25-35 mm² hexagonal screw head 4 mm
- power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1-25 mm² hexagonal screw head 4 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
Minimum switching voltage
Minimum switching current
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Contact compatibility
Protective treatment
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- vibrations contactor closed (4 Gn, 5...300 Hz)
- shocks contactor closed (15 Gn for 11 ms)
- shocks contactor open (10 Gn for 11 ms)
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Packaging made with recycled cardboard
Packaging without single use plastic
Green premium status for reporting
Sustainable packaging
Weee
Pvc free
Pvc free
F-gas usage performance
Take-back
Take-back
Product contributes to saved and avoided emissions
Removable battery
Global warming ; total life cycle
Carbon footprint (kg.eq.co2 per cr, total life cycle)
Minimum percentage of recycled plastic content
Documents & downloads
hide show-
All
-
CAD Files and Packs
-
Technical Data Catalogues
-
Data Bulletin
-
Installation Instruction
-
End of Life Manual
-
Environmental Disclosure
-
Technical illustration
-
Certificates (MSDS)
-
Declaration of Conformity